August
13,
2018 7044-225I
9
3100 Insert ACC
In Canada a full length 6 inch (152mm) S635 flue liner required as per ULC S628.
In USA a minimum 5 ft length (1.82m), 6 inch (152mm) diameter flue liner is required as per UL 1482.
SIDE TRIM
SIDE W
ALL
TOP TRIM
27-1/4 in
(692mm)
32-1/4 in
(819mm)
HEARTH
EXTENSION
USA 16-3/4 in (171mm)
CANADA
24-3/4 in (629mm)
40-11/16 in
(1033mm)
FIREPLA
CE FR
ONT SURF
ACE
USA 23-1/2
CANADA 25-1/2 (648mm)
HEARTH EXTENSION
51 7/16
1306mm
12in max
MANTEL
See next page for thermal protection
calculations
Optional
Mantel
Deflector
FIREPLA
CE FR
ONT SURF
ACE
USA 23-1/2
CANADA 25-1/2 (648mm)
HEARTH EXTENSION
41 7/16
1052mm
12in max
MANTEL
See next page for thermal protection
calculations
Without Mantel Deflector
With Mantel Deflector
B. Clearances to Combustibles
United States and Canada (UL and ULC)
C
D
A
B
Minimum Opening Dimensions
Inches
Millimeters
A
Height
22-3/4
578
B
Front Width
28-7/8
733
C
Back Width
24-1/8
613
D Depth
14-1/2
368
NOTE:
Minimum opening dimensions include a 1/4”
(6mm) clearance around unit.
NOTE:
If trim measurement is over 3/4 in (19mm)
in depth use mantle or side clearances to
combustibles.
NOTE:
Clearances may only be reduced by means
approved by the regulatory authority having
jurisdiction
Fire Risk.
•
Comply with all minimum clearances to
combustibles as specified.
•
Failure to comply may cause house fire.
WARNING