2100 Millennium Wood Stove (ACC)
R
D. Chimney Termination Requirements
Follow manufacturer’s instructions for clearance, securing
flashing and terminating the chimney.
•
Must have an approved and listed cap
•
Must not be located where it will become plugged by
snow or other material
• Must terminate at least 3 feet (91cm) above the roof
and
at least 2 feet (61cm) above any portion of the
roof within 10 feet (305cm).
• Must be located away from trees or other struc-
tures
These are safety requirements and are not meant to assure proper flue draft.
Figure 17.1
E. 2-10-3 Rule
Figure 17.2
NOTE:
• Chimney performance may vary.
• Trees, buildings, roof lines and wind conditions affect
performance.
• Chimney height may need adjustment if smoking or
overdraft occurs.
3 ft. (91cm)
Minimum
Less than 10 ft. (305cm)
2 ft. (61cm)
3 ft. (91cm)
Minimum
10 ft. (305cm) To Nearest Roofline
2 ft. (61cm)
Pitched Roof
10 ft. (305cm) or more
3 ft. (91cm) Minimum
Less than 10 ft. (305cm)
2 ft. (61cm)Minimum
3 ft. (91cm) Minimum
Wall or Parapet
Flat Roof