2100 & 4300 Millennium ACC Wood Burner

GENERAL INSTRUCTIONS FOR FLUE SYSTEM

 

1.QF.1D

 

ƒ

 Flue pipe installed crimp/narrow end down

 

ƒ

 Outer casings installed crimped/narrow end up. (Critical when exposed above the roof)

 

ƒ

 Inner casings - direction not critical

 

ƒ

 Flue pipes   - seal all joints including firebox spigot.

 

- fix with a minimum of 3 stainless steel rivets

 

ƒ

 Flue pipe spacers - affix to flue pipe

 

ƒ

 Flue system termination point - 

Refer to AS/NZS 2918:2001 4.9.1, see Fig. 9.

 

ƒ

 Flue pipe shall extend not less than 4.6m above top of the floor protector as per

 

AS/NZS 2918:2001 4.9.1(a)

 

ƒ

 Façade or chase systems  -  same rule applies as above.

 

ƒ

 Roof penetration and flashing method refer to NZ Building Code E2.(From 01/07/05)

 

Note: These instructions apply to 150mm diameter flue pipe systems as tested to

 

AS/NZS 2918:2001

 

1.  Either locate the appliance in position or by measuring at the ceiling mark the flue pipe centre 

position. Check that the outer casing is unobstructed through the attic space or roof area.

 

2.   Spike the centre with a nail. Transfer this position to the next surface above. Plumb bob/laser.

 

3.   Cut out the ceiling penetration hole – square or rectangle – short axis equals outer casing 

diameter plus 50mm, long axis as required. See Table 5 . Perform the same at the roof 

penetration.

 

4.   Frame out the hole with minimum  75 x 50 timber or as required  for roofing material. Minimum 

requirement at roof penetration see NZ Building Code E2 Acceptable Solution (from 01/07/05).

 

5.   Install the outer casing so that :-

 

(i) 

lower end is flush with the underside of the ceiling material and

 

(ii) 

with the addition of metal “L” brackets, affix to the outer casing at 90 degrees secure the outer 

casing centrally to the ceiling and roof nogs.  Alternatively substitute the “L” brackets for 25mm 

thick non heat sensitive packers. Secure the outer casing through the packers with horizontal 

fixings to the nogs. Refer to the General Instruction for termination height. The option of outer 

casing slips to be taken into account.

 

6.   Flash the outer casing to the roof material with the appropriate approved flashing.

 

7.  If using an outer/inner casing combination, now install the inner casing ensuring it extends a 

minimum 200mm above the high side of the roof penetration. If not using a combination see ‘11’ 

below.

 

8.   Refer to Firebox Installation, points 1 & 2.

 

9.   Prepare the ceiling plate and place upside down over the flue spigot.

 

10. Install the flue pipes by preferred method – either up or down the outer casing. Affix each length 

per the notes in General Instructions (above). Extend the flue pipe  above the outer

 

casing to suit the casing cover/cowl assembly.

 

11. If the inner casing has not been installed, install now. Refer to 7 above  for minimum height.

 

12. Install the cowl assembly, i.e. Top spacer, casing cover and cowl.

 

13. Position and secure the ceiling plate with the screws and spacers.

 

14. Wipe the flue pipe to remove finger marks.

 

15. Refer to Firebox Installation, point 3.

 

16. If flue offset is required, refer to AS/NZS 2918:2001 4.1

 

Summary of Contents for 21M-ACC-NZ

Page 1: ...30 inclusive For installations with a ceiling angle greater than 30 refer to Fig 6 7 and AS NZS 2918 2001 4 6 3 b Ceiling Plate may vary in size depending on ceiling angle Please specify ceiling pitc...

Page 2: ...mm 271mm 475mm 373mm 660mm 247mm 330mm C L 292mm 527mm 406mm C L L C 729mm 668mm 170mm 108mm Outside Air Connection Fig 2 Quadra Fire 4300 Millenium ACC Wood Burner Dimensions roomfor 14x 875 S N 1 5...

Page 3: ...ESTEDINACCORDANCEWITHAS NZS4013 MAXIMUMAVERAGEHEATOUTPUTBURNINGSOFTWOOD APPROVEDFUEL WETBACK ALLMODELS MANUFACTUREDBY PERFORMANCEMAYVARYFROMTESTVALUESDEPENDINGONACTUAL OPERATINGCONDITIONS U S ENVIRONM...

Page 4: ...0 4300 A Min clearance from firebox to rear wall 150 200 B Min clearance from firebox to side wall 550 400 C Min distance from firebox opening to floor protector front 300 300 D Min distance from fire...

Page 5: ...is being used position now Place the firebox on the floor protector to suit the minimum installation clearances See Fig 3 or 4 2 Seismically restrain the firebox and the floor protector to the floor...

Page 6: ...t roof penetration see NZ Building Code E2 Acceptable Solution from 01 07 05 5 Install the outer casing so that i lower end is flush with the underside of the ceiling material and ii with the addition...

Page 7: ...sing cover is necessary minimum 25mm gap between flue pipe casing combustible material Non combustible material Hebel block or 12mm Promina board or similar under the flashing 25 25 Approved Flashing...

Page 8: ...b Fig 4 6 downward distance of casing and 3 x flue distance of the ceiling plate ADD Cowl Casing Cover Spider Bracket Approved Flashing A Ceiling Plate Batten A 3 x flue pipe Ceiling flue pipe Fig 7...

Page 9: ...legs from the bracket 5B leaving the entral tongue to locate inside the flue outlet only Two tabs are provided and if folded back at 90 degrees the bracket and Flue Mounted Shield will mount lower ont...

Page 10: ...ESULT IN HAZARDOUS CONDITIONS WHERE SUCH ACTION IS CONSIDERED THE MANUFACTURER SHOULD BE CONSULTED IN THE FIRST INSTANCE CAUTIONS CRACKED AND BROKEN COMPONENTS e g GLASS PANELS OR CERAMIC TILES MAY RE...

Page 11: ...October 12 2015 7037 141D Page 11 2100 4300 Millennium ACC Wood Burner Service And Maintenance Log Date of Service Performed By Description of Service...

Page 12: ...verage under this manufacturer s warranty begins on the date of first occupancy of the dwelling or six months after the sale of the product by an independent authorized HHT dealer distributor whicheve...

Page 13: ...ents not supplied with the appliance or any other components not expressly authorized and approved by HHT 8 modification of the appliance not expressly authorized and approved by HHT in writing and or...

Page 14: ...Page 14 7037 141D October 12 2015 2100 4300 Millennium ACC Wood Burner Homeowner s Notes...

Page 15: ...C Wood Burner Service Parts 21M ACC AU 21M ACC NZ Beginning Manufacturing Date July 2012 Ending Manufacturing Date Active R Part number list on following pages 2100 Millennium Wood Stove Advanced Comb...

Page 16: ...4 1 2 x 1 1 4 Qty 9 Req 4 2 Brick 5 3 4 x 4 1 2 x 1 1 4 Qty 3 Req 4 3 Brick 8 x 4 1 2 x 1 1 4 Qty 2 Req 4 4 Brick see diagram Qty 1 Req 4 5 Brick see diagram Qty 1 Req Brick Uncut Pkg of 1 832 0550 Pk...

Page 17: ...6 7 Air Control Rod Guide 7033 210 16 8 Timer Only Replacement Assembly SRV480 1940 Y 16 9 Timer Arm Assembly 7033 034 Y 16 10 Door Gasket Front Air Timer Door 7033 282 Y 17 1 Door Assembly Black SRV7...

Page 18: ...provide model number and serial number All parts listed in this manual may be ordered from an authorized dealer Stocked at Depot ITEM DESCRIPTION COMMENTS PART NUMBER Gasket Glass Tape 5 FT 832 0460...

Page 19: ...19 2100 4300 Millennium ACC Wood Burner Service Parts R 43M ACC NZ Beginning Manufacturing Date July 2009 Ending Manufacturing Date Active Wood Stove Part number list on following page 43M ACC NZ 1 2...

Page 20: ...9 1 2 832 3390 Y 7 Tube Support Rack 7033 148 8 Baf e Fiber Board 9 1 2 W x 15 3 4 H Qty 2 SRV7037 112 Y 9 Brick Retainer 7033 149 10 Tube Channel Assembly Manifold Tubes SRV7033 023 Y 11 Label Burn R...

Page 21: ...T NUMBER 16 Brick Assembly Complete Set Pkg of 20 SRV7037 003 16 1 Brick 9 x 4 5 x 1 25 Qty 12 Reg 16 2 Brick 6 x 4 5 Qty 4 Reg 16 3 Brick 9 x 4 5 with angle Qty 1 Reg 16 4 Brick 9 x 3 with angle Qty...

Page 22: ...Stocked at Depot ITEM DESCRIPTION COMMENTS PART NUMBER 18 1 Door Assembly Black DR 31 43BK FH 18 2 Hinge Pins 1 2 Black 7000 606 2 18 3 Door Handle Assembly 832 0540 Cam Latch 430 1141 Key Cam Latch 4...

Page 23: ...om your dealer or distributor Stocked at Depot ITEM DESCRIPTION COMMENTS PART NUMBER 19 Baf e Protection Channel SRV7033 298 Component Pack Includes Spring Handles 1 1 2 Inch 2 1 4 Inch Trimount Plug...

Page 24: ...r phone Notes DO NOT DISCARD THIS MANUAL CAUTION Important operating and maintenance instruc tions included Leave this manual with party responsible for use and operation Read understand and follow th...

Reviews: