- 14 -
devices (the devices are ignored when the door is closed). Setting
AF
to 3 allows this connection to
be used for a safety beam input. Other values of
AF
are reserved and disable the
CN7
input when
selected.
ct
Cycle Test. This cycles the door at regular intervals for testing. Default is off.
PG
Push And Go. This automatically completes a cycle if someone begins pushing the door open
manually. Default is off (no push and go). Also see the
d2
parameter.
Cr
Close recycle. This recycles the door open if an obstruction is encountered prior to the door
entering latch check. Default is on.
SL
SLower open speeds. This reduces all open speed settings by approximately 50%, allowing the
use of very slow open speeds if desired. Remaining speeds (open check, hold open, etc.) are not
affected by
SL
. Default is off (use normal open speeds).
LL
Lock present. When the
LL
parameter is on, the control will trigger the lock relay prior to
opening. It will also attempt to unjam the door, if requested (see the
UJ
and
UP
parameters), and
will wait through the unlock delay (see the
UL
parameter) before opening the door. Default is off (no
lock).
HS
Hold Strike. If the
HS
parameter is left off, the lock will be released approximately 1 second after
the door begins opening. This is normally the preferred setting, as it prevents burn out or buzzing of
inexpensive mortise type strikes. If
HS
is turned on, the lock will be held in the released condition for
the total duration of the open cycle, the close cycle, and the latch check delay (see the
LC
parameter). Default is off (do not hold strike through open cycle).
U1-3
User Parameters 1-3. These parameters adjust from 0-99 and are not used in any way by the
control itself. They may be set to any data the installer wishes to save (month/year of installation,
date of last service, technician code, etc.).
SPECIAL NOTES ON SYNCHRONIZED PAIRS
A six-conductor synchronization harness is supplied with paired operators. It is strongly suggested
that this harness be left unplugged until each door of the pair is set up properly and operating
normally as an independent unit. The harness may then be plugged into
SYNC
connector
CN5
on
each control to synchronize the two doors.
Connections for actuating and safety devices as well as the
on/off/hold
switch may be made to
either
control. It is not necessary to connect them to both.
Due to the method used for synchronization, it is not possible to have different values for the
standard delay (
d1
) and the close recycle delay (
d3
). Delays
d1
and
d3
should be set to the same
value in each operator, and must also be set identically on both operators. The push-n-go delay
(
d2
) may be different from
d1
/
d3
, but should also be set identically on both operators. This
restriction does
not
apply to single operators.
Summary of Contents for EZ-4000
Page 8: ... 8 In Swing Out Swing ...
Page 16: ... 16 ...
Page 17: ... 17 ...
Page 18: ... 18 Lock with No Transformer not recommended Lock with Transformer recommended ...
Page 20: ... 20 BEA Technical Support East Region 866 836 1863 West Region 888 419 2564 ...
Page 21: ... 21 Optex Technical Support 800 966 7839 ...
Page 22: ... 22 Optex Technical Support 800 966 7839 904C ...
Page 23: ... 23 ...
Page 26: ... 26 ...