background image

 

SMS Lite 4G

 User Guide 

© 2021 QTech Data Systems Ltd 

 

Inputs and Outputs (I/O) 

The basic I/O connection details are shown in the diagram below. 
Default Setting <input name>:  INP1  INP2  INP3  INP4 
These can be labelled 

 refer to Configuration Instructions. 

 
 
 

 

Close switch contact to turn “INP1” “ON”                        

 

Send “ON” command to 

close 

“RLY1” 

 

                                                                                         

 

operating light

 

Output Relays 

The output relays are normally open devices with a maximum rating of 32V DC at a current of 2A. The 
relays  can  switch  low  DC  voltage,  low  current  devices  directly.  However,  we  recommend  using 
interface relays as they improve future serviceability and are required for higher voltages or currents. 

 

 

Warning 

 DO NOT directly connect to 220V AC voltage. The New Zealand and Australian wiring regulations require 

that any wiring in excess of 32 volts must be carried out or be certified by a registered electrician. Consult your local 

electrical installer for further guidance. 

Summary of Contents for SMS Lite 4G

Page 1: ...SMS Lite 4G User Guide SMS Lite 4G Version 2 0...

Page 2: ...alations 11 Advanced Commands 11 Debouncing Inputs 11 Configuration 12 Clearing the configuration settings 12 Supply Voltage Alarm 12 Operational Commands 12 Inputs 12 Message Paths 13 Alarms 13 Alarm...

Page 3: ...tput Permissions Default 21 Empty Configuration Values 21 Active Alarm Interruption 21 Error Message 21 Case Sensitivity 21 Technical Specifications 22 SMS Lite Specification 22 Configuration Workshee...

Page 4: ...3 Fax 64 3 365 2815 Email support qtech co nz Web www qtech co nz Revision Details Version Date Author Change Description V1 0 10 11 14 IH Original Format V1 1 23 02 15 RH FA Addition of debounce opti...

Page 5: ...ction to current New Zealand telecommunications companies Spark Vodafone 2Degrees and selected Australian Networks including Telstra and Optus but not all frequency band classes Contact QTech for advi...

Page 6: ...ges Carefully remove the SMS Lite cover by prising the side panels close to the retaining dimples Locate the SIM card holder adjacent to the antenna Push the top of the holder in the direction of the...

Page 7: ...relays are normally open devices with a maximum rating of 32V DC at a current of 2A The relays can switch low DC voltage low current devices directly However we recommend using interface relays as the...

Page 8: ...ng procedure to program up to 4 individual phone numbers 1 Locate the PIN Personal Identification Number printed inside your SMS Lite case The PIN in this example is 12345 2 Compose text message to th...

Page 9: ...tput name e g PULSE RLY1 To pulse an output for a defined period of time PULSE output name duration units e g PULSE RLY1 10 mins Where the units can be ms sec min or hr and the maximum duration is 1 d...

Page 10: ...onfigurable inputs Name An identifying name for the input 8 character limit Phones Ph1 Ph4 Which configured phone number s will receive notifications from this input RLY1 RLY2 These are the 2 outputs...

Page 11: ...ands Debouncing Inputs This feature prevents the SMS Lite from sending multiple messages when connected to devices such as float switches which can switch on and off several times before settling due...

Page 12: ...this notification message The supply voltage at site has gone low When the voltage increases above 11 5V DC a supply voltage message will be sent The supply voltage at site has returned to normal Oper...

Page 13: ...mple 5 Output Control Output with Phone 1 OUTPUT TURNS ON OFF OR PULSE Ph1 END OF PROCESS Example 3 Phone 1 Alerted No Response Escalate to Phone 2 After 10 Mins OK INPUT END OF PROCESS INPUT TURNS ON...

Page 14: ...of 3 to be sent this message Other alarm messages Other alarm messages have the following format Alarm has been acknowledged message Site Input alarm has been acknowledged Alarm has not been acknowled...

Page 15: ...s of all inputs and outputs as well as current supply voltage BAL e g Text BAL The SMS Lite will request the prepay account balance information from the cellular operator then forward that message or...

Page 16: ...nd to commands 4 pulses indicate that the SIM card is not inserted 5 pulses indicate that the SMS Lite is not registered to the cellular network 6 pulses mean that the cellular operator is not support...

Page 17: ...the number of pulses in an error code when it is displayed The typical boot sequence when the device starts is as follows The device will turn the indicator status LED on then flash briefly with a nu...

Page 18: ...a test message Send a test message to the device from a phone by creating a new text message addressed to the device s phone number Test Note that no PIN number is required 5 Verify operation If the...

Page 19: ...flashing on and off slowly F If the test pattern is not displayed this means that the device may not be registered on the network or there is a lack of coverage or network unavailability or that the...

Page 20: ...devices An input is active or ON when the input switch is closed and inactive or OFF when the input switch is open 5 The relays are internally protected by solid state snubbers for operating with indu...

Page 21: ...Use this to clear all programming Output Permissions Default If you do not program the phone numbers for an output then each person Ph1 Ph4 will automatically have permission to send control commands...

Page 22: ...y 0 90 non condensing Ingress Protection IP20 water contact must be avoided Power Input voltage 12V 24 V DC Current 13mA 12V DC 9mA 24V DC Power Connector 2 1mm DC socket centre positive I O Digital I...

Page 23: ...erson Ph1 Ph2 Ph3 Ph4 e g Input 1 Input 2 Input 3 Input 4 Name Pump Phones Ph1 Ph2 Ph3 Program the phones which will be included in each input escalation if required e g Output 1 Output 2 Name Fan Pho...

Page 24: ...ion as the conditions in which it is used are beyond our control This is not withstanding warranty of merchantability Additional Information and Support If you have problems try the following Visit th...

Reviews: