Qoltec 53940 User Manual Download Page 13

1) When operating in bypass mode, the UPS beeps every 2 minutes. If the “Function” key is pressed for more 

than 2 seconds, the alarm will not beep (silence function). Press the “Function” key more than 2 seconds 
again to resume the alarm function.

 

2) If the utility power indicator blinks, it shows that the voltage or frequency of the utility power is out of the 

input range of the UPS or there are problems with reversed polarity (L/N) of site wiring or disconnect to the 
ground for protection.

 

3)  The  other  four  display  pages  are  load  percent  page,  actual  load  page,  input  information  page  and  the 

maximum temperature page.

 

 

Notes: When operating in bypass mode, the backup function of the UPS is not available and the power used by the 

load is directly from the utility power via internal EMI filter.

 

 

 

 

Figure 4-4 Bypass Mode

 

 
4.2.4 LCD indication of UPS alarm status and faults

 

In  the  event  of  an  UPS  fault,  UPS  enters  fault  operation  mode,  at  this  point,  the  fault  icon  turns  on 
consistently, the buzzer beeps continuously and the data information area shows current fault code (refer to 
table  4-2),  the  display  on  the  front  panel  is  shown  as  the  figure  4-5,  users  can  switch  to  output  page  by 
pressing function button.

 

 

 

Figure 4-5 Fault display

 

 
When a warning occurred, the fault icon blinks every second, and users can switch to the alarm display page 
shown as the figure 4-6 to check the warning code. 

 

 

Summary of Contents for 53940

Page 1: ...www qoltec com USER MANUAL UPS RACK MODEL 53940 53942...

Page 2: ...rating Principle 5 3 Installation 5 3 1 Unpacking Inspection 5 3 2 Installation Notes 5 3 3 Cable Connection 6 4 Operation 8 4 1 Operation Display Panel 8 4 2 Operation Mode 11 4 3 Operating Instructi...

Page 3: ...ollowing environment Where there is inflammable gas corrosive agents or heavy dust Where the temperature is very high or low above 40 or below 0 or the humidity is very high more than 90 Under direct...

Page 4: ...in batteries of 12V 7AH 3K With a 1A internal charger and 8 or 6 build in batteries of 12V 7AH Long Backup Time 1KS 1KL With a 6 5A internal charger and external battery slot 2KS 2KL With a 5 5A inte...

Page 5: ...filters the output and provides clean AC power to the load 3 Installation 3 1 Unpacking Inspection 1 Open the packing box of UPS and take it out visually examine the unit for transit damage 2 Check ag...

Page 6: ...ic shock Therefore the following steps must be strictly complied with 1 First connect in series the batteries of the pack to ensure proper battery voltage that 1KS 1KL for 36VDC or 24VDC 2KS 2KL for 7...

Page 7: ...ou can choose for one of them to installed a dry contact card You can utilize monitor function of dry contact to manage the power supply directly b SNMP It enables you monitor the UPS remotely through...

Page 8: ...stalled the AS400 card optional PIN1 UPS failure normally open active close PIN2 Summary alarm PIN3 Ground PIN4 Remote shutdown PIN5 Common PIN6 Bypass active relay close PIN7 Low battery PIN8 UPS on...

Page 9: ...e buzzer will beep once the OUTPUT is flashing which means all of bottom are used for UPS setting at this point if the VAC is flashing which means the output voltage is set to enable if the Hz is flas...

Page 10: ...50Hz Capacity graphics section display the capacity of the battery and load Every pane represents 20 capacity As graphics showed above the capacity of the battery is 80 100 5 panes the load reaches 4...

Page 11: ...In order to extend the LCD usage life the backlight will turn off after 1 minute without any switch operation At this point Users just need to touch any button briefly to turn on the backlight 4 2 1...

Page 12: ...le that of the UPS 4 2 2 Battery Mode When operating in the battery mode the display of main page on the front panel is shown as the figure 4 3 The battery indicator and the Inverter indicator are tur...

Page 13: ...mum temperature page Notes When operating in bypass mode the backup function of the UPS is not available and the power used by the load is directly from the utility power via internal EMI filter Figur...

Page 14: ...urn on about 4 seconds A few seconds later the battery indicator inverter indicators will be turn on to indicate that the UPS is working in battery mode 2 Powering down the UPS The operation of poweri...

Page 15: ...r a long period charging is recommended at the intervals 3 months 4 Batteries should not be replaced individually 5 Under normal conditions the battery life lasts 3 to 5 years In case if the battery i...

Page 16: ...the UPS is defective Please contact the distributor or Service center F11 On constantly Beep continuously EPO fault After confirm the equipment safety reset EPO Faults Possible cause Solution Fault W...

Page 17: ...in the range of 46 Hz 54 Hz 2 The output frequency is 50Hz when the input frequency is not in the range of 46 Hz 54 Hz 3 Can be set as 60Hz Battery mode Inverter overload capacity Utility power 25 10...

Page 18: ...nment humidity 20 90 No condensation Altitude Lower than 1000m no derating Over 1000m 1 derating for every 100m rise Storage temperature 15 45 7 4 EMC Item Standard Level ESD IEC61000 4 2 LEVEL4 RS IE...