1.4 Product specification and performance 

 

Electrical performance 

 

Model

 

6KVA 

10KVA 

Rating

 

6kVA/4.8kW 

10kVA/8kW 

Input 

Input system 

Single phase & earth ground 

Voltage range 

(12

0±5)VAC~

 (274

±5)VAC

 

Power factor 

≥0.99

 

Voltage range of bypass 

(6

0±5)VAC

~ (300

±5)VAC

 (default: 80VAC~264VAC Could be 

adjusted by software) 

Output 

Output system 

Single phase & earth ground 

Rated voltage 

230VAC   

 

Power factor 

0.8 

Voltage precision 

±

1% 

Output frequency 

Normal 

mode 

1.The  output  frequency  synchronizes  with  the  input  frequency 

when the input frequency is in the range of    46 Hz~ 54 Hz. 

2.The output frequency is 50Hz when the input frequency is not in 

the range of 46 Hz~ 54 Hz. 

3.Can be set as 60Hz.

 

Battery 

mode 

Inverter overload capacity (Utility 

power, 25

105% 

±5%

 < Load 

 125% 

±

 5% 60s transfer to bypass 

125% 

±5%

 < Load < 135% 

±

 5% 30s transfer to bypass 

Load > 135% 

±

 5%, 100ms transfer to bypass 

Transfer time 

0ms (Normal mode

←→

 Battery mode) 

<4ms (Normal mode

←→

Bypass mode) 

Crest factor 

3:1 

Battery 

Batteries voltage 

192VDC 

Battery quantity 

None 

None 

Battery Type 

Sealed  maintenance-free  lead 

acid  battery  of  battery  voltage 

12V/7AH 

Backup Time (25

Full load 

 5min (Standard) 

Charge current 

5.5A 

5.5A 

Dimensions (L*W*H)mm 

425x190x328 

533x260x501 

Weight (kg) 

65 

75 

 

 

Note1: Output voltage can be set: 200V/208V/220V/230V/240V. 

 
 

 Operating environment 

 

 

 

 
 
Note: If the UPS is installed or used in a place where the altitude is above than 1000m, the output power must be decrease in use, please refer   
to the following: 

 
 

Altitude(M) 

1000  1500  2000  2500  3000  3500  4000  4500  5000 

Load 

100%  95% 

91% 

86% 

82% 

78% 

74% 

70% 

67% 

 

2. Safety Instruction                                                                             

     

 

Even if the interruptible Power System (UPS) is not connected to utility power, the output socket of the UPS may still present 220V/230V 

output voltage. 

 

 

If  it  is  necessary  to  replace  the  external  battery  cord  or  power  cord,  please  purchase  the original  material  from  the  service  center  or 
distributor of our company so as to avoid overheat or spark resulting in fire due to insufficient capacity. 

 

 

Do not let battery or batteries get close to any heating source and do not incinerate battery or batteries, they may explode. 

 

 

Do not open or mutilate the battery or batteries, released electrolyte is highly poisonous and harmful to the skin and eyes. 

Temperature 

Humidity 

Altitude 

Storage 

temperature 

0

-40

 

<95% 

<1000m 

0

-40

 

Summary of Contents for 53923

Page 1: ...0 USER MANUAL Uninterruptible power supply UPS MODEL 53923 53925 www qoltec com EN...

Page 2: ...dure for connecting the battery module models 5 4 Operation 5 4 1 Operation display panel 5 4 2 Operation mode 6 4 2 1 Normal mode 6 4 2 2 Battery mode 6 4 2 3 Bypass mode 7 4 2 4 LCD indication of UP...

Page 3: ...nect strict load especially for the basic equipments in some areas as finance communication government traffic manufacture education and so on This manual is applicable to the following models Type Mo...

Page 4: ...C Battery quantity None None Battery Type Sealed maintenance free lead acid battery of battery voltage 12V 7AH Backup Time 25 Full load 5min Standard Charge current 5 5A 5 5A Dimensions L W H mm 425x1...

Page 5: ...which complies with AWG Standard for the UPS input and output wirings 3 For 10KVA UPS it is recommended to select the UL1015 8AWG 10 mm2 wire or other insulated wire which complies with AWG Standard f...

Page 6: ...2 Set the battery pack breaker in OFF position and connect the 16 pieces of batteries in series To complete the connection by plugging the connector of the external battery cable into the external ba...

Page 7: ...nput range of the UPS The UPS works in battery mode Figure 4 2 Normal Mode 2 If load is more than 105 percent the buzzer beeps twice every second meanwhile the warning icon blinks every second too rem...

Page 8: ...ll the level icons are turn on 1 When operating in bypass mode the UPS beeps every 2 minutes If the Function key is pressed for more than 5 seconds the alarm will not beep silence function Press the F...

Page 9: ...ress the OFF button persistently for more than 1 second to power off the UPS If it bas been set up to work in bypass mode by software the bypass indicator will be turn on to indicate that the UPS is w...

Page 10: ...in twenty second the UPS exits the setting screen automatically 4 6 Troubleshooting In the event of an UPS fault shoot the trouble according to Table 4 1 If the fault still persists please contact our...

Page 11: ...ry second Please contact the distributor or Service center A20 Blink once every second Beep 3 sounds Please check the battery cables connect or not A33 Blink once every second No beep Please contact t...

Page 12: ...ent of RS232 Baud rate 2400bps DB 9 pin assignment Data bit 8 bit Ending bit 1bit Parity bit None RS232 Interface 2 USB introduction Male Female USB pin definition Note When RS232 and USB are provided...

Page 13: ...of discharging the standard charging time for the standard UPS should be at least 12 hours Discharge the battery with the load more than 50 6 Notes for battery disposal and battery replacement 1 Befor...

Page 14: ...1 INSTRUKCJA OBS UGI Zasilacz awaryjny UPS MODEL 53923 53925 www qoltec com PL...

Page 15: ...unkcje wy wietlacza 6 4 2 Wygl d wy wietlacza w poszczeg lnych trybach pracy 6 4 2 1 Tryb normalny 7 4 2 2 Tryb akumulatora 7 4 2 3 Tryb obej cia bypass 8 4 2 4 Komunikaty wy wietlacza LCD podczas wyk...

Page 16: ...ast puj cych modeli Typ Model Wej cie Akumulator D ugi czas podtrzymywani a 6KVA 6KVA Pojedyncza faza N Zewn trzny akumulator 10KVA 10KVA Pojedyncza faza N Zewn trzny akumulator 1 2 Opis cz sto u ywan...

Page 17: ...s autonomii 25 100 obci enia 5min Standard Pr d adowania 5 5A 5 5A Wymiary L W H mm 425x190x328 533x260x501 Waga kg 65 75 2 rodki ostro no ci 1 Przed u yciem produktu uwa nie przeczytaj instrukcj 2 U...

Page 18: ...AWG 3 Dla modelu 10KVAzaleczane jest u ycie przewod w UL1015 8AWG o przekroju 10mm2 lub izolowanych przewod w spe niaj cych standardy AWG 4 Pod cz przewody wej ciowe i wyj ciowe do odpowiednich wej i...

Page 19: ...cisk ON przytrzymaj przez oko o jedn sekund eby w czy UPS jeden sygna d wi kowy 2 Przycisk OFF przytrzymaj przez oko o jedn sekund eby wy czy UPS Wy cza urz dzenie zar wno w trybie normalnym jak i w t...

Page 20: ...rzymaj przycisk F przez oko o pi sekund Je eli po czenie akumulatora z UPS jest prawid owe problem mo e by spowodowany defektem akumulatora lub jego zu yciem Odnie si do rozdzia u 7 Rozwi zywanie prob...

Page 21: ...by wyciszy alarm przytrzymaj ponownie oko o pi sekund aby przywr ci alarm 2 Je eli ikona zasilania sieciowego miga oznacza to e napi cie lub cz stotliwo zasilania sieciowego jest po za normalnym zakre...

Page 22: ...zia a w trybie obej cia bypass wy wietla si ikona obej cia bypass Aby odci moc wyj ciow od cz UPS z r d a zasilania UPS rozpocznie autodiagnoz wszystkie ikony na wy wietlaczu LCD wy wietlaj si przez o...

Page 23: ...lnego 3 Sprawdzanie poprawno ci dzia ania diod LED sprawd czy w trybie normalnym wieci si dioda trybu normalnego a w trybie akumulatorowym dioda trybu akumulatorowego oraz w trybie obej cia bypass dio...

Page 24: ...y Sprawdzi poprawno pod czenia przewodu r wnoleg ego F34 wieci na sta e Sta y sygna d wi kowy Skontaktuj si z dystrybutorem lub centrum serwisowym F35 wieci na sta e Sta y sygna d wi kowy Skontaktuj s...

Page 25: ...kontaktuj si z dystrybutorem lub centrum serwisowym A34 Miga co 1 sek Sygna d wi kowy trwaj cy 1 5 sekundy cznie 3 sygna y Skontaktuj si z dystrybutorem lub centrum serwisowym A35 Miga co 1 sek Sta y...

Page 26: ...unkcje Nadzorowanie stanu zasilacza monitorowanie obci enia stanu i napi cia akumulatora trybu pracy napi cia wej ciowego cz stotliwo ci wej ciowej oraz temperatury wewn trznej zasilacza Ustawienia op...

Page 27: ...jest przeprowadzenie raz na 4 miesi ce procedury ca kowitego roz adowania akumulator w Nale y roz adowa akumulatory z obci eniem wi kszym ni 50 a do automatycznego wy czenia si UPS a nast pnie adowa g...

Reviews: