11. CONNECTING THE ELECTRICAL CABLES.
11.1 Connecting the electrical cables for the SC41xx & SC5xxx models.
a.
4,5 Meter cable for electrical connection between indoor and outdoor unit is delivered with the pac-
kage and is included in the refrigerant piping sleeve (indoor unit).
B.
The electrical cable is provided with an electrical quick connector.
c.
The outdoor unit is also provided with electrical quick connector.
d.
Remove the control cover from the outdoor unit by loosening the screw.
e.
Click the connector of the interior unit into the connector of the exterior unit and secure the cable
to the terminal block with the cable clamp mounted on it.
f.
The earth cable must be connected directly to the metal plate on which the terminal strip is mounted.
The location is indicated with the symbol
Cover
Figure 17
Cover plate
g.
Only connect the power supply cable once the entire installation of the air conditioner has been
completed.
G
TAKE CARE
For models with a capacity < 4.5 kW plug the plug into a wall socket.
For models with a capacity > 4.5 kW connect the power supply cable directly the power source.
Do not use a plug and socket as the high current can damage both the terminals of the plug and
the socket and even cause a fire.
L
N
S
L
N
S
Outdoor unit
Control cover
Screw
Outdoor unit
Plug connector
To indoor unit
or
Secure the cable with cord clamp
‘click’
Figure 18
11.2 Connecting the electrical cables for the S41xx & S5xxx models.
a.
Connect the cable to the indoor unit
4
58