Grid and Load Connection
32
4
Connect the L, N, and PE wires for the load and grid cables.
If you don't strip the ends of wire properly or don’t engage connectors properly,
it may lead to fire.
PE
N
LOAD
L
PE
N
GRID
L
• PE bolt: M4
• Torque for PE bolts: 1.2 to 1.9 N·m
• If the L and N wires are a fine-stranded conductor type, raise the lever and insert the wire,
and then lower the lever to secure the wire.
• If the L and N wires are a single solid conductor type, the wire can be inserted without raising
the lever.
• After connect the wires, make sure the wires are correctly connected. When the wires are
pulled, they should not come out of the connectors.
5
Assemble the sealing nut to secure the cables.