10.3 Model Specifications (400 V Class)
SIEPYEUOQ2A01G AC Drive Q2A Technical Manual
371
Model
Input Voltage
Duty Rating
4453
4568
4675
Outputs
Rated Output Capacity
(kVA)
< 460 V
HD
272
298
398
ND
298
374
444
≧
460 V
HD
330
380
410
ND
380
410
482
Rated Output Current
(A)
< 460 V
HD
414
453
605
ND
453
568
675
≥ 460 V
HD
414
477
515
ND
477
515
605
Overload Tolerance
•
HD: 150% of the rated output current for 60 seconds
•
ND: 110% of the rated output current for 60 seconds
Note:
Derating may be necessary for applications that start and stop
frequently.
Carrier Frequency
HD: 2 kHz without derating the drive capacity.
ND: 2 kHz without derating the drive capacity.
Derate the drive capacity to use values to 5 kHz maximum.
Maximum Output Voltage
Three-phase 380 V to 480 V
Note:
The maximum output voltage is proportional to the input voltage.
Maximum Output Frequency
•
Advanced Open Loop Vector Control (AOLV) and EZ Open Loop
Vector Control (EZOLV): 120 Hz
•
Closed Loop V/f Control (CL-V/f), Closed Loop Vector Control (CLV),
Advanced Open Loop Vector Control for PM (AOLV/PM), and Closed
Loop Vector Control for PM (CLV/PM): 400 Hz
•
V/f Control (V/f), Open Loop Vector Control (OLV), and Open Loop
Vector Control for PM (OLV/PM): 590 Hz
Measures for
Harmonics
DC Reactor
Standard internal characteristics
Braking Device
Braking Transistor
External options
EMC Filter
EMC Filter
IEC61800-3, C3
There is a category C3 EMC filter in the drive.
Power Supply
Rated Voltage/Rated Frequency
•
Three-phase AC power supply 380 V to 480 V at 50/60 Hz
•
DC power supply 513 V to 679 V
Permitted Voltage Fluctuation
-15% to +10%
Permitted Frequency Fluctuation
±5%
Input Power (kVA)
< 460 V
HD
327
370
465
ND
370
465
523
≥ 460 V
HD
335
382
429
ND
468
526
584
*1
The maximum applicable motor output complies with 380 V motor ratings as specified in Annex G of IEC 60947-4-1. The rated
output current of the drive output amps must be equal to or more than the motor rated current.
*2
The maximum applicable motor output complies with 460 V motor ratings as specified in NEC Table 430.250. The rated output
current of the drive output amps must be equal to or more than the motor rated current.
*3
Assumes the value at the rated output current. The input current rating changes when the power supply transformer, input reactor,
wiring connections, or power supply impedance change.
*4
The rated output capacity is calculated with a rated output voltage of 380 V.
*5
The rated output capacity is calculated with a rated output voltage of 460 V.
Summary of Contents for Q2A
Page 2: ...This Page Intentionally Blank 2 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 12: ...12 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 18: ...i 2 Legal Information 18 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 28: ...1 2 Features and Advantages of Control Methods 28 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 64: ...2 9 Installation Methods 64 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 166: ...4 9 Test Run Checklist 166 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 172: ...5 2 European Standards 172 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 173: ...Standards Compliance 5 5 2 European Standards SIEPYEUOQ2A01G AC Drive Q2A Technical Manual 173...
Page 174: ...5 2 European Standards 174 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 175: ...Standards Compliance 5 5 2 European Standards SIEPYEUOQ2A01G AC Drive Q2A Technical Manual 175...
Page 176: ...5 2 European Standards 176 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 258: ...6 2 Modbus Communications 258 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 356: ...8 7 Storage Guidelines 356 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 360: ...9 2 Disposal Instructions 360 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...