Figure 4.
Processor Module Dimension, inch (mm)
The processor module of the LSP-X01 Series sensor can be installed to a 1” bulkhead fitting on the top of
the tank. Alternatively, you may also use the LSP-X01 Series Mounting Bracket (P/N: 50770) for installations
where top tank mount may be to too high for maintenance. In this format, the processor module is installed
in a location away from the tank top to take the advantage of the 32.8-ft cable. Each LSP-X01 Series sensor
is also shipped with a 2” male NPT bulkhead adapter with internal cable gland (pre-installed on transducer
cable) for installations requiring a sealed bulkhead/cable fitting as shown in Figure 5.
Figure 5.
LSP-X01 Series Mounting Bracket (P/N: 50770) w/ 2” male NPT bulkhead adapter
The following is a list of installation guidelines and precautions:
1. Leave a 1-inch space between the transducer module and the tank bottom surface.
2. Do not remove the protective cap and expose the diaphragm directly to the liquid. This may cause
permanent sensor damage.
3. Ensure that installation is not near large vibration locations.