MOUNTING THE DETECTOR

1.

Using three No. 8 flat head screws placed through
the counterbored holes in the detector flange,
secure the detector to the surface location.  Secure
the junction box if necessary.

2.

Remove the cover from the junction box and com-
plete installation of system conduit.  Feed the exter-
nal wiring through the remaining junction box entry
or M25 to 3/4 inch adapter.  Use care not to dam-
age the wires by twisting them when installing the
junction box.

3.

Connect the external wiring to the appropriate ter-
minals and re-install the junction box cover.  See
Figures 3, 4 and 5 for wiring details.

DETECTOR CONNECTIONS

The detector contains two sets of relay contacts:

1.

One set of NO Alarm contacts close upon detec-
tion of smoke.

2.

One set of NC Trouble contacts close when the
detector is powered.

3

95-8366

12-3/4 INCHES (325 MM)

8-1/16 INCHES (205 MM)

3-1/2 INCHES

(89 MM)

4-1/2 INCHES

(114 MM)

A1967

120

°

5/32 INCH DIA. (3)

2-7/16 INCHES

(62 MM)

5-5/16 INCHES (135 MM)

Figure 2—U5005 Dimensions in Inches (MM)

1

2

3

4

5

NORMALLY CLOSED SUPERVISORY CONTACTS

NORMALLY OPEN ALARM CONTACTS

                 AUXILIARY ALARM CONTACTS

+

GROUND

YELLOW
YELLOW
VIOLET
VIOLET
BLACK
RED

TO DETECTOR

1        2        3       4        5        6

TB – 1

TB – 2

TB – 3

NOTE:
CIRCUIT SHOWN IN THE NORMAL STANDBY ENERGIZED MODE

C1192

7

10

8

9

6

Figure 3—Wiring Terminals

Summary of Contents for 30-3003

Page 1: ...ector reverts to normal sensitivity INSTRUCTIONS Explosion Proof Smoke Detector Model 30 3003 PHOTOVOLTAIC SENSOR CELL LENS IRED LIGHT SOURCE ALARM LED LENS SMOKE CHAMBER B1178 Figure 1 Cross Section of Sensing Chamber Assembly Detector Electronics Corporation 2000 8 00 95 8366 03 O2 6K 6K J 6K 7 6K 6K 6K 6K 6K 6K 6K 6K 6K 6K 6X K 6K 6X K 6X K 6X X X O2 6X X O2 1 X O2 O2 hf I4 K O2 O2 I4 6X O2 O2 ...

Page 2: ...ent of an alarm and an LED located on the outer surface of the hous ing is illuminated to provide a visual indication that an alarm condition has occurred The detector is reset by momentarily interrupting input power SPECIFICATIONS OPERATING VOLTAGE 20 to 28 vdc filtered supply with less than 1 4 vpp at 60 to 120 Hz OPERATING CURRENT Standby 10 milliamperes Alarm 35 milliamperes TEMPERATURE RANGE ...

Page 3: ...e junction box cover See Figures 3 4 and 5 for wiring details DETECTOR CONNECTIONS The detector contains two sets of relay contacts 1 One set of NO Alarm contacts close upon detec tion of smoke 2 One set of NC Trouble contacts close when the detector is powered 3 95 8366 12 3 4 INCHES 325 MM 8 1 16 INCHES 205 MM 3 1 2 INCHES 89 MM 4 1 2 INCHES 114 MM A1967 120 5 32 INCH DIA 3 2 7 16 INCHES 62 MM 5...

Page 4: ...atement describing the malfunction must accompany the returned device or component to expedite finding the cause of the fail ure Return all equipment transportation prepaid to the factory in Minneapolis 1 2 3 4 5 AUXILIARY ALARM CONTACTS C NO NC TB 2 TB 3 POWER 2 WIRE CLASS B RECEIVING ZONE CHASSIS GROUND LISTED CONTROL PANEL EOL DEVICE SUPPLIED BY PANEL MANUFACTURER ADD JUMPER GROUND STUD B1193 6...

Reviews: