background image

 

 
 

5

 / 

25

 

                                                                                                      18BQSV0801 
 

 

2. Introduction 

US3000 Plus lithium iron phosphate battery is one of new energy storage products developed and 

produced by Pylontech, it can be used to support reliable power for various types of equipments 

and systems. US3000 Plus is especially suitable for application scene of high power, limited 

installation space, restricted load-bearing and long cycle life. 

US3000 Plus has built-in BMS battery management system, which can manage and monitor cells 
information including voltage, current and temperature. What’s more, BMS can balance cells 
charging and discharging to extend cycle life.   

Multiple batteries can connected in parallel to expand capacity and power in parallel for larger 
capacity and longer power supporting duration requirements.

 

2.1 features: 

 

The whole module is non-toxic, non-polluting and environmentally friendly; 

 

Cathode material is made from LiFePO4 with safety performance and long cycle life; 

 

Battery management system (BMS)has protection functions including over-discharge, 

over-charge, over-current and high/low temperature; 

 

The system can automatically manage charge and discharge state and balance current 

and voltage of each cell; 

 

Flexible configuration, multiple battery modules can be in parallel for expanding capacity 

and power 

 

Adopted self-cooling mode rapidly reduced system entire noise; 
The module has less self-discharge, up to 6 months without charging it on shelf, no memory 
effect, excellent performance of shallow charge and discharge;

 

 

Working temperature range is from -10

 to 50

, (Charging 0~50

; discharging -10~50

with excellent discharge performance and cycle life; 

 

Small size and light weight, standard of 19-inch embedded designed module is comfortable 

for installation and maintenance; 

 

2.2 Specifications 

Summary of Contents for US3000B Plus

Page 1: ...Pylon Technologies Co Ltd Confidential Information Version 1 1 Lithium Iron Phosphate Battery US3000 Plus Product Manual...

Page 2: ...t Pin 8 Definition of RJ11 Port Pin 9 LED Indicators Instructions 10 3 SAFE HANDLING OF LITHIUM BATTERIES GUIDE 11 3 1 Schematic Diagram of Solution 11 3 2 Explanation of Symbol 11 3 3 Tools 12 3 4 Sa...

Page 3: ...s 10 Do not connect battery with PV solar wiring directly 11 The warranty claims are excluded for direct or indirect damage due to items above 12 Any foreign object is prohibited to insert into any pa...

Page 4: ...y QC tab removed or damaged 5 In case of fire only dry powder fire extinguisher can be used liquid fire extinguishers are prohibited 6 Please do not open repair or disassemble the battery except staff...

Page 5: ...e whole module is non toxic non polluting and environmentally friendly Cathode material is made from LiFePO4 with safety performance and long cycle life Battery management system BMS has protection fu...

Page 6: ...44 5 53 5 Charge Voltage V 52 5 53 5 Recommend Charge Discharge Current A 37 Max Charge Discharge Current A 74 Peak Charge Discharge Current A 100A 15sec Communication RS232 RS485 CAN Configuration ma...

Page 7: ...ery is running US3000B does not have this LED light Alarm Alarm light red LED flashing to show the battery has alarm and lighting to show the battery is under protection SOC SOC light 6 green LEDs to...

Page 8: ...uld setup as this 1 0 1 5th 5th battery group s master battery should setup as this 0 1 1 6th 6th battery group s master battery should setup as this 1 1 1 7th 7th battery group s master battery shoul...

Page 9: ...ug Dry Contact Terminal Dry Contact Terminal provided 1 way input and 3 ways output dry contact signal IN GND NO1 COM1 NO2 COM2 NO3 COM3 Input Wake up master battery use 5 12V input DC the circuit has...

Page 10: ...em error Protect ON flash on 0 3s off 3 7s flash on 0 5s off 1 5s BMS function Protection and Alarm Management and Monitor Charge Discharge End Cells Balance Charge Over Voltage Intelligent Charge Mod...

Page 11: ...11 25 18BQSV0801 3 Safe handling of lithium batteries Guide 3 1 Schematic Diagram of Solution 3 2 Explanation of Symbol...

Page 12: ...sulated tools to prevent accidental electric shock or short circuits If insulated tools are not available cover the entire exposed metal surfaces of the available tools except their tips with electric...

Page 13: ...battery package Grounding cable 2 For battery system connects to inverter Two long power cables current capacity 120A and one communication cable for each energy storage system NOTE These three long...

Page 14: ...o 50 C The temperature and humidity is maintained at a constant level There is minimal dust and dirt in the area CAUTION If the ambient temperature is outside the operating range the battery pack stop...

Page 15: ...15 25 18BQSV0801 Put the battery into the cabinet Drive the 4 pcs screws Connect the cables between battery modules Connect the cables to inverter...

Page 16: ...eck all the power cable and communication cable 1 Switch power on Switch on all the battery modules 2 The one with empty Link Port 0 is the Master Battery Module others are slaves 1 master battery con...

Page 17: ...button of master battery to power on all the battery LED light will be on one by one from the Master battery If all the battery LED lights on and then off which means the battery system is good and wo...

Page 18: ...18 25 18BQSV0801...

Page 19: ...19 25 18BQSV0801 Aim at the 4 pare of Location Pin and Location Hole stack the batteries together And hasp the 4 agraffes together...

Page 20: ...20 25 18BQSV0801 Maximum 4 batteries can be athwart stacked One or two batteries can be sidelong stacked Cables connection and batteries system start are same as cabinet installation...

Page 21: ...e system if has grid power it should turn on the inverter at first to avoid current pulse of the inverter add on the battery bank Between battery bank and inverter should install breaker to protect sy...

Page 22: ...22 25 18BQSV0801...

Page 23: ...urrent If current is greater than 100A battery protection will turn on Solution Check whether current is too large or not if it is to change the settings on power supply side c High Voltage If chargin...

Page 24: ...ntion 2 Fire NO WATER Only dry powder fire extinguisher can be used if possible move the battery pack to a safe area before it catches fire 3 Wet Batteries If the battery pack is wet or submerged in w...

Page 25: ...18BQSV0801 Pylon Technologies Co Ltd No 73 Lane 887 ZuChongzhi Road Zhangjiang Hi Tech Park Pudong Shanghai 201203 China T 86 21 51317697 F 86 21 51317698 E service pylontech com cn W www pylontech c...

Reviews: