Automatic DMX Addressing made during setting of the main DMX address may be insufficient for 

in many cases. That is why, in the menu            DMX addresses can be individually set the for 

each of the 64 ballast, and each of the 16 groups (see chapters 4.7.3 or 4.8.2).

After entering the          menu, you can choose number           of the ballast. Using NEXT or 

PREV buttons to navigate, go to the requested number of the ballast, and as indicated the ballast 

will light up. Press ENTER to confirm. Select the desired DMX address for the ballast from the 

scope of 1-512, or choose            to turn off the ballast with DMX control. Number of ballasts is 

determined by the user (see chapter 4.4.). Default setting is the maximum number allowed by the 

standard DALI ballast i.e. 64.

The same procedure applies if you want to set the DMX address of the group (         ). To do that 

you need to go using NEXT button in the same menu to the group option. After choosing group of 

lamps, those ones being members of this pack will light up. The DALI standard can set address 

up to the 16 groups.

4.7. PROGRAMMING OF INDIVIDUAL 

ADDRESS 

DMX 

To set the parameters for all DALI ballasts you need to: choose             from the main menu and 

press ENTER. On the display will appear                   confirm with ENTER. Using NEXT or PREV 

buttons go to the DALI parameter (or one of the groups) you want to and then press ENTER to 

select the desired value. 

In ALL menu you can enter parameter values, but it is not possible to read them. There will always 

be displayed the minimum value, although the real ones may be different. To read the value 

placed on the parameter settings you need to go to a specific individual ballast (see chapter 

4.8.1.)

4.8. MENU dAL       ALL

4.8.1. Determination of parameters for all DALI ballasts

10

Summary of Contents for DMX-DALI Converter

Page 1: ...MANUAL DMX DALI Converter PX175...

Page 2: ...device on loss of DMX signal 4 7 Programming of individual DMX address 4 8 Menu dAL ALL 4 8 1 Determination of parameters for all DALI ballasts 4 8 2 Description of the available DALI parameters 4 8 2...

Page 3: ...dth of 4 standard DIN rail modules adapted for mounting on 35 mm wide DIN rails The PX175 is a device powered with safe voltage 24V however during its installation and use the following rules must be...

Page 4: ...e scrolls menu forward or set the value increases allows to enter programming device mode or approve the set value esc prev next enter After switching on the display of the device shows the version of...

Page 5: ...T NEXT NEXT NEXT NEXT NEXT NEXT ENTER NEXT ENTER ENTER NEXT NEXT ENTER ENTER ENTER NEXT NEXT NEXT NEXT NEXT Ballast settings in the next submenu is described in the following chapters ENTER ENTER NEXT...

Page 6: ...XT NEXT ENTER 4 3 A DETAILED SCHEME OF THE MENU 4 3 1 Menu ALL 4 3 2 Menu Ind This menu allows to set the DMX address of the converter and to set a response of DALI equipment to DMX signal loss see ch...

Page 7: ...NEXT ENTER ENTER NEXT NEXT NEXT ENTER NEXT ENTER NEXT NEXT NEXT ENTER NEXT ENTER NEXT ENTER NEXT ENTER NEXT ENTER NEXT ENTER NEXT NEXT ENTER NEXT ENTER NEXT NEXT ENTER NEXT ENTER NEXT NEXT ENTER NEXT...

Page 8: ...NEXT ENTER NEXT ENTER NEXT NEXT NEXT NEXT NEXT NEXT NEXT NEXT ENTER ENTER ENTER ENTER NEXT ENTER ENTER NEXT NEXT NEXT NEXT ENTER NEXT NEXT NEXT ENTER NEXT ENTER NEXT ENTER NEXT ENTER NEXT ENTER NEXT...

Page 9: ...latively slow compared to the DMX protocol therefore in large installations is recommended Reducing the number of ballasts in the menu to the actual number of lamps in the system Grouping ballasts Rem...

Page 10: ...ppear press ENTER The converter will start automatically search the network in order to give addresses to encountered ballasts The display will start to flash and found ballasts will in turn on Addres...

Page 11: ...gnal diode goes out To set the behavior of the device in case of DMX signal loss you need to After selecting in the menu confirm the selection by pressing ENTER Using NEXT or PREV buttons select an ap...

Page 12: ...lies if you want to set the DMX address of the group To do that you need to go using NEXT button in the same menu to the group option After choosing group of lamps those ones being members of this pac...

Page 13: ...ange 0 254 The lowest brightness level of the lamp 0 disabled 254 100 brightness When it is set to a relatively high level DMX control will respond to the reduction of the value to some specified leve...

Page 14: ...in the SSLparameter see chapter 4 8 2 2 Reset ballast reset To reset the ballast you have to press ENTER when on the screen appears After that display will show press ENTER to accept All these data a...

Page 15: ...ype range 0 255 Displays the type of device 0 means the ballast Physical minimum Level range 1 255 Indicates the minimum lighting level set by the manufacturer Power Failure Range Yes No Reports a pow...

Page 16: ...NTER to accept Then set the device to parameter using NEXT or PREV buttons on and then accept with ENTER All ballasts are members of the selected group To remove the ballast from the group select the...

Page 17: ...NECTION SCHEME 15 power supply 24 V DC power supply 24 V DC DALI Bus DALI Bus Ballasts Ballasts DMX controller DMX controller Consecutive DMX devices e g lamp Consecutive DMX devices e g lamp ground g...

Page 18: ...512 64 24V DC max 250 mA terminal blocks 70 mm 86 mm 60 mm DMX channels DALI channels Power Current consumption Output Terminals Dimensions width height depth 6 SPECIFICATIONS 16...

Page 19: ...er Address of producer declares that the product Name of product Type answers the following product specifications EMC Additional information Krak w 01 01 2009 DECLARATION OF CONFORMITY according to g...

Page 20: ......

Reviews: