background image

DURAWATT

®

 ELECTRIC WATER HEATERS

 

PV500-6   05/13

 

16

8 TROUBLESHOOTING 

GUIDE 

 

PROBLEM 

PROBABLE CAUSE 

CORRECTIVE ACTION 

No hot water 

Thermostat(s) 

Check to assure proper thermostat setting. 

Contactors will not pull in 

Check continuity between all three thermostats or pressure 
controls. Complete circuit. If one is open, it must be replaced. 

Control circuit switch is in OFF position 

Close switch. (Turn to ON position) 

Control circuit fuse blown 

Isolate cause for failure and replace fuse. 

Contactor(s) coil open 

Check continuity. Replace coil if not a complete circuit. 

Time delay sequencer not operating 

Check for 120 volts to coil on first sequencer step. Allow ample 
time for additional steps to energize. If steps do not energize in 
reasonable time, replace only the defective relay step. See 
wiring diagram. 

Proportional sequencer not operating 

Check for 120 volts to line connection (L) on sequencer. Check 
fuse for continuity. See wiring diagram. Consult factory. 

Low water cutoff closed 

Check for open circuit. Check water level in tank. Replace low 
water cutoff if defective. 

Heating elements 

Check for open legs. (See table 2). 

Insufficient hot 

water 

Heater not large enough to satisfy peak 
demands 

Add booster or additional kw input. Consult local PVI 
representative. 

Hot water lines not insulated 

Add insulation; it will protect against heat loss and save on cost 
of operation. 

Power fuse(s) blown 

Check fuses for continuity. Replace if blown. If blown, determine 
cause of break before replacing with same type fuse. 

Contactor(s) not closing 

Check coil for continuity. If defective, replace. 

Thermostat(s) not correctly set 

Check to assure proper thermostat control setting. 

Element(s) not heating 

Check for proper amperage draw. Check for proper ohm 
resistance. Replace if defective. Consult factory. 
(See table 1) 

Burned or 

discolored wires 

Loose connections 

Tighten all connections. If charred, replace wire with wire of 
same type and size. 

Dirty or pitted contactor points 

Remove contactor points and inspect. If dirty, clean with emery 
paper. 

CAUTION

Point must remain flat. If pitted or burned, 

contactor points must be replaced.

 

Blown fuses 

Loose connection. Defective element 

Check all connections for tightness. Check ohm resistance in 
electric elements. Replace. 

High or low 

voltage 

Local utility 

Check with local utility. 

High or low 

amperage 

High or low voltage. Defective element 

Check with local utility. Low amperage, check fuses, tighten 
connections. Check ohm resistance on elements. 

Wire burned or 

melted at 

element 

Loose connections. Water leaking on elements 

Tighten connection and replace wire. Isolate leaking water and 
repair. Replace wire with same type and size. 

 

Summary of Contents for DURAWATT Series

Page 1: ...AD AND FOLLOW THE INFORMATION IN THIS MANUAL AND ALL OTHER PROVIDED INSTRUCTIONS LABELS AND MARKINGS BEFORE INSTALLING OPERATING OR SERVICING THIS UNIT TO THE INSTALLER After installation these instructions must be given to the equipment user or left near the appliance SPECIAL INSTRUCTIONS TO THE OWNER Retain this manual for future reference These instructions contain important information that wi...

Page 2: ...stible Surfaces 3 8 Electronic Low Water Cutoff 4 Optional Equipment 4 1 Shunt Trip Circuit Interrupter 4 2 Time Sequencer 4 3 Proportional Sequencer 5 Start up Procedures and Operation 6 Element Continuity Checks 7 Maintenance 7 1 Flushing 7 2 Draining the Tank 7 3 Sediment Lime Scale Removal 7 4 T P Relief Valve 7 5 Low Water Cutoff 7 6 Electrical Connections 7 7 Replacing Electric Elements 7 8 ...

Page 3: ...agency or qualified electrical contractor WARNING Installation and service must be performed by a qualified installer service agency or qualified electrical contractor who must read and follow the supplied instructions before installing servicing or removing this appliance Refer to the information contained in this manual Improper installation adjustment alteration service or maintenance can cause...

Page 4: ...THE PHYSICALLY HANDICAPPED HOSPITALS AND NURSING HOMES ELDER CARE FACILITIES AND REST HOMES ORPHANAGES AND CHILD CARE FACILITIES OTHER INSTALLATIONS WHERE RESPONSE TO CONTACT WITH HOT WATER MAY BE SLOWER OR WHERE THE DANGER OF HOT WATER CONTACT IS GREATER Thermostatically controlled mixing valves must be used in the design of the potable hot water system Potable hot water should be tempered to no ...

Page 5: ...DURAWATT ELECTRIC WATER HEATERS PV500 6 05 13 5 2 PRODUCT DESCRIPTIONS Without 23 Diameter Tank Access FIGURE 1 With 23 Diameter Tank Access FIGURE 2 ...

Page 6: ...connecting wire 3 Use proper wire size for the ground connection Attach to the bottom ground terminal connection on the terminal block assembly marked with decal GR 4 Connect supply feeders to the distribution block or circuit interrupter if furnished inside the electrical enclosure on the heater IMPORTANT Check all wiring connections in heater and element enclosure to assure tightness prior to en...

Page 7: ...ombustible material is 6 from the top sides and rear and 24 from the front Distance minimale aux matériaux combustibles est de 15 cm sur le dessus les côtés et à l arrière et 61 cm à l avant et ne doit pas être installé sur un plancher combustible 3 8 Electronic Low Water Cutoff The device consists of a probe in the tank that acts as a switch open when submerged in water and closed when the water ...

Page 8: ...ge for a long period of time If leaks are present tighten all four nuts uniformly on the element mounting flange in a criss cross pattern Tighten one nut then the nut on the diagonal from the first nut Next tighten the nut adjacent to the second nut and then the nut diagonal from the third nut Repeat this sequence until all nuts are tight Each nut should be tightened to 15 foot pounds of torque To...

Page 9: ...ting and Operating thermostats should be set minimum 10 F higher Le thermostat est réglé à environ 49 degrés Celsius Températures de l eau supérieures à 52 degrés Celsius peut causer instantanément de graves brûlures ou la mort de brûlures Suivez les instructions dans le manuel d installation et de maintenance pour modifier la température de l eau 9 If an optional proportional sequencer is furnish...

Page 10: ...the element should be replaced B C 40 60 60 C A 40 60 18 480 A B 26 78 B C 26 39 39 C A 26 39 18 380 A B 17 50 B C 17 25 25 C A 17 25 18 240 A B 7 20 B C 7 10 10 C A 7 10 18 208 A B 6 16 B C 6 8 8 C A 6 8 9 600 A B 80 240 B C 80 120 120 C A 80 120 9 480 A B 52 154 B C 52 77 77 C A 52 77 9 380 A B 33 98 B C 33 49 49 C A 33 49 9 240 A B 14 40 B C 14 20 20 C A 14 20 9 208 A B 10 30 B C 10 15 15 C A 1...

Page 11: ...AL THREE PHASE WIRING FIGURE 4 FIGURE 6 TYPICAL WIRE TERMINATIONS FIGURE 5 FIGURE 7 FIGURE 8 REQUIRED WIRE SIZE Contactor Fuseholder Wire Size 600V 30A 10 AWG 300V 60A 6 AWG 600V 60A 6 AWG TORQUEING REQUIREMENTS Wire Size Terminal Type In lbs 10 AWG RING 25 10 AWG BOX 35 6 AWG BOX 45 ...

Page 12: ...11 11 4 5 kW 480V 5 1 2 5 1 2 18 kW 380V 28 28 9 kW 380V 14 14 4 5 kW 380V 7 7 18 kW 240V 44 44 25 75 9 kW 240V 22 22 13 38 4 5 kW 240V 11 11 6 18 18 kW 208V 50 50 29 87 9 kW 208V 25 25 15 44 4 5 kW 208V 12 1 2 12 1 2 7 22 TABLE 2 NOTE Elements are usually wired to contactors in groups in order to maintain an amperage draw of close to but not more than 50 amps per contactor Applications for 600V m...

Page 13: ...an extended shutdown it is suggested the drain valve be left open during this period 7 3 Sediment Lime Scale Removal Waterborne impurities consist of the particles of soil and sand which settle out and form a layer of sediment on the bottom of the tank and adhere to heat exchange surfaces The amount of calcium carbonate lime released from water is in direct proportion to water temperature and usag...

Page 14: ... repair or replace pitted points caused by foreign particles Check fuses periodically for continuity and replace if necessary with the same type and rating 7 7 Replacing Electric Elements Some electric heating elements installed in dished heads may be factory bent to allow clearance from adjacent elements Replacement elements must be identical to the original equipment installed The Bend Angle Sta...

Page 15: ...y of the scale buildup is also determined by the watt density of the element It is good maintenance practice to remove and clean 80 W in 18kW density elements on a monthly basis The interval between removal and cleaning can usually be extended to six months when 40 W in 9kW density elements are installed Most installations where 20 W in 4 1 2kW density elements are used require only annual cleanin...

Page 16: ... Consult local PVI representative Hot water lines not insulated Add insulation it will protect against heat loss and save on cost of operation Power fuse s blown Check fuses for continuity Replace if blown If blown determine cause of break before replacing with same type fuse Contactor s not closing Check coil for continuity If defective replace Thermostat s not correctly set Check to assure prope...

Page 17: ...DURAWATT ELECTRIC WATER HEATERS PV500 6 05 13 17 ...

Page 18: ...DURAWATT ELECTRIC WATER HEATERS PV500 6 05 13 18 PVI INDUSTRIES LLC 3209 Galvez Ave Fort Worth Texas 76111 1 800 433 5654 www pvi com ...

Reviews: