background image

PV500-9  04-2000 

(2) 

Section 9 

 

POWER GAS BURNER START-UP 

(Refer to Figure 9-1 to identify burner parts) 

 

1.  Remove the enclosure panel cover on the water heater 

or boiler to expose the control circuit. Located on the 
back side of this cover is a wiring diagram  of the unit. 
This diagram will show the controls used in our 
circuitry. 

 
2.  Visually check to be sure all components are intact and 

no damage has occurred during transit. 

 
3.  Check all connections within the control cabinet. A 

loose connection on a component could cause 
intermittent shutdowns. 

 
4.  Some burners will use direct spark ignition. They may 

use a single gas pressure regulator and gas valve or 
multiple valves and regulators. On a call for heat, the 
motor starts, the gas primary control is energized, and 
after a short delay (pre-purge), the gas valve(s) opens 
and ignition should occur. Some burners have longer 
pre-purge periods. On a call for heat, the control is 
energized which starts the motor and begins a purge 
sequence. On completion of the purge cycle, the gas 
valve(s) opens and ignition occurs. 

 
5.  Remove flame safeguard control from its base. Check 

connections in the control mounting base. Again, loose 
connections can cause nuisance shutdowns. Also 
check the time card or programmer, when applicable, 
for good connection. 

 

NOTE: Always secure gas lines and tag “Out of 
Service” before servicing burner nozzle or electrodes. 

 
6.  Pull the nozzle assembly to check the flame and 

ignition electrodes. This is done by first removing the 
burner cover, exposing the nozzle assembly. 

 
7.  The L-Series burner must be removed from the heater 

and the blast tube removed to access the electrodes. 
The electrodes may be accessible by removing the 
nozzle assembly on larger burners. Free the nozzle 
assembly from the gas train by breaking the unions on 
the gas lines. Some models will use an orifice that is 
installed in these unions. Retain for re-use. 

 
8.  Next, remove the four bolts that hold the nozzle 

assembly to the burner housing. Once the nozzle 
assembly is free, pull it back slightly and remove the 
wires going to the flame and ignition rod. The easiest 
method of removing the nozzle assembly is to rotate it 
90° upward and tilt slightly forward while working it 
towards you (see Figure 9-2). Be careful not to damage 
the electrodes. 

 
9.  With the electrodes exposed, check them for the 

proper settings as called for in Figure 9-3. Also check 
for any hairline cracks in the insulators. Should 
replacement of burner electrodes be required, certain 
procedures must be followed. In all cases, removal of 
the electrodes is accomplished by loosening the 
electrode mounting bracket retaining screw. Draw the 
electrodes out of the nozzle assembly through the 
holes in the pressure plate. 

 
10.  Inspect the electrodes for cracked ceramics or loose 

retaining studs that hold the wire within the ceramic. 
Using supplied metric Allen wrench, loosen one or two 
pressure plate retaining screws so that the plate rotates 
freely on nozzle hub. Push plate towards the nozzle 
assembly gas spider to ensure it remains fully back and 
level. Do not re-tighten retaining screws at this time. 
Select the proper pressure plate hole in which to place 
each electrode and insert the electrode through the 
hole, retaining stud end first. Place electrodes in the 
electrode mounting bracket between the mount and the 
retaining bracket. 

 
11.  Tighten electrode mounting bracket screw slightly until 

electrode ceramics are seated firmly and completely in 
mounting bracket without gaps between ceramics and 
mounting bracket at the bearing faces. 

 

NOTE: Electrodes may have a high temperature, 
electrically insulating tape around them. The tape is 
designed to cushion the ceramic insulators in the 
mounting bracket, but is not absolutely necessary, and 
may be removed if it interferes with the positioning of 
the electrodes. 

 
12.  Ensure electrodes are loose enough to be rotated and 

that they will slide back and forth in the mounting 
bracket with firm finger pressure. 

 
13.  While ensuring the pressure plate is in the previously 

described position, measure and set electrodes 
according to Figure 9-3. After the gaps and settings are 
complete, fully tighten the electrode mounting bracket 
retaining screw. Do not overtighten or the insulation 
may crack. 

 

CAUTION: Electrodes may shift while tightening the 
screw due to rotation of the upper electrode mounting 
bracket. Holding down on this bracket while tightening 
the screw will stop this from happening. 

 

NOTE: The pressure plate may rotate on the nozzle hub 
as the electrodes seek their position during the 
tightening of the electrode mounting bracket retaining 
screw. This is desirable to prevent the electrodes from 
binding and not seating properly in the mounting 
bracket. The electrode ceramics will crack, causing 
ground faults in the circuit if this condition exists. 

 
14.  After complete mounting and positioning of the 

electrodes is accomplished, rotate the pressure plate 
so that no portion of the plate touches the electrode 
ceramics at the holes the electrodes pass through in 
the plate (ream holes slightly larger if needed to obtain 

Summary of Contents for FIREPOWER

Page 1: ...ket 19 Ignition transformer 33 Air shutter 6 Blast tube screw 20 On off switch 34 Union 7 Blast tube 21 1 4 NPT pressure port plug 35 Flame safeguard control 8 Nozzle assembly 22 Motor mounting plate 36 Flame cone 9 Nozzle mount bolt 23 Motor relay or starter 37 Manual gas valve 10 Air inlet cone 24 Pressure plate 38 Lifting eye bolt 11 Air screen 25 Primary gas ports 39 Power connector 12 Fan whe...

Page 2: ...ent of burner electrodes be required certain procedures must be followed In all cases removal of the electrodes is accomplished by loosening the electrode mounting bracket retaining screw Draw the electrodes out of the nozzle assembly through the holes in the pressure plate 10 Inspect the electrodes for cracked ceramics or loose retaining studs that hold the wire within the ceramic Using supplied ...

Page 3: ...itch on the side of the control enclosure assembly and the toggle switch on the burner If the operating control switches are closed the burner should come on and pre purge begin B If nothing happens check the control to be sure it is not in the tripped position and reset it by pushing flame safeguard reset button The burner should pre purge for not longer than thirty seconds The TFM series control...

Page 4: ...ster in 1 4 test opening and take CO reading CO should not exceed 03 A reading greater then 03 indicates lack of air Open air shutter slightly and take readings until CO is within proper range Optimum reading is no CO F If air shutter has been changed during CO test take a final CO2 reading G Insert stack temperature gauge in 1 4 test opening and read gross stack temperature Temperature should be ...

Page 5: ...PV500 9 04 2000 5 Section 9 REMOVAL OF THE NOZZLE ASSEMBLY EXCEPT L SERIES BURNERS Figure 9 2 ELECTRODE POSITIONS L P Q R S T SERIES BURNER Figure 9 3 ...

Page 6: ...Make all adjustments with linkage in the low fire position CAUTION Do not allow the modulating motor to push the air damper past the full open or full closed position while making adjustments Damage will occur Record damper positions from indicator dials and hold linkage rod in ball joint with fingers as motor actuates to eliminate this risk After correct damper movement is determined tighten ball...

Page 7: ...9 04 2000 7 Section 9 Figure 9 6 NOTE Nomograph is limited for use with Natural Gases with the following characteristics Heating Value gross Btu SCF 970 1100 Specific Gravity 0 57 0 70 Ultimate CO2 11 7 12 2 ...

Page 8: ...ND FLUE TEMPERATURE FOR L P GAS STEADY STATE EFFICIENCY CAN BE DETERMINED FROM THE FLUE LOSS Figure 9 7 NOTE Nomograph is limited for use with L P Gas with the following characteristics Heating Value gross Btu SCF 2466 2542 Specific Gravity 1 522 1 574 Ultimate CO2 13 73 13 82 ...

Page 9: ...if supplied is correct for the voltage and power VAC being supplied E Occasional low gas supply pressure Have local utility correct 3 BURNER MOTOR RUNS BUT PILOT DOES NOT LIGHT A Gas supply to burner shut off make sure all manual gas supply valves are open Automatic high pressure valve at meter such as Sentry type tripped shut due to high gas pressure reset valve and correct cause for trip out B P...

Page 10: ...ize as required or raise supply pressure to compensate for small line Do not raise pressure so high that under static no flow condition the pressure exceeds the maximum allowable pressure to the gas train components on the burner F Burner gas train components sized too small for supply pressure Increase component size as appropriate or consult factory G Automatic gas valve not opening fully due to...

Reviews: