2
Electrical Specification
“ECDDR” Series
Deionized
Water Unit
Model No.
Steam Output Capacity †
Humidifier Weight
Empty Full
lbs/hr
kg/hr
lbs kg
lbs kg
ECDDR
-
5
15.0
6.8
139.0 63.1
223.0 101.2
ECDDR
-
10
30.0
13.6
140.0 63.5
224.0 101.6
ECDDR
-
15
45.0
20.4
141.0 64.0
225.0 102.1
ECDDR
-
20
60.0
27.2
142.0 64.4
226.0 102.5
ECDDR
-
25
75.0
34.0
143.0 64.9
227.0 103.0
ECDDR
-
35
102.0
46.3
146.0 66.2
230.0 104.3
Capacity & Weights
“ECDDR” Series
Deionized
Water Unit
Model No.
Single Phase Amperage
Control
Circuit
Voltage
Three Phase Amperage
KW
No. of
Heaters
120V 208V 240V 480V 600V
No. of
Heaters
208V 240V 480V 600V
ECDDR
-
5
5
Single
41.7* 24.0 20.8 10.4 8.3
Triple
13.9 12.0 6.0 4.8
24 vac
ECDDR
-
10
10
Double
41.7 20.8 16.7
Triple
27.8 24.1 12.0 9.6
24 vac
ECDDR
-
15
15
Triple
31.3 25.0
Triple
41.7 36.1 18.1 14.4
24 vac
ECDDR
-
20
20
Triple
41.7 33.3
Triple
24.1 19.2
24 vac
ECDDR
-
25
25
Triple
41.7
Triple
30.1 24.1
24 vac
ECDDR
-
35
34
Triple
Triple
40.9 32.7
24 vac
*
ECDDR
-
5 at 120/1 requires 3 heating elements.
†
The above capacities are based on 100% efficiency. Actual humidifier capacity may vary due to the heat loss
from the humidifier reservoir. The ambient air temperature, air velocity, and injection tube system will affect
the rate of heat loss from the humidifier reservoir.
Capacity & Weights