Off Mode Output
Enter the output mA value desired when the output is in Off mode, or being Inter
-
locked, or if the Output Time Limit has expired, or during a calibration of the sensor
being used as an input. Also if there is a Probe Wash programmed for the sensor, and
the Sensor Mode option is set to Disable the output during the Wash cycle (if the Sen-
sor Mode option is set to Hold the output holds its last setting and the Integral is not
updated during the Wash). The acceptable range is 0 to 21 mA.
Error Output
Enter the output mA desired when the sensor is not giving the controller a valid signal.
The acceptable range is 0 to 21 mA.
Input
Select the sensor to be used by this output.
Direction
Set the control direction. This setting is used to determine the sign of the calculated
error (current process value versus set point) and allows flexible control with only
positive values for all PID tuning parameters.
Input Minimum
The low end of the sensor input range, used to normalize errors into percent of full scale
units. These values are set to the nominal range of the selected input sensor by default.
Input Maximum
The high end of the sensor input range, used to normalize errors into percent of full scale
units. These values are set to the nominal range of the selected input sensor by default.
Gain Form
Select the PID Equation Format used to enter tuning parameters.
5.3.32
Analog Output, Manual Mode
Output Details
The details for this type of output include the analog output %, HOA mode or Interlock status, accumulated on-
time, alarms related to this output, current cycle on time, and the current control mode setting.
Settings
Touch the Edit icon to view or change the settings related to the output.
A Manual analog output will activate if the HOA mode is Hand, or if it is Activated With another channel. There
are no additional programmable parameters
5.3.33
Analog Output, Retransmit Mode
Output Details
The details for this type of output include the output %, HOA mode or Interlock status, accumulated on-time,
alarms related to this output, current cycle on time, relay type and the current control mode setting.
Settings
Touch the Edit icon to view or change the settings related to the output.
4 mA Value
Enter the process value to correspond to a 4 mA output signal.
20 mA Value
Enter the process value to correspond to a 20 mA output signal.
Hand Output
Enter the output % desired when the output is in Hand mode.
Error Output
Enter the output % desired when the input signal is invalid (Error mode).
Input
Select the sensor input to retransmit.
5.4 Configuration Menu
The configuration Settings Menu is used for settings and activities that are not tied to Inputs or Outputs.
5.4.1
Global Settings
Date
Enter the current year, month and day.
Time
Enter the current hour (military time), minute, and second.