3.3.  Acoustic indication. 

 

A collective failure is indicated by the piezoelectric indicator, 1 beep every second. The acoustic indication 

can be turned off by changing the ON / OFF position of the switch   . 
 

 

switch in the up position, indication ON

 

      

 

switch in the down position, indication OFF 

 
 
4.  Operation and use. 
 

4.1.  Overload or short circuit of the PSU output. 

   The 

AUX1 ÷ AUX16, DVR power supply outputs are protected against short-circuit with glass fuses. If a 

fuse-assisted protection has been chosen, replace the fuse (of the same parameters) in case of a failure. 

 
 
   4.2  Battery-assisted operation

  In case of a main power outage, the device is immediately switched 

into a battery-assisted operation.  
 

 
The  PSU  is  equipped  with  the  discharged  battery  disconnection  system.  During 

the  battery-assisted  operation,  reducing  voltage  below  9,5V  at  the  battery  terminals  will 
cause battery disconnection. 

 
 

4.3  Maintenance. 

Any  and  all  maintenance  operations  may  be  performed  following  the  disconnection  of  the  PSU  from  the 

power supply network. The PSU does not require performing any specific maintenance measures. In case of fuse 
replacement, use a replacement of the same parameters. 

 

 

 

 

WEEE LABEL 

 

Waste electrical and electronic equipment must not be disposed of with normal household 

waste. According to the European Union WEEE Directive, waste electrical and electronic 

equipment should be disposed of separately from normal household waste

 

 

CAUTION! 

The power supply unit is adapted for a sealed lead-acid battery (SLA). After the operation period it must not be disposed of but 

recycled according to the applicable law

.

 

 

 
 

 
 

 
 

 

Pulsar  

Siedlec 150,  32-744 Łapczyca, Polska 

Tel. (+48) 14-610-19-40, Fax. (+48) 14-610-19-50 

e-mail: 

[email protected]

[email protected]

 

http:// 

www.pulsar.pl

www.zasilacze.pl

 

 

Summary of Contents for RUPS1612RT

Page 1: ...RUPS1612RT v 1 0 RUPS 13 8V 12V 20A TOPIC RACK mounted buffer power supply for up to 16 cameras and recorder EN Edition 2 from 30 03 2017 Supercedes the edition 1 from 15 03 2016 ...

Page 2: ...y charge current 2A batteries 1x17Ah 1x28Ah 1x40A 1x65Ah control of voltage presence at the AUX1 AUX16 outputs DVR acoustic indication of failure LED optical indication AC DC TEMP LoB ALARM AUX1 AUX16 DVR the ALARM technical output of collective failure relay type activated by 230V AC power loss low voltage of the PSU 11 5V activation of the output fuse in the camera power supply circuit activatio...

Page 3: ...0 75A 4A recorder 2A battery charge Total device current battery 18A max In case of power decay a battery back up is activated immediately The PSU is fitted with 16 outputs protected independently with glass fuse 1A and the output for the recorder is protected with the 4A glass fuse The power supply is fitted with the ALARM output of collective failure In case of failure relay contacts are switche...

Page 4: ...f the recorder BAT battery output ALARM technical output of collective failure relay BUZZER micro switch turning ON OFF of acoustic indication switch in the top position indication ON switch in the down position indication OFF F1 F16 glass fuses in the cameras AUX power supply circuits F1A FDVR glass fuses in the recorder DVR power supply circuits F4A 230V AC INPUT power socket 230V AC power cable...

Page 5: ...peration LED AC DC TEMP LoB ALARM AUX1 AUX16 Acoustic operation indication Piezoelectric indicator 75dB 0 3m The ALARM technical output of collective failure Relay type 1A 30VDC 50VAC The FMAINS fuse in the 230V power supply circuit T 6 3A FDVR fuse in the recorder power supply circuits F 4A F1 F16 glass fuses in the cameras AUX power supply circuits 16x F 1A Mechanical parameters tab 3 Enclosure ...

Page 6: ...on of the recorder 4A Maximum battery charging current is 2A Total device current battery 18A max As the PSU is designed for a continuous operation and is not equipped with a power switch therefore an appropriate overload protection shall be guaranteed in the power supply circuit Moreover the user shall be informed about the method of unplugging usually through assigning an appropriate fuse in the...

Page 7: ...oltage 11 5V GREEN LED on DC voltage in the AUX1 AUX16 output off no DC voltage in the AUX1 AUX16 output GREEN LED on DC voltage in the DVR output off no DC voltage in the DVR output 3 2 Technical output The power supply is fitted with the ALARM output of collective failure relay type A collective failure can be triggered by the following events 230V AC mains power failure Activation of the glass ...

Page 8: ...em During the battery assisted operation reducing voltage below 9 5V at the battery terminals will cause battery disconnection 4 3 Maintenance Any and all maintenance operations may be performed following the disconnection of the PSU from the power supply network The PSU does not require performing any specific maintenance measures In case of fuse replacement use a replacement of the same paramete...