background image

www.pulsar.pl

    

 

 

 

RUPS1612RP   

 

 

RACK POWER CCTV

 

 

1.4.  Specifications. 

- electrical parameters (tab.2) 
- mechanical parameters (tab.3) 
- operation safety (tab.4) 
- operating parameters (tab.5) 

 

       Electrical parameters (tab. 2). 

Mains supply 

176÷264V AC  

Current up to 

1,3A@230V AC max. 

Supply power 

241W max. 

Efficiency 

82% 

Output voltage 

AUX1÷AUX16 - cameras 

 
Output voltage DVR - recorder 

11V ÷ 13,8V DC – buffer operation 
9,5V ÷ 13,8V DC – battery-assisted operation 
12V DC 

– maintained regardless of the state of battery charge 

Output current 

16 x 0,75A + 4A re 2A battery charge 

Ripple 

120 mV p-p max. 

Battery charge current 
(batteries 1x17Ah/ 1x28Ah/ 1x40Ah/ 1x65Ah) 

2A max. (+/-5%) 

Short-circuit protection SCP 

cameras: 16 x PTC 1A, polymer fuse 
recorder: 1 x F 4A, glass fuse 

Overload protection OLP 
Current consumption by PSU systems 

105% ÷ 150% of the PSU power, automatic return 
0,33A 

Overvoltage protection OVP 

>16V (activation requires disconnecting the load or supply for 
about 20s.) 

Battery circuit protection SCP and reverse  
polarity connection 

glass fuse 30A 

Surge protection 

varistors 

Excessive discharge protection UVP 

U<9,5V (+/-5%) 

– disconnect of connection battery 

Optical indication of operation: 

LED: AC, DC, TEMP, LoB, ALARM, AUX1÷AUX16 

Acoustic operation indication: 

Piezoelectric indicator ~75dB/0,3m 

The ALARM technical output of collective failure 

Relay type: 1A@ 30VDC/50VAC 

The 

F

MAINS

 

fuse in the 230V power supply circuit 

T 6,3A 

F

DVR

 

fuse in the recorder power supply circuits 

F 4A 

       
       

Mechanical parameters (tab. 3). 

Enclosure dimensions 

W=19”, H=2U; 482 x 88 x 223  mm (WxHxD) 

Fixation 

four-point butt mounting to RACK profiles 

– the set include 4 M6 cage nuts 

Net weight 

6,20kg / 6,60kg  

Enclosure 

Steel plate RAL 9005, black 

Connectors 

230V AC input: the IEC C14 socket with a fuse, power cable 2m  
(included) 
Outputs: 

ALARM, AUX1÷AUX16: Φ0,5-2,1 (AWG 24-12) 0,5-1,5mm

2

 

Output DVR

: Φ0,5-2,1 (AWG 24-12) 0,5-1,5mm

2

, power cable 2m (included) 

Battery output BAT: 6,3F-2,5  

Notes 

Forced cooling (fan). 

        
      

Operation safety (tab.4). 

Protection class PN-EN 60950-1:2007 

I (first) 

Protection grade PN-EN 60529: 2002 (U) 

IP20 

Electrical strength of insulation: 
- between input and output circuits of the PSU (I/P-O/P) 
- between input circuit and PE protection circuit (I/P-FG) 
- between output circuit and PE protection circuit (O/P-FG) 

 
3000 V/AC min. 
1500 V/AC min. 
  500 V/AC min. 

Insulation resistance: 
- between input circuit and output or protection circuit 

 
100 MΩ, 500V/DC  

 
Operating parameters (tab.5). 

Environmental class 

II 

Operating temperature 

-

10ºC...+45ºC 

Storage temperature 

-

20ºC...+60ºC 

Relative humidity 

20%...90%, without condensation 

Vibrations during operation 

unacceptable 

Impulse waves during operation 

unacceptable 

Direct insulation 

unacceptable 

Vibrations and impulse waves during transport 

According to PN-83/T-42106 

 
 

Summary of Contents for RUPS1612RP

Page 1: ...RUPS1612RP v 1 0 RUPS 13 8V 12V 20A PTC RACK mounted buffer power supply for up to 16 cameras and recorder EN Edition 2 from 30 03 2017 Supercedes the edition 1 from 15 03 201 ...

Page 2: ...ery charge current 2A batteries 1x17Ah 1x28Ah 1x40A 1x65Ah control of voltage presence at the AUX1 AUX16 outputs DVR acoustic indication of failure LED optical indication AC DC TEMP LoB ALARM AUX1 AUX16 DVR the ALARM technical output of collective failure relay type activated by 230V AC power loss low voltage of the PSU 11 5V activation of the output fuse in the camera power supply circuit activat...

Page 3: ...A 4A recorder 2A battery charge Total device current battery 18A max In case of power decay a battery back up is activated immediately The PSU is fitted with 16 outputs protected independently with polymer fuse PTC 1A and the output for the recorder is protected with the 4A polymer fuse The power supply is fitted with the ALARM output of collective failure In case of failure relay contacts are swi...

Page 4: ...ndependently protected outputs of the recorder BAT battery output ALARM technical output of collective failure relay BUZZER micro switch turning ON OFF of acoustic indication switch in the top position indication ON switch in the down position indication OFF FDVR glass fuses in the recorder DVR power supply circuits F4A 230V AC INPUT power socket 230V AC power cable 1 5m included FMAINS fuse in th...

Page 5: ...RM technical output of collective failure Relay type 1A 30VDC 50VAC The FMAINS fuse in the 230V power supply circuit T 6 3A FDVR fuse in the recorder power supply circuits F 4A Mechanical parameters tab 3 Enclosure dimensions W 19 H 2U 482 x 88 x 223 mm WxHxD Fixation four point butt mounting to RACK profiles the set include 4 M6 screws cage nuts Net weight 6 20kg 6 60kg Enclosure Steel plate RAL ...

Page 6: ...a power switch therefore an appropriate overload protection shall be guaranteed in the power supply circuit Moreover the user shall be informed about the method of unplugging usually through assigning an appropriate fuse in the fuse box The electrical system shall follow valid standards and regulations 2 2 Installation procedure 1 Before installation cut off the voltage in the 230V power supply ci...

Page 7: ...UX16 output off no DC voltage in the AUX1 AUX16 output GREEN LED on DC voltage in the DVR output off no DC voltage in the DVR output 3 2 Technical output The power supply is fitted with the ALARM output of collective failure relay type A collective failure can be triggered by the following events 230V AC mains power failure Activation of the PTC polymer fuse in the camera power supply circuit Acti...

Page 8: ...he PSU is equipped with the discharged battery disconnection system During the battery assisted operation reducing voltage below 9 5V at the battery terminals will cause battery disconnection 4 3 Maintenance Any and all maintenance operations may be performed following the disconnection of the PSU from the power supply network The PSU does not require performing any specific maintenance measures I...