www.pulsar.pl
PSDCR161214
5
Mechanical specifications (tab. 4).
Dimensions
W=432, H=607, D+ D
1
=102+14 [+/- 2mm]
W
1
=437, H
1
=612 [+/- 2mm]
Dimensions of recorder
space
W
2
=400, H
2
=345, D
2
=95 [+/- 2mm]
Fixing
See figure 3
Net/gross weight
7,8/8,6 kg
Enclosure
Steel plate, DC01 0,7mm colour: RAL 9003
Closing
2 x cheese-head screw: at the front
The possibility of installing two locks with different codes.
Connectors
Power supply: 230V AC:
Φ0,63-2,05 (AWG 22-12)
AUX outputs
: Φ0,51- 2,05 (AWG 24-12)
LB8: Φ0,51- 2,05 (AWG 24-12)
Notes
The enclosure does not adjoin the assembly surface so that cables can be led.
Convectional cooling.
Operation safety (tab.5).
Protection class EN 60950-1:2007
I (first)
Protection grade EN 60529: 2002 (U)
IP20
Electrical strength of insulation:
- between input (network) circuit and output circuits of the PSU (I/P-O/P)
- between input circuit and PE protection circuit (I/P-FG)
- between output circuit and PE protection circuit (O/P-FG)
3000V/AC min.
1500V/AC min.
500V/AC min.
Insulation resistance:
- between input circuit and output or protection circuit
100 MΩ, 500V/DC
Operating specifications (tab.6).
Operating temperature
-
10ºC...+40ºC
Storage temperature
-
25ºC...+60ºC
Relative humidity
20%...90%, without condensation
Vibrations during operation
unacceptable
Impulse waves during operation
unacceptable
Direct insolation
unacceptable
Vibrations and impulse waves during transport
PN-83/T-42106
2. Installation.
2.1 Requirements.
The stabilized PSU is to be mounted by a qualified installer, holding relevant permits and licenses (applicable
and required for a given country) for 230V/AC interference and low-voltage installations. The unit should be mounted in
confined spaces, in accordance with the 2nd environmental class, with normal relative humidity (RH=90% maximum,
without condensation) and temperature from -
10°C to +40°C. The PSU shall work in a vertical position that guarantees
sufficient convectional air-flow through ventilating holes of the enclosure.
During normal operation the total current consumption of the receivers cannot exceed I=14A
As the PSU module is designed for a continuous operation and is not equipped with a power-switch, therefore an
appropriate overload protection shall be guaranteed in the power supply circuit. Moreover, the user shall be informed
about the method of unplugging (most frequently through separating and assigning an appropriate fuse in the fuse-box).
The electrical system shall follow valid standards and regulations.