Pulsar PSDC 08128 Quick Start Manual Download Page 5

www.pulsar.pl 

 

 

 

 

PSDC08128 

 

 

 

 

 
 

1.4. Specifications: 

   - electrical specifications (tab.3) 
   - mechanical specifications (tab.4) 
   - operation safety (tab.5) 
   - operating specifications (tab.6) 

 
Electrical specifications (tab. 3). 

Supply voltage 

176 ÷ 264V AC 

Current consumption 

0,9A@230VAC max. 

PSU power 

120W max. 

Efficiency 

83% 

Output voltage 

12V DC 

Output current 

8 x 1A 

Output voltage adjustment range 

12V÷ 15V DC  

Ripple voltage 

100mV p-p max. 

Short-circuit protection SCP  

LB8/AW STRIP 
8x F 1A fuse or PTC 1A 
PSU MODULE 
105% ÷ 150% of PSU power, electronic current limiting 

Overload protection OLP 

105% ÷ 150% of PSU power, electronic current limiting 

Surge protection 

varistors 

Surge over voltage protection OVP 

>16V (activation requires disconnecting the load or supply for  
about 20 s.) 

Tampering protection system  
- TAMPER 

– indicating unwanted 

opening of the 

PSU’s enclosure 

 
- microswitch, NC contacts (enclosure closed), 0,5A@50V DC (max.) 

Technical outputs: 
- FPS  outputs indicating fuse failure 
(blow) of LB8/AW strips:  (SCP activation) 

 
- OC type, 50mA max, 
normal status: L level (0V), 
failure: hi-Z level 

F1÷ F8 fuses  

F 1A/250V or PTC 1A (manual selection) 

 

Mechanical specifications (tab. 4). 

Enclosure dimensions 

280 x 256 x 60+8 (WxHxD) [mm] (+/- 2) 

Fixing 

See figure 3 

Net/gross weight 

1,96/2,25 kg 

Enclosure 

Steel plate, DC01 0,7mm colour: RAL 9003 

Closing 

Cheese-head screw: at the front 

Connectors 

Power supply: 230V AC: 

Φ0,63-2,05 (AWG 22-12) 

AUX outputs: Φ0,51- 2,05 (AWG 24-12) 
LB8/AW: Φ0,51- 2,05 (AWG 24-12) 
TAMPER output: wires 25cm 

Notes 

The enclosure does not adjoin the assembly surface so that cables can be led. 
Convectional cooling. 

 
Operation safety (tab.5). 

Protection class PN-EN 60950-1:2007 

I (first) 

Protection grade PN-EN 60529: 2002 (U) 

IP20 

Electrical strength of insulation: 
- between input (network) circuit and output circuits of the PSU (I/P-O/P) 
- between input circuit and PE protection circuit (I/P-FG) 
- between output circuit and PE protection circuit (O/P-FG) 

 
3000V/AC min. 
1500V/AC min. 
  500V/AC min. 

Insulation resistance: 
- between input circuit and output or protection circuit 

 
100 MΩ, 500V/DC  

 
Operating specifications (tab.6). 

Operating temperature 

-

10ºC...+50ºC  

Storage temperature 

-

25ºC...+60ºC 

Relative humidity 

20%...90%, without condensation 

Vibrations during operation 

unacceptable 

Impulse waves during operation 

unacceptable 

Direct insolation 

unacceptable 

Vibrations and impulse waves during transport 

PN-83/T-42106 

 

Reviews: