1.2. Block diagram. (fig.1). 

 

Fig.1. Block diagram of the PSU. 

 

1.3. Description of PSU components and connectors.  

 

Table 1.  Elements of the PSU (see fig. 2). 

Element no. 

Description 

[1] 

LED indicating presence of AC power

  

[2] 

LED indicating presence of DC power 

[3] 

LED indicating correct battery voltage 

[4] 

FAC-

 AC absence technical output – relay type 

[5] 

FPS-

 output indicating DC absence/PSU failure – relay type

 

[6] 

FLB- 

output indicating battery low voltage – relay type 

[7] 

FAC-

 AC absence technical output – OC  type 

[8] 

FPS-

 output indicating DC absence/PSU failure - OC  type

 

[9] 

FLB- 

output indicating battery low voltage - OC  type 

[10] 

+V ,-V-

 DC supply output

 

[11] 

L-N  

230V/AC power connector, 

 PE protection connector 

[12] 

LED indication

 on the front panel

 

[13] 

Battery connectors: +BAT =red, - BAT = black 

[14] 

V

ADJ

 - potentiometer,

 DC

 voltage adjustment

 

 

Fig. 2. The view of the PSU. 

Summary of Contents for PSBOC751250

Page 1: ...PSBOC751250 v 1 0 PSBOC 13 8V 5A OC Enclosed buffer switch mode power supply unit with automatic operation control EN Edition 1 from 28 03 2014 Supercedes edition...

Page 2: ...ption 1 1 General description 1 2 Block diagram 1 3 Description of PSU components and connectors 1 4 Specifications 2 Installation 2 1 Requirements 2 2 Installation procedure 3 Operating status indica...

Page 3: ...sence technical output relay type 5 FPS output indicating DC absence PSU failure relay type 6 FLB output indicating battery low voltage relay type 7 FAC AC absence technical output OC type 8 FPS outpu...

Page 4: ...y connection polymer fuse Surge protection varistors Surge over voltage protection OVP 16V automatic recovery Deep discharge protection UVP U 9 5V 5 disconnection of the battery terminal Technical out...

Page 5: ...tion and temperature from 10 C to 40 C The device shall be mounted in a metallic enclosure a cabinet an intended case In order to fulfil LVD and EMC requirements the rules for power supply encasing an...

Page 6: ...by the AC diode going out Caution LED indicates power absence if the outage lasts 10s green LED Fig 2 element 2 indicates DC power at the PSU output Under normal status the diode is permanently illum...

Page 7: ...voltage OC type output Under normal status UBAT 11 5V the output is connected to ground L level 0V In case of decrease of battery voltage UBAT 11 5V the output is switched into high impedance state h...

Page 8: ...t within 14 days from the delivery to the service centre of the manufacturer 6 The repair period mentioned in item 5 may be prolonged if there are no technical possibilities to carry out the repairs o...