1.2 Block diagram. (fig.1). 

 

 

Fig.1. Block diagram of the PSU. 

 

1.3 Description of PSU components and connectors.  

 

Table 1.  Elements of the PSU (see fig. 2). 

Element no. 

Description 

[1] 

LED indicating presence of AC power

  

[2] 

LED indicating presence of DC power 

[3] 

LED indicating correct battery voltage 

[4] 

EPS -

 AC absence technical output 

– relay type 

[5] 

PSU -

 output indicating DC absence/PSU failure 

– relay type

 

[6] 

LoB - 

output indicating battery low voltage 

– relay type 

[7] 

EPS -

 AC absence technical output 

– OC  type 

[8] 

PSU -

 output indicating DC absence/PSU failure - OC  type

 

[9] 

LoB - 

output indicating battery low voltage - OC  type 

[10] 

V

ADJ

 - potentiometer,

 DC

 voltage adjustment

 

[11] 

+V ,-V-

 DC supply output 

[12] 

L-N  

230V/AC power connector, 

 PE protection connector

 

[13] 

Battery connectors: +BAT =red, - BAT = black 

[14] 

LED indication on the front panel

 

[15] 

Battery charging current selection:  

 

  Ibat =0,5 A 

 

  Ibat =1 A 

Legend: 

 dip switch installed 

 dip switch removed 

 

 

Fig. 2. The view of the PSU. 

 
 
 

Summary of Contents for PSBOC1554828

Page 1: ...PSBOC1554828 v 1 0 PSBOC 54V 2 8A OC Enclosed buffer switch mode power supply unit with technical outputs EN Edition 2 from 01 06 2016 Supercedes edition 1 from 13 05 2016...

Page 2: ...description 1 2 Block diagram 1 3 Description of PSU components and connectors 1 4 Specifications 2 Installation 2 1 Requirements 2 2 Installation procedure 3 Operating status indication 3 1 LED indi...

Page 3: ...ating DC absence PSU failure relay type 6 LoB output indicating battery low voltage relay type 7 EPS AC absence technical output OC type 8 PSU output indicating DC absence PSU failure OC type 9 LoB ou...

Page 4: ...ection SCP electronic automatic recovery Overload protection OLP 105 150 of power supply automatic recovery Battery circuit protection SCP and reverse polarity connection polymer fuse Surge protection...

Page 5: ...paces in accordance with the 2nd environmental class with normal relative humidity RH 90 maximum without condensation and temperature from 10 C to 40 C The device shall be mounted in a metallic enclos...

Page 6: ...ted AC power absence is indicated by the AC diode going out green LED Fig 2 element 2 indicates DC power at the PSU output Under normal status the diode is permanently illuminated In case of a short c...

Page 7: ...ease of battery voltage UBAT 46V the output is switched into high impedance state hi Z relay output In case of a battery voltage drop UBAT 46V the contacts of the relay change over The power supply un...

Page 8: ...ays from the delivery to the service centre of the manufacturer 6 The repair period mentioned in item 5 may be prolonged if there are no technical possibilities to carry out the repairs or if the equi...

Reviews: