3.2 Technical outputs

 

The PSU has indication outputs: 
 

 

FAC - absence of AC supply output:  
-  OC  type  output  that  indicates  AC  power  loss.  Under  normal  status,  with  230V  AC  supply,  the  output  is 
connected  to  ground  (L  level  –  0V).  In  case  of  power  loss,  the  PSU  will  switch  the  output  into  high 
impedance state hi-Z after approx. 10s. 
relay output indicating the absence of AC supply. In case of power loss, the PSU  module will switch the 
relay contacts after approx. 10 seconds. 

 
CAUTION! In Fig.2. the contact set in the potential-free status corresponds to a state with no AC 
power (AC power failure). 
 
 

 

 

FPS – technical output indicating absence of DC voltage at the PSU
-    OC  type  output  indicating  the  PSU  failure.  In  normal  state  (during  correct  operation)  the  output  is 
connected to ground (L level – 0V). In case of absence of DC voltage at the output (e.g. short circuit), the 
output is switched into high impedance state – hi-Z. 

     - relay output. In case of a failure, the contacts of the relay change over. 

 
 

CAUTION!  In  the  Fig.2.  the  set  of  contacts  shows  a  potential-free  status  of  the  relay  which 
corresponds to a state with no DC power (PSU failure). 

 

 

FLB – technical output indicating battery voltage:  
-  OC  type  output.  Under  normal  status  (U

BAT

  >  23V)  the  output  is connected  to  ground  (L  level  –  0V).  In 

case of decrease of battery voltage (U

BAT

 < 23V) the output is switched into high impedance state – hi-Z. 

      -  relay output. In case of a battery voltage drop U

BAT

 < 23V, the contacts of the relay change over. 

 

 
CAUTION! In the Fig.2. the set of contacts shows a potential-free status of the relay which 
corresponds to a state with low battery level (U

BAT

 <23V). 

 

 

Fig. 4. Electrical diagram of OC outputs. 

 

4. Operation and use. 

4.1 Overload or short circuit of the PSU module output 
In case of an overload or a short circuit at the PSU output, the output voltage is automatically cut off. The 

voltage is restored automatically after removing the failure (overload). 

 
4.2 Battery-assisted operation.  
In case of a main power outage, the device is immediately switched into a battery-assisted operation. 

 

 
 
The  PSU  is  equipped  with  the  discharged  battery  disconnection  system.  During  the 

battery-assisted operation, reducing voltage below 19V at the battery terminals will cause 
battery disconnection. 

 

 

4.3 Maintenance 
Any  and  all  maintenance  operations  may  be  performed  following  the  disconnection  of  the  PSU  from  the 

power  supply  network.  The  PSU  does  not  require  performing  any  specific  maintenance  measures.  However,  in 
case of significant dust ingress, it is recommended to clean the PSU with compressed air. 

 
 

Summary of Contents for PSBOC1002435

Page 1: ...PSBOC1002435 v 1 1 PSBOC 27 6V 3 5A OC Enclosed buffer switch mode power supply unit with automatic operation control EN Edition 5 from 10 02 2014 Supercedes edition 4 from 30 10 2013...

Page 2: ...ription 1 1 General description 1 2 Block diagram 1 3 Description of PSU components and connectors 1 4 Specifications 2 Installation 2 1 Requirements 2 2 Installation procedure 3 Operating status indi...

Page 3: ...output indicating DC absence PSU failure relay type 6 FLB output indicating battery low voltage relay type 7 FAC AC absence technical output OC type 8 FPS output indicating DC absence PSU failure OC...

Page 4: ...systems 50 mA Battery charging current 0 5A 1A jumper selectable Short circuit protection SCP electronic automatic recovery Overload protection OLP 105 150 of power supply automatic recovery Battery...

Page 5: ...orage temperature 20 C 60 C Relative humidity 20 90 without condensation Vibrations during operation unacceptable Impulse waves during operation unacceptable Direct insolation unacceptable Vibrations...

Page 6: ...le as V 5 Connect the technical outputs to the central or other device 6 Connect the battery in accordance with the signs colours 7 Once the tests and operation control have been completed the enclosu...

Page 7: ...ttery voltage OC type output Under normal status UBAT 23V the output is connected to ground L level 0V In case of decrease of battery voltage UBAT 23V the output is switched into high impedance state...

Page 8: ...at within 14 days from the delivery to the service centre of the manufacturer 6 The repair period mentioned in item 5 may be prolonged if there are no technical possibilities to carry out the repairs...

Reviews: