Features of the power supply unit: 

 

 

13.8 VDC uninterruptible power supply  

 

Controlling of battery charging and 
maintaining 

 

Protecting of battery against excessive 
discharging (UVP) 

 

Securing the BAT circuit against short-circuit 
and the battery reverse connection  

 

Selectable charging current 

 

START function of manual battery actuation  

 

Checking the status of safety fuses of AUX1, 
AUX2 and AUX3 outputs 

 

LED optical signalisation  

 

BS output for the signalling loss of the 230V 
network 

 

AW output of power supply unit failure, 
tripped by: 

 

outlet short-circuit (SCP) 

 

outlet overload (OLP) 

 

battery disconnection < 10V (UVP) 

 

failure of DC/DC voltage converter  

 

Safety equipment:  

 

SCP short-circuit protection  

 

OLP overload protection  

 

OHP overheat protection  

 

OVP overvoltage protection  

 

Surge protection  

 

Against sabotage

 
 
 
 
CONTENTS: 
1. Technical description 

1.1. General description 
1.2. Block diagram 
1.3. Description of elements and power supply connectors 
1.4. Technical parameters 

2. Installation. 

2.1. Requirements 
2.2. Installation procedure 

3. The power supply operation indication 

3.1. Optical indication 
3.2. Technical output 

4. Service and operation 

4.1. Overload or short circuit 
4.2. Battery operation 
4.3. Maintenance 

 
1. Technical description. 
 

1.1. General description. 

The buffer power-supply is used for uninterrupted supply of devices requiring stabilized voltage of 

12V DC 

(+/-15%). 

The  power-supply  provides  voltage  within  the  following  range: 

U=  11.0V÷13.8V  DC 

of  total  current 

efficiency equal to 

10A. 

In case of power voltage decay, prompt switching to battery supply occurs.  

The power-supply has got a metal casing (RAL 9003 colour) with a space for 40Ah/12V battery. The casing 

features a micro-switch indicating door (front) opening and separating from the wall.  
 

Information about additional equipment for PSBD 10A12 power-supply:

 

 
Modules of DC/DC 
voltage converters 

DC/DC 10 (1,0 A) 
DC/DC 20 (2,0 A) 

Protection module 
(fuse blocks) 

AWZ 535 – LB4/AW, AWZ 536 – LB5/AW (PTC or FTA, with failure indication – OC 
type output) 
AWZ 573 – LB4/0,3A/PTC, AWZ 574 – LB4/0,5A/PTC, AWZ 575 – LB4/1,0A/PTC,  
AWZ 576 – LB4/0,3-1,0A/FTA,  
AWZ 577 – LB8/0,3A/PTC, AWZ 578 – LB8/0,5A/PTC, AWZ 579 – LB8/1,0A/PTC, 
AWZ 580 – LB8/0,3A-1,0A/FTA 

DC voltage reducers 
13,8V DC / 12V DC 

RN250 – RN-2,5A/12V 
RN500 – RN-5,0A/12V 

Summary of Contents for PSBD 10A12

Page 1: ...PSU B 13 8V S 10A 1 EL TR 40Ah MC PSBD 10A12 v 1 0 Buffer switch mode power supply unit EN Edition 2 from 27 th October 2010 Supercedes edition 1 from 27 th May 2010...

Page 2: ...e 3 The power supply operation indication 3 1 Optical indication 3 2 Technical output 4 Service and operation 4 1 Overload or short circuit 4 2 Battery operation 4 3 Maintenance 1 Technical descriptio...

Page 3: ...3 1 2 Block diagram fig 1 Fig 1 Block diagram of the power supply unit...

Page 4: ...ply operation 7 AC LED diode that indicates the presence of AC voltage 8 LB LED diode that indicates battery charging 9 OVP LED diode that indicates the activation of the OVP overvoltage protection 10...

Page 5: ...t 1 Separation transformer 2 Power supply unit board tab 1 3 TAMPER micro switch contacts of the anti sabotage protection NC 4 F2 fuse in the power supply circuit 230VAC 5 L N 230VAC power supply conn...

Page 6: ...6 Fig 3 View of the power supply unit...

Page 7: ...otection of the battery circuit and reverse polarity protection 10A current limitation F1 fuse failure requires replace of the fuse element UVP excessive discharge protection U 10 0 V 5 Technical outp...

Page 8: ...rrents collected by receivers shall not exceed I 10A P 138W max including the maximum battery charging current Ibat As the power supply is designed for a continuous operation and is not equipped with...

Page 9: ...reover the PSU is equipped with three diodes indicating operation status AC LB AUX O1 O2 O3 and UVP placed on the PCB of the power supply unit module AC red diode under normal status AC supply the dio...

Page 10: ...the fuse F1 in the battery circuit becomes permanently damaged The restoration of the voltage at the BAT output requires the replacement of the fuse 4 2 Battery operation In the case of power failure...

Page 11: ...ing of the equipment to the service centre of the manufacturer 7 The repair period mentioned in item 5 may be prolonged if there is no technical capability to carry out the repairs and in the case tha...