Features of the power supply: 

 

 

DC 13,8V/1,5A uninterruptible power supply  

 

wide AC input  voltage range 176÷264V  

 

high efficiency 70% 

 

controlling of battery charging and maintaining 

 

protecting of battery against excessive 
discharging (UVP) 

 

battery charging current 0,5A 
 

 

battery output is full protected against short-
circuit and reverse connection  

 

LED optical signalisation  

 

protections: 

 

SCP short-circuit protection 

 

OVP overvoltage protection 

 

overvoltage protection  (output AC) 

 

overload (OLP) 
 

 
1. Technical description. 

 

1.1  General description. 
Buffer-type power supply units are intended for continuous power supply to devices that require stabilised voltage 

of 12 V DC (+/-15%). The power supply provides a voltage of U=13,8 V DC with an output current of I=1A+ 0,5A battery 
charging. 

In  case  of  power  voltage  decay,  prompt  switching  to  battery  supply  occurs.  The  power  supply  has  the 

following protections: short-circuit (SCP), overload (OLP) and overvoltage (OVP). 

 

Under normal operation, the total current drawn by the equipment may not exceed I = 1 A;  Maximum 

battery charging current: 0.5 A. Total device c battery: 1,5 A max. 

 

1.2. Technical parameters. 

Supply voltage 

176÷264V AC 50Hz  

Current consumption 

0,35A@230VAC max.  

Supply power 

25W max.  

Efficiency 

70% 

Output voltage 

13,8V DC – buffer operation 
9,5V÷13,8V DC – battery operation 

Output current

 

1A + 0,5A battery charging 

Output current t

AMB

<30°C 

1A + 0,5A battery charging - refer to graph 1 . 

Output current t

AMB

=40°C 

0,7 A + 0,5A battery charging - refer to grap h 1. 

Voltage adjustment range 

12÷14V DC 

Ripple voltage 

120mV p-p max. 

Battery charging current 

0,5A max 

Short-circuit protection SCP 

electronic 

Overload protection (battery) OLP 

polymer fuse (PTC) 

Overvoltage protection OVP 

U>115% ÷ 150% of the output voltage, isolation of the 
output voltage, atomatic recovery 

Excessive discharge protection UVP 

U<9,5 V (± 5%) – disconnection of battery 

Optical signalisation 

green LED- presence of  AC voltage 

Output of optical signalization 

LED AC- presence of  AC voltage 
LED DC- presence of  DC voltage on power supply output 

Operation conditions                                            

2-nd enviromental class,  temperature: -10 

o

C÷40

 o

relative humidity 20%...90%, without condensation 

Dimensions (LxWxH) 

110 x 78 x 36 [mm] 

Net/gross weight 

0,28kg / 0,31kg 

Protection class PN-EN 60950-1:2007 

I (first) - requires a protective conductor (PE) 

Connectors 

power-supply: 

Φ

0,63÷2,5   I/O PCB : 

Φ

0,41÷1,63   

battery output BAT: 6,3F-2,5/40cm, 
output of optical signalization: plug 3-pin 5 mm 