2
relative humidity 20%...90%, without condensation
Dimensions
L=199, W= 110, H=50 [
±2mm]
Net/gross weight
0,67 / 0,71 [kg]
Protection class electric shock protection
I (first) - requires a protective conductor
Connectors
I/O PCB: 0,5
– 2,5 mm
2
(AWG 26
– 12)
output of optical signalization: 4 pins micromatch socket
Additional accessories
Battery wires
Ф6 (M6-2,5), 45cm
Electrical strength of insulation:
- between input (network) circuit and output circuits
of power-supply
- between input circuit and protection circuit
- between output circuit and protection circuit
2500 V AC min.
1500 V AC min.
500 V AC min.
Insulation resistance:
- between input circuit and output or protection
circuit
100 MΩ, 500 V DC
Storage temperature
-
20ºC...+60ºC
Vibrations and impulse waves during transport
according to PN-83/T-42106
1.3. Description of terminals.
Elements/connectors [Fig.1]
Description
[1]
LED for DC output voltage
[2]
Potentiometer - output voltage adjust
[3]
Connector of optical signalization LED
[4]
Power supply output (
V+
,
V-)
[5]
Battery connector (
B+, B-)
[6]
Jumper -battery charging current configuration:
Ibat =1,0 A
Ibat =4,0 A
Legend:
jumper installed,
jumper removed
[7]
L-N
- input voltage connectors 230 V,
– protective conductor connector
1.4. Dimensions and fitting of the PSB-12V10A power supply.