background image

www.pulsar.pl 

PSACH01244 

   

 

 

 

1.4 Specifications: 

     

- electrical specifications (tab.2) 

     - mechanical specifications (tab.3) 
     - operation safety (tab.4) 
     - operating specifications (tab.5) 

 
       Electrical specifications (tab. 2).

 

Mains supply 

230V AC  (-15%/+10%) 

Current consumption 

0,5A max. 

Power frequency 

50Hz  

Power of the S PSU 

100VA max. 

Output voltage 

U1

: 23÷28V AC (100% load ÷ 0% load) 

U2

: 25,5÷31,5V AC (100% load ÷ 0% load) 

AUX output current 

4A@24V AC max. or 3,7A@27V AC max.

 

Short-circuit protection SCP  

1x F 4A glass fuse 
- glass fuse damage requires fuse-element replacement 

Overload protection OLP 

circuit AC 24V: 1x F4A   
circuit AC 230V: 1x T1A  

Overheat protection OHP 

inside transformer 

Sabotage protection: 
- TAMPER output indicating enclosure 
opening 

 
- microswitch, NC contacts (enclosure closed), 
 0,5A@50V DC (max.) 

F1 fuse 
F2 fuse 

T 1A/ 250V 
F 4A/ 250V   

       

Mechanical specifications (tab. 3).

 

External dimensions of the PSU 

W=160, H=160, D=90 [+/- 2 mm] 

Mounting dimensions PSU 

W

1

=126, H

1

=145 [+/- 2 mm] 

Height glands 

H

2

=25 [mm] 

The number of cable glands/ Ø cables  2szt. / 4÷8mm 
Net/gross weight 

2,2/2,3 kg 

Enclosure 

ABS, IP65, light grey 

Closing 

Cheese head screw x 4 (at the front) 

Connectors 

Power supply: 

Φ0,63÷2,50 (AWG 22-10) 

Outputs: 

Ф0,63÷2,50 (AWG 22-10),  

TAMPER output: wires, 25cm 

Notes 

The enclosure has a removable mounting board with the PSU systems. 

       
 
 
 
 
 
 
 