          The unit should be installed in the metallic enclosure (cabinet) and, in order to meet the requirements of UE, the 
following rules should be observed: supply, development, shielding - accordingly to the application. The module requires 
20-22V AC power supply with galvanic separation (transformer insulation). 

 

2.2. Installation procedure 
 

1. Install the enclosure or cabinet and insert the cabling through the cable passes. 
2. Install the PSU module voltage reducer on the assembly bolts (the bolts should be installed prior to the operation of 
enclosure or cabinet assembling).  
3. Deliver the AC voltage to the 

~AC~

 terminals. 

4. Connect the conductors of consumers to the +AUX, -AUX terminals of the terminal box on the power-supply unit. 
5. If necessary, connect the conductors from the equipment to the technical outputs:  
 -  FAC; status indication AC (alarm panel, controller, signaling unit, LED diode, etc.)

 Use the 

T

AC

 (J1,J2) 

jumper to 

determine the indication time lag.

 

6. Using the dip switch I

BAT 

 the maximum current the battery should be determine, regarding  to the battery parameters.  

7. Using the dip switch P

BAT

 determine whether the function of disconnecting the discharged battery U<10V (+/-5%) is to 

be on or off. 

The battery protection is on

 

if the dip switch P

BAT

 is removed.

 

8. Activate the ~230V/AC supply (the AC red diode should be permanently illuminated, and AUX diode should be 
permanently illuminated) 
9. Check the output voltage (the PSU voltage without load should be anywhere between 13,6 V÷ 13,9 V, and during 
battery charging 11 V÷ 13,8 V). If the value of the voltage requires adjustment, the setting should be made by means of 
the potentiometer V

ADJ

, monitoring the voltage at the AUX output of the PSU. 

10. Connect the battery in accordance with the indications: +BAT red to ‘plus’ , -BAT black to ‘minus’, (the LB diode 
should go on and the lighting intensity should reduce with the charging time elapsed increasing). 
11. Once the tests and control operation have been completed, lock the enclosure, cabinet, etc. 

 
3. PSU module operation indication 

 

3.1. Optical indication 

The PSU module  is equipped with three diodes indicating operation status: AC, LB, AUX.  

 

AC-  red  diode

:  under  normal  status  (AC  supply)  the  diode  is  permanently  illuminated.  The  absence  of  AC 

supply is indicated by the AC diode going off.    

 

LB- red diode

: indicates the battery charging process; the intensity of illumination is dependent on the charging 

current: 

 

AUX

green diode

:  indicates the DC supply  status at the output of the PSU module. Under  normal  status, the 

diode is permanently illuminated and in the case of short-circuit or overload, the diode goes off.

 

 

3.2. Technical output 

The PSU module  is equipped with indication outputs: 

 

FAC - absence of AC supply output

: relay output indicates

 the absence of AC supply

. In case of power failure power 

supply unit will switch relay contacts after time set by jumpers T

AC

 (J1, J2). 

 

In Figure 2 configuration of contacts shows relay voltage-free state, which corresponds to the state 
signalling no AC network. 

 
 

4. Handling and operation 

4.1 Overload or short-circuits to the PSU module  output 

The AUX output of the PSU module  is equipped with the PTC polymer fuse assisted protection. If the load of the 

PSU module  exceeds Imax. (load 110% ÷ 150% @25ºC of the PSU module  power), the output voltage is automatically 
disconnected  and  this  is  indicated  by  the  green  diode  going  off.  The  voltage  at  the  output  may  be  restored  by 
disconnecting the output load for the period of about one minute. 
 

In  the  case  of  the  short-circuit  to  the  AUX,  BAT  output,  (load  200%  ÷  250%  of  the  PSU  module    power)  or 

incorrect connection of the battery, the fuse F

BAT

 in the battery circuit becomes permanently damaged and the restoration 

of the voltage at the BAT output requires the replacement of the fuse. 

 

4.2 Battery assisted operation 

In the case of power failure, in the unit will instantly switch to the battery assisted operation. 
In  order  to  activate  the  operation  of  the  PSU  module      from  the  battery  itself,  connect  the  BAT  connectors  in 

accordance  with  the  indications:  +BAT  red  to  ‘plus’  and,  -BAT  black  to  'minus’  of  the  battery  and  press  and  keep 
depressed for five seconds the START pushbutton on the equipment board.  

 
 
 

Summary of Contents for MSRK 2512

Page 1: ...MSRK 2512 v 1 1 MSRK 13 8V 2A Buffer PSU module swith mode EN Issue 3 from 16 09 2013 Supersedes the edition 2 from 16 12 2011 ...

Page 2: ...ram 1 3 Description of elements and connection links of the PSU module 1 4 Technical parameters 2 Installation 2 1 Requirements 2 2 Installation procedure 3 PSU module operation indication 3 1 Optical indication 3 2 Technical output 4 Handling and operation 4 1 Over loads or short circuits to the PSU module 4 2 Battery assisted operation 4 3 Maintenance 1 Technical description 1 1 General descript...

Page 3: ...eter voltage adjustment DC 4 FBAT fuse in the battery circuit 5 Connectors BAT DC supply output of the battery BAT red BAT black AUX DC supply output AUX U AUX GND FAC technical output for no AC network relay type In Figure 2 configuration of contacts shows relay voltage free state which corresponds to the state signalling no AC network 6 Optical signaling LED AC LED diode that indicates the prese...

Page 4: ...wels x 4 PCB fi 4 2 mm Net gross weight 0 08kg 0 13kg Connectors Outputs Ф0 41 1 63 AWG 26 14 Battery output BAT 6 3F 2 5 30cm Operation parameters tab 5 Operation temperature 10ºC 40ºC Storage temperature 20ºC 60ºC Relative humidity 20 90 without condensation Vibrations during operation unacceptable Impulse waves during operation unacceptable Direct insolation unacceptable Vibrations and impulse ...

Page 5: ...osure cabinet etc 3 PSU module operation indication 3 1 Optical indication The PSU module is equipped with three diodes indicating operation status AC LB AUX AC red diode under normal status AC supply the diode is permanently illuminated The absence of AC supply is indicated by the AC diode going off LB red diode indicates the battery charging process the intensity of illumination is dependent on ...

Page 6: ...the defect 5 Should the claim be accepted the manufacturer is obliged to provide warranty repairs at the earliest convenienve however not later that within 14 days from the delivery to the service centre of the manufacturer 6 The repair period mentioned in item 5 may be prolonged if there are no technical possibilities to carry out the repairs or if the equipment has been conditionally accepted du...

Reviews: