Pulsar MS 1012 Manual Download Page 5

www.pulsar.pl                                                                                        MS1012 

   

 

 

2. Installation. 
 

2.1. Requirements. 

The  buffer  PSU  module  is  to  be  mounted  by  a  qualified  installer,  holding  relevant  permits  and  licenses 

(applicable  and  required for a  given  country)  for  230V/AC  and  low-voltage  installations.  The  unit  should  be  mounted  in 
confined  spaces,  in  accordance  with  the  II-nd  environmental  class,  with  normal  relative  humidity  (RH=90%  maximum, 
without condensing) and temperature from -

10°C to +40°C.  

The unit should be mounted in a metal enclosure (cabinet) in a vertical position so as to ensure free, convection 

air flow through the vents.  

In order to meet the EU requirements, follow the guidelines on: power supply, enclosures and shielding:  

- according to application. The module requires 18

÷22V AC power supply with galvanic (transformer) isolation.

 

 

1. Output current 1A + 0,2A battery charge 
2. Output current 0,7A + 0,5A battery charge 
 

                        Total device c battery: 1,2A max. 

 

    As the PSU module is designed for a continuous operation and is not equipped with a power-switch, therefore 

an appropriate overload protection shall be guaranteed in the power supply circuit. Moreover, the user shall be informed 
about the method of unplugging (most frequently through separating and assigning an appropriate fuse in the fuse-box). 
The electrical system shall follow valid standards and regulations.

 

          

 

2.2. Installation procedure. 
 

1. Before installation, cut off the voltage in the 230V power-supply circuit.

 

2. Install the enclosure or cabinet and lead the cables through the cable ducts. 
3. Install the PSU module on mounting pins (the mounting pins should be installed before the assembly of the  
    enclosure/cabinet). 
4. Deliver the AC voltage to the ~AC~ terminals. 
5. Connect the 

receivers’ cables to the +AUX, -AUX terminals of the terminal box on the PSU board. 

6. Using the I

BAT 

 pins, determine the maximum battery charging current the should be determine, in accordance with 

     battery parameters. 
7. Make the connections between the battery and the power supply panel paying special attention to the correct polarity. 
8. Connect the ~ 230V AC power to the transformer (the AC diode and the AUX diode should be permanently 
illuminated). 
9. Check the output voltage (the PSU voltage 

without load should amount to 13,6V÷ 13,9V, during battery charging 

 

11V÷ 13,8V). If the value of the voltage requires adjustment, it should be set by the V

ADJ

 potentiometer, monitoring the  

  voltage at the AUX output of the PSU module.         
10. Check the current consumption of the receivers, taking into account the battery charging current, so as not to  
   exceed the total current efficiency of the PSU (section 1.1). 
11. Once the tests and control operation have been completed, close the enclosure/cabinet. 

 
3. Operating status indication. 

 

3.1 LED indication. 

The PSU module is equipped with three diodes indicating operating status: AC, LB, AUX.  

 

AC- red diode

: under normal status (AC supply) the diode is permanently illuminated. The absence of AC 

supply is indicated by the AC diode going off.    

 

LB - yellow diode

: indicates the battery charging process; the intensity of illumination is dependent on the 

charging current. 

 

AUX

green diode

: indicates the DC supply status in the output of the PSU module. Under normal status, 

the diode is permanently illuminated and in case of a short-circuit or overload, the diode goes off.

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 