1.2 Specifications: 
- electrical specifications (tab.2) 
- mechanical specifications (tab.3)       

 

        Table 2. 

Supply voltage 

27,6V DC  

Current consumption 

30mA max.  

Voltage of low battery indication 

U<23V +/- 3% 

Technical outputs: 

- FAC; output indicating AC power 
failure 

 
 
 
 
 
- FPS; output indicating DC 
absence/PSU failure 
 
-FLB output indicating low battery 
voltage 

 
- relay type: 1A@ 30VDC/50VAC, time lag: approx. 10s. 
- OC type, 50mA max., normal status: L (0V) level, failure: hi-Z level, time 
lag: 10s. 
CAUTION!  In  Fig.2.  the  contact  set  in  the  potential-free  status 
corresponds to a state with no AC power (AC power failure). 
 
 
- OC type, 50mA max., normal status: L (0V) level, failure: hi-Z level 
 
 
- OC type, 50mA max., normal status: (U

BAT

 >23V): L (0V), 

 failure: (U

BAT

 <23V): hi-Z level 

LED indication : 
- presence of AC power 
 
 
 
 
– 

presence of DC voltage at the 

PSU output 
 
- battery voltage level  

 
-red LED (fig.1, element 1). 

Under normal status (AC supply) the diode 

is permanently illuminated. The absence of AC supply is indicated by 
the AC diode going out.    
Caution: the LED indicates absence of AC power if the loss lasts minimum 
10s.   

-green  LED  (fig.1,  element  2) 

indicates  DC  power  at  the  PSU  output. 

Under normal status the diode is permanently illuminated. In case of a 
short circuit or an overload, the diode is off. 

-  green  LED  (fig.1,  element  3) 

indicates  battery  voltage  level.  Under 

normal  status  (U

BAT

  >  23V)  the  diode  is  permanently  illuminated.  In 

case of decrease of battery voltage (U

BAT

 < 23V) the diode is off. 

Operating conditions

 

temperature: -10 

o

C÷40

 o

C, relative humidity : 20%...90%, without 

condensation

 

Storage temperature 

-20ºC...+60ºC 

 
Table 3. 

D

imensions 

110 x 44 x 55 (LxWxH) [mm] (+/-2) 

Fixing 

M3 screws, mounting plate adjusted for PSB13,8V series power supplies 

Connectors 

Ф

0,41÷1,63 (AWG 26-14) 

Net/gross weight 

0,1/0,13 kg 

 
2.1. Requirements. 

 

The  module  is  to  be  mounted  by  a  qualified  installer,  holding  relevant  permits  and  licenses  (applicable  and 

required  for  a  given  country)  for  230V/AC  interference  and  low-voltage  installations.  The  unit  should  be  mounted  in 
confined  spaces,  in  accordance  with  the  2nd  environmental  class,  with  normal  relative  humidity  (RH=90%  maximum, 
without condensation) and temperature from -10°C to +40°C. 

The module shall be mounted with a PSU of PSB 27,6V series in a metal enclosure (cabinet, intended device). In 

order  to  fulfil  LVD  and  EMC  requirements,  the  rules  for:  power-supply,  encasing  and  screening  shall  be  followed, 
according to application.  

It is crucial to connect the PE wire to the appropriate PSU terminal. 

 

2.2. Installation procedure. 

1. Before installation of the module, make sure that the PSB 27,6V PSU supplying LEDs are disconnected from the 230V 
AC mains supply.  
2. Mount the module on the PSB 27,6V power supply unit. 
3. Cut the BAT+, BAT- leads in the PSB 27,6V PSU, separate and connect to the module, following the diagram. (fig.2). 
4. Cut the leads of the signal connector in the PSB 27,6V power supply unit, separate and connect to the module, 
following the diagram. Connect the Lac, Ldc, GND leads of the PSU with appropriate outlets on the automation module. 
(see fig. 4).   
5. Connect the technical outputs of the other device. 
6. Connect the 230VAC power cables. Connect the PE cable (yellow-green) to the appropriate PSU terminal (marked with 

 - earth symbol). 

 

 

Summary of Contents for MPSB24

Page 1: ...te PSU operating status presence of AC voltage presence of DC voltage battery voltage The module is also equipped with technical outputs of AC power loss PSU failure low battery voltage 1 1 Description of the module s components and connectors fig1 tab 1 Table 1 Element no Description 1 LED indicating presence of 230VAC voltage 2 LED indicating presence of DC voltage at the PSU output 3 LED indica...

Page 2: ...90 without condensation Storage temperature 20ºC 60ºC Table 3 Dimensions 110 x 44 x 55 LxWxH mm 2 Fixing M3 screws mounting plate adjusted for PSB13 8V series power supplies Connectors Ф0 41 1 63 AWG 26 14 Net gross weight 0 1 0 13 kg 2 1 Requirements The module is to be mounted by a qualified installer holding relevant permits and licenses applicable and required for a given country for 230V AC i...

Page 3: ... shock protection circuit is UNACCEPTABLE It can cause a device failure or an electric shock 7 Connect load loads to proper output connectors of the power supply positive pole is marked as V negative pole as V 8 Connect the battery in accordance with the signs colours 9 Once the tests and operation control have been completed the enclosure cabinet can be locked Fig 2 Diagram of connecting the modu...

Page 4: ...of the defect 6 Should the claim be accepted the manufacturer is obliged to provide warranty repairs at the earliest convenience however not later that within 14 days from the delivery to the service centre of the manufacturer 7 The repair period mentioned in item 6 may be prolonged if there are no technical possibilities to carry out the repairs or if the equipment has been conditionally accepted...

Reviews: