The mmWave Radar should be installed directly above the material to be measured, at a
90° angle. Avoid positioning near the process filling or emptying areas. Check there are
no obstructions between the sensor and the material. The mmWAVE Radars can be
installed via the 1” BSP/NPT thread on the sensor, or with the supplied 1” BSP to M20
adapter. Installing the mmWAVE Radar outside of a closed vessel, the following must
be adhered to:
•
The mmWave Radar must be directed vertically downwards.
•
Special permission must be granted by the appropriate national authority, to mount
the mmWAVE Radar closer than 4km from any radio astronomy stations.
•
The mmWAVE Radar must not be installed higher than 15m from the ground when
installed within 4-40km of a radio astronomy station.
•
The following table depicts the geographical location of Europe’s radio astronomy
stations (in alphabetical order):
Country
Station Name
Geographic
Latitude
Geographic
Longitude
Finland
Metsâhovin
60
°
13’04” N
24
°
23’37” E
Tuaorlan
60
°
24’57” N
22
°
26’40” E
France
Plateau de Bure
44
°
38’02” N
05
°
54’26” E
Floirac
44
°
50’07” N
00
°
31’33” W
Germany
Effelsburg
50
°
31’32” N
06
°
52’58” E
Hungary
Penc
47
°
47’23” N
19
°
16’53” E
Italy
Medicina
44
°
31’26” N
11°38’46” E
Noto
36
°
52’36” N
14
°
59’20” E
Sardinia
39
°
29’35” N
09
°
14’42” E
Poland
Krakow—Fort Skala
50
°
03’13” N
19
°
49’27” E
Russia
Kalyazin
57
°
13’22” N
37
°
54’01” E
Pulkovskoe
59
°
46’20” N
30
°
19’34” N
Pushchino
54
°
49’14” N
37
°
37’41 E
Zelenchuksaya
43
°
49’33” N
41
°
35’13” E
Spain
Pico Veleta
37
°
03’46” N
03
°
23’09” W
Robledo
40
°
49’53” N
04
°
14’57” W
Switzerland
Bleien
47
°
25’38” N
08
°
06’44” E
Sweden
Onsala
57
°
23’45” N
11
°
55’35” E
UK
Cambridge
52
°
09’59” N
00
°
02’20” E
Darnhall
53
°
09’22” N
02
°
32’03” W
Jodrell Bank
53
°
14’10” N
02
°
18’26” W
Knockin
52
°
47’24” N
02
°
59’45” W
Pickmere
53
°
17’18” N
02
°
26’38” W
Ex ia version
: This model must be connected via resistive barriers as described below:
Entity parameters are:
Power: Ui = 28V, li = 120mA, Pi = 0.83W. RS > 234Ω
Signal: Ui = 10V, li = 200mA, Pi = 0.5W. RS > 50Ω
Note:
Barrier with rated nominal resistance of Rs
≤ 250Ω is recommended for best
performance.
Ex mb version:
This model must be supplied from apparatus that provides protection
from prospective short circuits > 1500A.
Fuses are fitted in the safe area end of the cable.
Colour
Description
Comments
Red
DC Power +Ve
+28V DC max.
White
Signal
Black
DC 0V / ground
Connect to same point.
Green
Cable Screen
Blue
Not used.
Hidden within cable sheath.
Orange
Not used.
Hidden within cable sheath.
The following Notified Body has been involved in the conformity assessment process:
Notified Body
Certification Management Ltd.
Notified Body No. 2503.
Role:
Issue of ATEX / IECEx EU
type examination certificates.
Ex ia (IS)
ATEX; CML 17ATEX2227X
IECEx; CML 17.0125X
Ex mb
ATEX; CML 17ATEX5228X
IECEx; CML 17.0126X
ATEX coding
II 1 G Ex ia IIC T4 Ga &
II 1 D Ex ia IIIC T135
o
C Da
Tamb -20
o
C to +80
o
C.
II 2 G Ex mb IIC T4 Gb &
II 2 D Ex mb IIIC T135
o
C Db
Tamb -20
o
C to +80
o
C.
X Limitations on use
1.
The sensor must be routinely inspected to avoid build-up of dust layers if installed in
zones 20, 21 & 22 (Ex ia) and zones 21 & 22 (Ex mb).
2.
Electro-static hazard
– The equipment shall not be installed in a location where the
external conditions are conductive to the build up of electrostatic charge. In addition, the
sensor may only be wiped with a damp or anti-static cloth.
3.
The outer enclosure is made from Valox 357U, a polyester / polycarbinate blend;
consider the performance of this material with respect to chemicals that may be present.
4.
The sensor must not be used if there are any cracks or damage to the enclosure.
5.
(Ex ia) The installer shall consider the total length of cable attached to the sensor.
The cable shall be considered to have parameters of 200pF/m & 1uH/m or 30uH/Ω.
6.
(Ex ia) The sensor shall only be connected via resistive barriers with the following
specifications:
Power ≥ 234Ω, Signal ≥ 50Ω (TX & RX ≥ 50Ω).
7.
(Ex mb) Only use fuses listed: Littlefuse 0242 100mA (blue band)
> 1500A breaking.
Fuses must be located in a safe area.
8.
(Exmb) The equipment shall only be installed in areas where there is a low risk of
mechanical danger.
Name and position of person binding the manufacturer or authorised representative:
Signature
Name
Tim Brown
Function
Electronics Engineer
Location
Pulsar Process Measurement Ltd,
WR14 1JJ, UK.
Issue date:
28
th
November 2018.
General Installation
Hazardous Area Installation
EU Declaration of Conformity
Dimensions
This declaration of conformity is issued under the sole responsibility of the manufacturer.
Manufacturer / authorised representative
Pulsar Process Measurement Ltd.
Address
Cardinal Building
Enigma Commercial Centre
Sandys Road
Malvern
Worcestershire
WR14 1JJ
Country
UK
Declare that the following apparatus:
Product / Brand:
mmWAVE Radar (dBR16 & dBR8)
Models:
mmWAVE, mmWAVE-is
Conform to the following relevant EU legislation:
ATEX directive 2014/34/EU
EMC directive
2014/30/EU
RoHS directive 2011/65/EU
RED directive
2014/53/EU
Based on the following harmonised standards:
EN 60079-0: 2012+A11:2013
EN 60079-11: 2012 (Ex ia)
EN 60079-18:2015 (Ex mb)
EN 61326-1:2013
EN 302729: v2.1.1:2016
And therefore, complies with the relevant essential requirements for those directives.
13
0 m
m
Exmb
drip
shield
Exia
housing
Exia 84mm
Exmb 90mm
Optional protective front cover not shown