This chapter will explain how to undertake the various functions of your
IMP+ i.s.
. Where specific parameters are used, consult Parameter Guide in
Chapter 5.
Setting up Your Application
Empty Distance
Empty Distance (P105)
is the distance from the face of the transducer to
the material at the bottom of the vessel.
Span
Span (P106)
is the distance from the empty level (0% full) to span (100%
full).
Near and Far Blanking
Near blanking
(
P107
) is the distance from the face of the transducer that
the
IMP+ i.s.
will not record a level nearer than. A typical reason to increase
this from the default value would be if you wish to ignore close in
obstructions.
Far blanking
(
P108
) is the distance (as a percentage of empty level) beyond
the empty level that the
IMP+ i.s.
will read, the default is plus 20% of empty
level. If you wish to monitor further than the
empty level
, then increase this
figure, so that the
empty level
plus the
far blanking
figure (as % of empty
level) is greater than the surface being measured, within the capability of the
transducer being used.
The 4-20 mA Output
The mA output can be used to monitor remotely what the
IMP+ i.s.
is
showing, so it can be displayed remotely, integrated into a PLC, or used to
generate a record using a chart recorder or similar.
By default, the
IMP+ i.s.
will provide a 4-20 mA output that represents what is
displayed on the
IMP+ i.s.
, but these parameters can be overwritten as follows.