Table 3. Electrical parameters.
Models
HPSB-12V2A-B
HPSB-12V3A-B
HPSB-12V3A-C
HPSB-12V5A-C
HPSB-12V7A-C
HPSB-12V10A-C
HPSB-12V15A-D
HPSB-12V20A-E
PSU type
A (EPS - External Power Source), II environmental class
Supply voltage
~ 200 - 240 V
Current consumption
0,4 A
0,5 A
0,5 A
0,8 A
1 A
1,3 A
2 A
1,5 A
Power frequency
50/60 Hz
Inrush current
40 A
50 A
60 A
PSU power
35 W
48 W
48 W
76 W
97 W
138 W
207 W
276 W
Output current max.
2,5 A
3,5 A
3,5 A
5,5 A
7 A
10 A
15 A
20 A
Efficiency
87%
87%
87%
87%
87%
87%
87%
86%
Output voltage
11 - 13,8 V
– buffer operation
10 - 13,8 V
– battery-assisted operation
Adjustment range U
AUX
13,5
– 14,4 V
Ripple voltage (max.)
100 mV p-p
250 mV p-p
150 mV p-p
Current consumption by
the PSU systems during
battery-assisted operation
40 mA
40 mA
40 mA
15 mA
15 mA
30 mA
30 mA
30 mA
Fitting battery
7Ah
7Ah
17Ah
17Ah
17Ah
17Ah
40Ah
65Ah
Jumper selectable battery
charging current
0,5 A
0,5 A
0,5 A
I1: 0,5 A
I2: 1 A
I1: 1 A
I2: 2 A
I1: 1 A
I2: 4 A
I1: 2 A
I2: 4 A
I1: 2 A
I2: 4 A
I3: 8 A
Net / gross weight
1/1,1 kg
1,3/1,4 kg
1,7/1,8 kg
1,8/1,9 kg
2,3/2,4 kg
2,6/2,7 kg
5/5,6 kg
7/7,8 kg
Battery circuit protection
SCP and reverse polarity
connection
- polymer fuse
(returnable)
- polymer fuse
(returnable)
- polymer fuse
(returnable)
- F
BAT
fuse (in case of a failure, fuse-element replacement required)
Deep discharge battery
protection UVP
U<9,5 V (
± 5%) – disconnection of battery terminal
Optical indication
- LEDs on PCB of power supply unit
-
LED indicators on power supply’s cover (see section 3.1)
Tamper protection:
- TAMPER indicates
enclosure opening
- microswitch, NC contacts (enclosure closed),
0,5 A@50 V DC (max.)
Fuses: - F
BAT
-
-
-
T 6,3A/250V
F 8A/250V
T 10A/250V
T15A
T20A
Terminals:
Mains supply:
Outputs:
Battery outputs:
TAMPER:
0,5
– 2,5 mm
2
(AWG 26
– 12)
Battery wires 6,3F
– 45cm, angle muffs ML062
Battery wires
Ф6 (M6-2,5), 45cm
40cm wires
Notes
convectional cooling
Forced cooling