background image

www.pulsar.pl

                                                               

HPSB3524C                                                      

GREEN POWER

 

 

 

3

 

- HPS RN25024 (27,6V/24V) + LB8 8x0,3A (AWZ577 or AWZ580) +2x17Ah 

7. 

Buffer power supply unit HPSB 27,6V/2x5V÷18V/2x2A

 

÷1,3A/2x17Ah. 

HPS 2xDCDC20 (2x5V÷18V/2A÷1,3A)  + 2x17Ah 

8. 

Buffer power supply unit HPSB 27,6V/2x5V÷18V/2x2A

 

÷1,3A/8x0,5A/2x17Ah. 

HPS 2xDCDC20 (2x5V÷18V/2A÷1,3A) + 2xLB4 8x0,5A (AWZ574 or AWZ576) + 2x17Ah 

 

           1.2 Block diagram (fig.1)

 

 

 

 

Fig.1. The block diagram of the PSU. 

1.3 Description of PSU components and connectors ( tab.1, tab.2, fig.2).

 

Element no. 

 [Fig. 2] 

Description 

[1] 

PSU module 

[2] 

connectors (see: tab.2) 

[3] 

green LED 

indicates AC power 

[4] 

potentiometer,  

output voltage adjustment 

[5] 

BAT+/GND:  battery outputs

 + BAT=red, - GND=black 

[6] 

TAMPER,  

contact of sabotage protection

 (NC) 

[7] 

Additional connector for LED indication

 

[8] 

Selection jumper for charging current: 

 

  Ibat =0,5A 

 

  Ibat =1A 

Legend: 

 jumper installed, 

  jumper removed. 

Factory settings: Ibat =0,5A (jumper installed).

 

Tab.1. The components of the PSU. 

 

 

Element no. 

 [Fig. 2] 

Description 

L, N 

L-N  

power supply connector.   

 

Protection connector (electric shock protection) 

V+ 

V- 

DC supply output   
DC supply output   (GND) 

Tab.2. Output terminals of the PSU. 

Summary of Contents for HPSB 3524C

Page 1: ...HPSB 3524C v 1 0 HPSB 27 6V 3A 2x17Ah Buffer switching power supply unit EN Edition 8 from 24 10 2016 Supercedes the edition 7 from 11 08 2 ...

Page 2: ...ion A buffer PSU is intended for an uninterrupted supply to devices requiring stabilised voltage of 24V DC 15 The PSU provides voltage of U 27 6V DC Current efficiency 1 Output current 3A 0 5A battery charge 2 Output current 2 5A 1A battery charge Total device current battery 3 5A max In case of power decay a battery back up is activated immediately The PSU is constructed based on the switch mode ...

Page 3: ...connectors tab 1 tab 2 fig 2 Element no Fig 2 Description 1 PSU module 2 connectors see tab 2 3 green LED indicates AC power 4 potentiometer output voltage adjustment 5 BAT GND battery outputs BAT red GND black 6 TAMPER contact of sabotage protection NC 7 Additional connector for LED indication 8 Selection jumper for charging current Ibat 0 5A Ibat 1A Legend jumper installed jumper removed Factory...

Page 4: ...www pulsar pl HPSB3524C GREEN POWER 4 Fig 2 The view of the PSU ...

Page 5: ...of connection battery Sabotage protection TAMPER output indicating enclosure opening microswitch NC contacts enclosure closed 0 5A 50V DC max LED indication AC diode indicating AC power status AUX diode indicating DC power status at the PSU output red normal status on failure off green normal status on failure off Mechanical parameters tab 4 Enclosure dimensions 400 x 350 x 90 8 mm WxHxD Fixation ...

Page 6: ...ufficient convectional air flow through ventilating holes of the enclosure Before installation prepare a PSU load balance 1 Output current 3A 0 5A battery charge 2 Output current 2 5A 1A battery charge Total device current battery 3 5A max As the PSU is designed for a continuous operation and is not equipped with a power switch therefore an appropriate overload protection shall be guaranteed in th...

Page 7: ...amount to U 27 6V DC 9 After installing and checking proper working the enclosure can be closed 3 Operating status indication 3 1 LED indication of operating status The PSU is equipped with two diodes on the front panel 4 Operation and use 4 1 Overload or short circuit of the PSU output SCP on In case of overload the output voltage is automatically shut off and so is the LED indicator The restorat...

Page 8: ...c equipment should be disposed of separately from normal household waste CAUTION The power supply unit is adapted for cooperation with the sealed lead acid batteries SLA After the operation period they must not be thrown but recycled according to the applicable law Pulsar Siedlec 150 32 744 Łapczyca Poland Tel 48 14 610 19 40 Fax 48 14 610 19 50 E mail biuro pulsar pl sales pulsar pl http www puls...