Pulsar HPSB 20A12C Manual Download Page 7

www.pulsar.pl

                                                               

HPSB20A12C                                                    

GREEN POWER

 

 

 

7

 

RED LED: 

 

on – the PSU is supplied with 230V AC  

 

off – no 230V AC supply  

 

GREEN LED: 

 

on – DC voltage in the AUX output of the PSU 

 

off – no DC voltage in the AUX output of the PSU 

 

2.2 Installation procedure. 

 

1. Before installation, cut off the voltage in the 230V power-supply circuit.

 

2. Mount the PSU in a selected location and connect the wires. 
3. Connect the power cables (~230Vac) to L-N clips of the PSU. Connect the ground wire to the clip marked by the 
earth symbol PE (PSU module connector). Use a three-core cable (with a yellow and green PE protection wire) to 
make the connection. Lead the cables to the appropriate clips through the insulating bushing of the connection 
board. 
 

 

 

The shock protection circuit shall be performed with a particular care, i.e. the yellow and 
green wire coat of the power cable shall stick to one side of the terminal - marked with  

 symbol on the PSU enclosure. Operation of the PSU without the properly made and 

fully  operational  shock  protection  circuit  is  UNACCEPTABLE!  It  can  cause  a  device 
failure or an electric shock. 

 
4. Connect the 

receivers’ cables to the terminals V+ (+), V-(-) of the PSU module.  

5. Connect the power (~230V) 
6. Check the PSU output voltage: 
- the PSU voltage without load should amount to U=13,8V DC.   
7. Connect the battery (mind the colours):   
- battery output (+V):  BAT+ cable / red, 
- battery output (0V):  BAT 

– cable / GND / black. 

8. Check the PSU operation indicator: green LED on the power supply module. 
9. After installing and checking proper working, the enclosure can be closed. 
 

 
3. Operating status indication. 

The PSU is equipped with two diodes on the front panel:

 

 

 
 
 

 
4. Operation and use. 

 
4.1 Overload or short circuit of the PSU output (SCP on) 

In case of overload, the output voltage is automatically shut off, and so is the LED indicator. The restoration 

of the voltage takes place immediately after the failure (overload) is over. 

 

4.2 Disconnection of discharged battery. 

      The  PSU  is  equipped  with  the  discharged  battery  disconnection  system.  During  the  battery-assisted 

operation, reducing voltage below 9,5V at the battery terminals will cause battery disconnection. 

 

4.3 Maintenance. 

Any and all maintenance operations may be performed following the disconnection of the PSU from the 

power supply network. The PSU   does not require performing any specific maintenance measures, however, in 
case of significant dust rate, its interior is recommended to be cleaned with compressed air. In case of fuse 
replacement, use a replacement of the same parameters. 
 

 

 
 
 
 
 
 
 

Summary of Contents for HPSB 20A12C

Page 1: ...HPSB 20A12C v 1 0 HPSB 13 8V 20A 17Ah Buffer switch power supply unit EN Edition 2 from 24 10 2016 Supercedes the edition 1 from 04 03 2016 ...

Page 2: ...cifications 2 Installation 2 1 Requirements 2 2 Installation procedure 3 Operating status indication 4 Operation and use 4 1 Overload or short circuit of the PSU output SCP on 4 2 Disconnection of discharged battery 4 3 Maintenance 1 Technical description 1 1 General description A buffer PSU is intended for an uninterrupted supply to devices requiring stabilised voltage of 12V DC 15 The PSU provid...

Page 3: ... Connectors PSU L N power supply connector 230V AC Protection connector PE V V DC power output B B battery output green LED indicates AC power P1 potentiometer output voltage adjustment Battery outputs red black TAMPER contact of sabotage protection NC Additional connector for LED indication Selection jumper for charging current Ibat 2 A Ibat 4A Description jumper installed jumper removed ...

Page 4: ...www pulsar pl HPSB20A12C GREEN POWER 4 Fig 2 The view of the PSU ...

Page 5: ...ttery circuit protection SCP and reverse polarity connection melting fuse 30A Surge protection varistors Overvoltage protection OVP 16V activation requires disconnecting the load or supply for about 20 s Excessive discharge protection UVP U 9 5V 5 disconnect of connection battery Sabotage protection TAMPER output indicating enclosure opening microswitch NC contacts enclosure closed 0 5A 50V DC max...

Page 6: ...erature 2 Installation 2 1 Requirements The buffer PSU shall be mounted by a qualified installer with appropriate permissions and qualifications for 230V AC installations and low voltage installations required and necessary for a given country The device shall be mounted in confined spaces according to the environment class II with normal air humidity RH 90 max without condensation and the tempera...

Page 7: ...odule 5 Connect the power 230V 6 Check the PSU output voltage the PSU voltage without load should amount to U 13 8V DC 7 Connect the battery mind the colours battery output V BAT cable red battery output 0V BAT cable GND black 8 Check the PSU operation indicator green LED on the power supply module 9 After installing and checking proper working the enclosure can be closed 3 Operating status indica...

Page 8: ...c equipment should be disposed of separately from normal household waste CAUTION The power supply unit is adapted for cooperation with the sealed lead acid batteries SLA After the operation period they must not be thrown but recycled according to the applicable law Pulsar Siedlec 150 32 744 Łapczyca Poland Tel 48 14 610 19 40 Fax 48 14 610 19 50 E mail biuro pulsar pl sales pulsar pl http www puls...

Reviews: