www.pulsar.pl
HPSB11A12C
5
1.4 Specifications:
- electrical parameters (tab.3)
- mechanical parameters (tab.4)
- operation safety (tab.5)
- operating parameters (tab.6)
Electrical parameters (tab. 3)
PSU type
A (EPS - External Power Source)
Mains supply
176÷264V AC
Current up to
1.4A@230VAC
Power frequency
50÷60Hz
Supply power
155W max.
Efficiency
83%
Output voltage
13,8V DC – buffer operation
9,5V÷13,8V DC – battery operation
Output current
10 A + 1A battery charge
7 A + 4A battery charge
Output current t
AMB
<30°C
10 A + 1 A battery charge - refer to chart 1
7 A + 4 A battery charge - refer to chart 1
Output current t
AMB
=40°C
6,7 A + 1 A battery charge - refer to chart 1
3,7 A + 4 A battery charge - refer to chart 1
Voltage adjustment range
12÷14VDC
Ripple
120mV p-p max.
Battery charge current
1 A / 4 A @ 17Ah (± 5%) jumper selectable
Short-circuit protection SCP
electronic
Overload protection OLP
PTC polymer fuse
Overvoltage protection OVP
U>115% ÷ 150% of the output voltage (set), power
cut off, automatic return
Excessive discharge protection UVP
U<9,5 V (± 5%) –
disconnect of connection battery
LED indication:
- AC diode indicating AC power status
- AUX diode indicating DC power status at
the PSU output
- red, normal status – on, failure: off
- green, normal status – on, failure: off
Protection against sabotage:
- TAMPER indicates enclosure opening
- microswitch, NC contacts (enclosure closed),
0,5A@50V DC (max.)
Mechanical parameters (tab. 4)
Enclosure dimensions
280 x 292 x 80 + 8 [mm] (WxHxD)
Fixation
See figure 2
Fitting battery
17Ah/12V (SLA) max.
Net/gross weight
2,4 / 2,6 kg
Enclosure
Steel plate DC01, thickness: 0,7mm, colour: RAL 9003
Closing
Cheese head screw x 2 (at the front), (lock assembly possible)
Connectors
Power-supply: Φ0,63-2,50 (AWG 22-10)
Outputs: Φ0,63-2,50 (AWG 22-10), battery output BAT: 6,3F-2,5
TAMPER output: wires
Notes
The enclosure does not touch the assembly surface so that cables can be led.
Convectional cooling.
Operation safety (tab.5)
Protection class PN-EN 60950-1:2007
I (first)
Protection grade PN-EN 60529: 2002 (U)
IP20
Electrical strength of insulation:
- between input input and output circuits of the PSU (I/P-O/P)
- between input circuit and PE protection circuit (I/P-FG)
- between output circuit and PE protection circuit (O/P-FG)
3000 V/AC min.
1500 V/AC min.
500 V/AC min.
Insulation resistance:
- between input circuit and output or protection circuit
100 MΩ, 500V/DC