www.pulsar.pl HPSBOC2512B
GREEN POWER plus
6
Mechanical parameters (tab. 4)
Dimensions
W=250, H=250, D+D
1
=82+8 [+/- 2mm]
W
1
=255, H
1
=255 [+/- 2mm]
The dimensions of the
battery compartment
160x100x75mm (WxHxD) max
Fixation
See figure 2
Net/gross weight
1,8kg / 2,0kg
Enclosure
Steel plate, DC01 0,7mm colour: RAL 9003
Closing
Cheese head screw x 1 (at the front), (lock assembly possible)
Connectors
Power-supply:
Φ0,63-2,50 (AWG 22-10)
Outputs: Φ0,63-2,50 (AWG 22-10)
Battery output BAT: 6,3F-2,5
TAMPER output: wires
Notes
The enclosure does not touch the assembly surface so that cables can be led.
Operation safety (tab.5)
Protection class PN-EN 60950-1:2007
I (first)
Protection grade PN-EN 60529: 2002 (U)
IP20
Electrical strength of insulation:
- between input and output circuits of the PSU (I/P-O/P)
- between input circuit and PE protection circuit (I/P-FG)
- between output circuit and PE protection circuit (O/P-FG)
3000 V/AC min.
1500 V/AC min.
500 V/AC min.
Insulation resistance:
- between input circuit and output or protection circuit
100 MΩ, 500V/DC
Operating parameters (tab.6)
Operating temperature
-
10ºC...+40ºC (see: chart 1)
Storage temperature
-
20ºC...+60ºC
Relative humidity
20%...90%, without condensation
Vibrations during operation
unacceptable
Impulse waves during operation
unacceptable
Direct insulation
unacceptable
Vibrations and impulse waves during transport
According to PN-83/T-42106
Chart 1. Acceptable output current from the PSU depending on ambient temperature.
2. Installation.
2.1 Requirements.
The buffer PSU shall be mounted by a qualified installer with appropriate permissions and qualifications for
230V/AC installations and low-voltage installations (required and necessary for a given country). The device shall
be mounted in confined spaces, according to the environment class II, with normal air humidity (RH=90% max.
without condensation) and the temperature from -
10°C to +40°C. The PSU shall work in a vertical position that
guarantees sufficient convectional air-flow through ventilating holes of the enclosure.