www.pulsar.pl                                                      POE044812B   

GREEN POWER CCTV PoE

 

 

 

 

 

Fig. 5. Connection of cameras and network devices to the IN and AUX terminals. 

 

6. 

Use  the  F1/PTC1  ÷  F4/PTC4  jumpers  to  select  the  type  of  short  circuit  /  overload  protection  of  individual  circuits. 

Jumper in the Fx position 

– melting fuse activation, PTCx – PTC fuse activation. 

7. If needed, the following technical connections can be made: 
- FPS technical output of the PSU status 

– indicates the voltage loss at any of the outputs (AUX1 ÷ AUX4). 

TAMPER

 indicating enclosure opening. 

8. Check the power supply output voltage: 
- output voltage of the unloaded power supply without a battery should amount to U=54V DC. 
9. Connect the batteries in series according to the color markings: 
- battery output (+V): BAT+ cable/ red 
- battery output (0V): BAT- cable / black 
10. Check the optical indication of the PSU status: green LED light on the PoE module. 
11. Close the cover after installing and checking the operation of the power supply. 

 

3.  Power supply operation indication. 

 

3.1. Optical indication. 

The PSU has 11 LED lights at the front panel: 
 

 

 
 

 

 
 

 

 
 

 

RED LED: 

 

on – The PSU supplied with 230V AC voltage 

 

off – no 230V AC mains supply 

 

 
RED LED: 

 

on – DC voltage at the output of the switch mode PSU  

 

off – no DC voltage at the output of the switch mode PSU 

 

RED LED: 

 

on – fuse failure at one of the AUX1…AUX4 outputs 

 

off – no failure 

 

GREEN LED: 

 

on – DC voltage at the AUX1…AUX4 output 

 

off – no DC voltage at the AUX1…AUX4 output 

 

 

Additionally, the PSU is fitted with LED lights inside the enclosure 

– see Fig. 2 and 3: 

L

AC

 

red LED (Fig. 2, component 1) is permanently illuminated during normal operation (AC power ON).  

No AC power is indicated by turning off the 

L

AC 

LED. 

L

IN

 green LED (Fig. 2, component 1) indicates DC voltage at the PoE module input. During normal operation (DC 

supply) the LED is permanently illuminated. No DC no DC voltage at the module input is indicated by turning off the 

L

IN 

LED.  

L

FPS

 

red LED (Fig. 2, component 10) is not illuminated during normal operation (no failure). In case of activation of the 

short circuit / overload protection at any output, the LED is permanently illuminated.  

L1 ÷ L4

 green LEDs (Fig. 2, component 5) indicate voltage at the individual outputs of the module (L1 for AUX 1 etc.). 

Activation of the short circuit / overload protection of a given circuit is indicated by turning off one of the Lx  LEDs.  
 
 

Summary of Contents for GREEN POWER CCTV PoE POE044812B

Page 1: ...POE044812B v 1 0 PoE 54V 4x0 3A 4x7Ah PoE buffer power supply for up to 4 IP cameras EN Edition 3 from 15 11 2017 Supersedes the edition 2 from 22 11 2016 GREEN POWER CCTV PoE...

Page 2: ...ay and OC type LED optical indication protections SCP short circuit protection OVP overvoltage protection Surge protection Antisabotage protection OLP overload protection Mounting plate for mounting t...

Page 3: ...AUX1 etc In addition the FPS output hi Z state and LFPS LED are activated and the relay contacts change their position The PSU is housed in a metal enclosure with signaling panel equipped with a micr...

Page 4: ...camera connection 7 Network inputs Ethernet 8 FPS technical output indicating failure OC type 9 FPS technical output indicating failure relay type 11 Optional external optical indication connector fac...

Page 5: ...agram 1 Output current tAMB 40 C 4 x 0 2A see diagram 1 Ripple voltage 150 mV p p max Current consumption by the PSU 65mA Battery charging current 0 3A max 4x7Ah 5 Approximate backup time 9h 43min Sho...

Page 6: ...se Table 5 Protection class PN EN 60950 1 2007 I first Protection grade PN EN 60529 2002 U IP20 Insulation electrical strength between input network circuit and the output circuits of the PSU I P O P...

Page 7: ...the camera can be done using UTP 3 cable networks with data rates up to 10 Mbit s or UTP 5 cable Due to the lower resistance wiring it is recommended especially at large distances between the power s...

Page 8: ...l RED LED on The PSU supplied with 230V AC voltage off no 230V AC mains supply RED LED on DC voltage at the output of the switch mode PSU off no DC voltage at the output of the switch mode PSU RED LED...

Page 9: ...or PTC polymer fuses The Fx PTCx jumper position determines which fuse is used If the power supply load current exceeds Imax 110 150 25 C of the PSU power the output voltage is automatically disconne...

Page 10: ...tronic equipment should be disposed of separately from normal household waste CAUTION The power supply unit is adapted for cooperation with the sealed lead acid batteries SLA After the operation perio...

Reviews: