F15
High battery
temp.!
PSU FLT,
ALARM
- Too high ambient temperature of the PSU.
- Overloaded batteries.
- Faulty batteries.
Section 7.7
F16
No battery!
APS FLT,
ALARM
- Disconnected batteries
Section 7.1
F17
Battery fail!
APS FLT,
ALARM
- Deeply discharged batteries, voltage below 20 V
Section 7
F18
High batt. circuit
resist.!
APS FLT,
ALARM
- Spent batteries
- Loose cables connecting the batteries
Section 7.6
F19
High AC voltage!
PSU FLT,
ALARM
- Mains supply over 254 V AC
Section 6.2.5.
F20
Low AC voltage!
PSU FLT,
ALARM
- Mains supply below 195 V AC
Section 6.2.5.
F21
PSU cover
opened!
PSU FLT,
ALARM
Section 6.6
F50-
F54
Internal supply
fail!
PSU FLT,
ALARM
- service codes
F60
No
communication
PSU FLT,
ALARM
- no communication with LCD panel
F61-
F64
Control panel fail
PSU FLT,
ALARM
- service codes
F65
Access unlocked
- passwords unlocked
Table 9. List of PSU message codes.
Message
code
Description
I00
No battery!
I01
Battery fail!
I02
High batt. circuit resist.!
High AC voltage!
I03
Low AC voltage!
I04
PSU cover opened!
I05
Internal supply fail!
I06
No communication
I07
Control panel fail
I08
Access unlocked
I09
No battery!
I10
Battery fail!
I11
High batt. circuit resist.!
I12
High AC voltage!
I13
Low AC voltage!