Pulsar EN54-5A17LCD Manual Download Page 31

www.pulsar.pl   

 

 

 

EN54-5A17LCD 

 

 

 

    

RED POWER

 

 
 

31 

- press the „SET” button, the prompt will appear at the end of the line 
 
 
 
 
 
 
- use the „<” or „>” buttons to set the delay time: 

- 10s 
- 1min 
- 10min 
- 30min

 

 
 
 
- confirm by pressing the „SET” button 
 
 
 
 
 
 

 

7.2.5. Setting the communication address 

 applies to cooperation with PowerSecurity. 

 
 

 

 
All power supplies are factory-set to address 1. 
 

All  the  parameters  responsible  for  communication  between  the  PSU  and  the  computer,  namely  the 

address, parity and speed should have the same settings for both the PSU and the PowerSecurity program. 
Communication address allows to identify power supply units in the same communication network. 
 
 
 
 
 
 
 
 
- use the „<” or „>” buttons to display the 

Communication address 

menu 

 
 
 
 
 
 
 
 
- press the „SET” button, the prompt will appear at the end of the line 
 
 
- use the „<” or „>” buttons to set the communication address 

1÷ 247

  – PSU address during the communication with the computer 

 
 
 
- confirm by pressing the „SET” button 
 

 
 

 
 

Summary of Contents for EN54-5A17LCD

Page 1: ...EN54 5A17LCD v 1 0 EN54 27 6V 5A 2x17Ah LCD power supply for fire alarm systems EN Edition 1 from 28 11 2013 Supersedes the edition LCD Version...

Page 2: ...OSURE OPENING TAMPER 23 6 8 INCREASING THE NUMBER OF OUTPUTS WITH OPTIONAL EN54 LB4 OR EN54 LB8 FUSE MODULES 23 6 9 OVERVOLTAGE PROTECTION OF THE PSU OUTPUT OVP 24 6 10 PSU OVERLOAD 24 6 11 INDICATION...

Page 3: ...TURE MEASUREMENT 39 8 8 STANDBY TIME 39 9 REMOTE MONITORING OPTIONS WI FI ETHERNET RS485 USB 40 9 1 COMMUNICATION VIA THE USB TTL INTERFACE 40 9 2 ETHERNET NETWORK COMMUNICATION 40 9 3 THE WI FI WIREL...

Page 4: ...m PowerSecurity to monitor the performance of the PSU remote control options WiFi Ethernet RS485 USB remote battery test required additional modules cooperation with optional EN54 LB4 or EN54 LB8 fuse...

Page 5: ...al CD Red mounting spacers 4 pieces Red metal mounting brackets for hanging the power supply 4 pieces M8x16 mounting screws 4 pieces PG9 cable glands 4 pieces PG11 cable glands 4 pieces Battery serial...

Page 6: ...circuit YES YES Low battery indication YES YES Deep discharge battery protection YES YES Protection against short circuit of the battery terminals YES YES Blown battery fuse indication YES YES Chargin...

Page 7: ...tput current Imax b 5A In case of power loss the PSU switches to battery power providing uninterruptible power supply The PSU is enclosed in a metal casing color RAL 3001 red with battery housing for...

Page 8: ...oltage AUX2 AUX2 output voltage OVL PSU overload APS battery failure PSU PSU failure ALARM collective failure EXTi EXTi input status EXTo EXTo relay output status LB battery charging 11 Terminals AC A...

Page 9: ...omponents of the PCB of the EMC filter Fig 3 Element No Description FMAINS fuse in the power supply circuit 230V T6 3A 250V L N power supply connector 230V AC PE protective connector Connector for con...

Page 10: ...nal module INTR INTE INTW 5 Place to install the EN54 LB4 or EN54 LB8 fuse module 6 TAMPER microswitch contacts of antisabotage protection NC 7 EMC filter module see Table 2 Fig 3 8 2x17Ah batteries 9...

Page 11: ...cables Installation cables should be firmly connected to the battery side terminals and to the power supply connector The side walls of the housing include the embossings which should be used to carry...

Page 12: ...g 4 Connect the batteries with the PSU paying special attention to the correct polarity Batteries must be connected in series using the special cable included 6 Switch on the 230V AC supply The corres...

Page 13: ...e parameters which should be displayed Fig 7 Control panel Table 6 The description of the buttons and LEDs of the LCD panel moves the pointer on the screen next screen selection selection approval qui...

Page 14: ...he LCD Main screen of the LCD displays the basic electrical parameters and indicates the current status of the power supply Fig 9 Main screen of the LCD The resolution of voltage and current measureme...

Page 15: ...starts the preview menu allowing to choose one of the four available PSU screens Use the or buttons to choose a proper screen and press the SET button to confirm current parameters of the PSU see sec...

Page 16: ...current flashing Imax a exceeded See section 6 10 6 11 PSU failure indication highlighted PSU failure See sections 6 4 6 6 5 Battery failure indication highlighted battery failure See sections 6 4 6 6...

Page 17: ...re of the highest priority If there are more than five failures at the same time use the or buttons to display the next failure 6 4 4 LCD screen history of the parameters To set the screen press the E...

Page 18: ...nimum the lowest value measured during 5 minutes maximum the highest value measured during 5 minutes of the following parameters UAC mains supply voltage 230V AC UAC MIN mains supply voltage minimum U...

Page 19: ...ying information about the fault type time of occurrence and the values of other electrical parameters In addition the diagnostic system assigns the failure code for a particular event on the basis of...

Page 20: ...ing circuit failure Low AUX1 voltage F09 Low AUX2 voltage PSU FLT ALARM Output voltage below 26V F10 Low battery voltage APS FLT ALARM The battery voltage has dropped below 23V during battery assisted...

Page 21: ...re The output indicates a failure in the battery circuit Under normal status during correct operation the output is closed In case of failure the PSU will switch the output into the open position Fail...

Page 22: ...n between the PSU s systems and the attached devices Fig 18 Electrical diagram of the EXT IN input The connection of external devices to the EXT IN input is shown in the electrical diagram below OC ou...

Page 23: ...circuit on the line could cause damage to other receivers connected to the same output The solution is provided by the optional fuse module EN54 LB4 4 channel or EN54 LB8 8 channel while its mounting...

Page 24: ...croprocessor may disconnect the AUX1 and AUX2 outputs and switch into the battery assisted operation Restart will occur after 1 minute PSU overload is indicated by the PSU FLT and ALARM technical outp...

Page 25: ...password full access to the PSU s settings User s password locked access to the PSU settings menu Table11 Access ranges Access range PASSWORD Control panel settings PSU settings SERVICE USER Preset p...

Page 26: ...hange it To do this choose a password that will be changed user s password or service password and enter the new one 7 1 3 Disabling the password If the password is not required it can be turned off T...

Page 27: ...by pressing the SET button When on the keyboard will be locked automatically if no buttons are pressed within 5 minutes After this time pressing any button on the control panel will display a window w...

Page 28: ...4 6 NO acoustic indication OFF Section 7 2 2 EXTo output ON output ON see section 4 9 OFF output OFF Section 7 2 3 Delay time for EPS output Setting the delay time for AC power failure indication 10s...

Page 29: ...1 1 signal every 10s battery mode AC power failure 2 1 signal every 10s mains operation Battery failure undercharged batteries 3 2 signals every 10s battery mode Low battery level 4 Fast signals batt...

Page 30: ...mation about the changes in the EXTo output is written in the event log of the PSU use the or buttons to display the EXTo output menu press the SET button the prompt will appear at the end of the line...

Page 31: ...ers responsible for communication between the PSU and the computer namely the address parity and speed should have the same settings for both the PSU and the PowerSecurity program Communication addres...

Page 32: ...e the same settings for both the PSU and the PowerSecurity program The PSU has preset transmission parameters of 115200 baud 8E1 if these values were changed they should be restored to original settin...

Page 33: ...isplayed messages Intensity of the LCD backlight can be set in the range from 0 to100 in 10 intervals The display features a function of constant or temporary backlight mode In temporary mode the scre...

Page 34: ...t date according to which error messages and operation history will be saved Built in real time clock does not take into account leap years and the changes resulting from the switch between summer and...

Page 35: ...the SET button the prompt will appear next to the hour digits use the or buttons to set the hour press the SET button the prompt will appear next to the minute position use the or buttons to set the m...

Page 36: ...st of the display text use the or buttons to display the Contrast menu press the SET button the prompt will appear at the end of the line use the or buttons to set the contrast confirm by pressing the...

Page 37: ...RED POWER 37 press the SET button the prompt will appear at the end of the line use the or buttons to select YES blinking light indicating failure ON NO blinking light indicating failure OFF confirm...

Page 38: ...ase of incorrect connection the FBAT fuse in the battery circuit becomes damaged The return to normal operation is possible only after replacing the fuse and correct connection of the batteries 8 4 De...

Page 39: ...tteries hence temperature readings should not be confused with the ambient temperature Temperature measurement and compensation of the battery charging voltage can extend the life of the batteries 8 8...

Page 40: ...power supply unit power supply current consumption used for the calculation of standby time should be taken into account see section 8 8 9 1 Communication via the USB TTL interface The easiest way of...

Page 41: ...mounted in a hermetic enclosure protecting against adverse environmental conditions Fig 31 Ethernet communication using the RS485 Ethernet INTRE interface 9 3 The Wi Fi wireless communication The Wi F...

Page 42: ...adverse environmental conditions Fig 33 The The Wi Fi communication using the RS485 WIFI INTRW interface 9 4 RS485 network communication Another type of network communication is the RS485 communicati...

Page 43: ...of the program into smaller areas depending on the number of monitored power supplies The program is equipped with manager mode which allows the grouping of power supplies for easier analysis and orie...

Page 44: ...attery voltage indication Ubat 23V during battery mode Overvoltage protection OVP U 30 5V 0 5V disconnection of the output voltage AUX disconnection automatic return Short circuit protection SCP F6 3A...

Page 45: ...EP 17 12 or 2 x GP12170 Net gross weight 9 7 10 8 kg Enclosure Steel plate DC01 1 2mm color RAL 3001 red Closing Key lock Terminals Mains supply 0 51 2 AWG 24 12 Outputs 0 51 2 AWG 24 12 Battery outp...

Page 46: ...ear During the inspection check the batteries and run the battery test 4 weeks after installation re tighten all threaded connections see Fig 2 11 and Fig 3 2 11 1 Battery replacement of the LCD panel...

Page 47: ...thin 14 days from the delivery to the service centre of the manufacturer 6 The repair period mentioned in point 5 may be prolonged if there are no technical possibilities to carry out the repairs or i...

Page 48: ...ulsar pl EN54 5A17LCD RED POWER 48 Pulsar K Bogusz Sp j Siedlec 150 32 744 apczyca Polska Tel 48 14 610 19 40 Fax 48 14 610 19 50 e mail biuro pulsar pl sales pulsar pl http www pulsar pl www zasilacz...