4.5. Battery charging time.
The PSU has a battery circuit charged with direct current. The current selection is done via
I
BAT
jumpers.
The table below shows how long it takes to charge a (fully discharged) battery up to min. 80% of its nominal
capacity.
Table 9. Battery charging time.
40Ah
battery charging time
up to capacity of 0,8*C
Charging
current [A]
Configuration of
I
BAT
jumper
12h
3
J1=
, J2=
, J3=
16h24m
2,2
J1=
, J2=
J3=
24h
1,5
J1=
, J2=
J3=
-
0,6
J1=
, J2=
J3=
4.6 Operation without a battery.
In case of an expected PSU operation without an attached battery, make a necessary configuration setting
from the level of the LCD desktop (see chapter 3.4.2, table 7).
”Settings -> PSU -> Battery present: YES/NO”
In this mode the automation system allows adjustments of PSU’s output voltage without indicating a failure
connected with working of the battery.
CAUTION. During operation without battery assistance the PSU does not perform any parameter
control that monitors its proper operation. Therefore, this mode ought to be chosen thoughtfully.