BLACK POWER

 

 

 

22 

5.5  Technical outputs. 

The  PSU  feature  indication  outputs,  with  galvanic  isolation,  which  change  their  state  if  any  of  the  following 

events occur: 

 

 

EPS FLT - output indicating 230 V power loss

The output indicates 230 V power loss. Under normal status (with 230 V supply on) the  
output is closed. In case of power failure, the PSU will switch the output into the open position after a 

time lag set by the 

T

AC

 jumpers (J1, J2). 

 

 

 

 

J1= 

, J2= 

  time lag T= 5s 

 

 

 

 

J1= 

, J2= 

  time lag T= 140s 

 

 

 

 

J1= 

, J2= 

  time lag T= 17m 

 

 

 

 

J1= 

, J2= 

  time lag T= 2h 20m 

Caption: 

 jumper on, 

  jumper off 

 

 

 

APS FLT - output indicating battery failure.

  

The output  indicates a failure in the  battery circuit. Under normal status (during correct operation) the 

output is close. In case of a failure the PSU will switch the output into the open state. Any failures can be 
triggered by the following events: 

 

 

- a faulty or undercharged battery 

 

 

- battery voltage below 23 V during battery-assisted operation 
- battery fuse failure 
- no continuity in the battery circuit 

 

 

PSU FLT - output indicating PSU failure

.  

The output indicates the PSU failure. Under normal status (during correct operation) the output is close. 

In case of a failure the PSU will switch the output into the open state. Any failures can be triggered by the 
following events: 

 

 

- low output voltage Uaux<23,6 V 

 

 

- high output voltage Uaux>29,4 V 

 

 

- high battery voltage Uaku>28 V (during battery test) 

 

 

- polymer fuse PTC activation 
- exceeding the PSU nominal current 
- failure in the battery charging circuit 
- activation of the over voltage protection OVP   

 

- enclosure opening - TAMPER 
- internal damage of the PSU 

                         - EXT IN input activation 

 

 

The technical outputs have been implemented with galvanic isolation between the P

SU’s systems and the 

attached devices. 
 

 

Fig. 8. Electrical diagram of the technical outputs.  

 

 

5.6  Input of collective failure EXT IN. 

 The EXT IN (external input) technical input indicating a collective failure is intended for additional, external 

devices that generate the failure signal. The voltage at the EXT IN input will save information about an incident in 
the internal memory of the power supply and sending the signal about the failure to the PSU FLT output. 

   The EXT IN technical input has been impl

emented with galvanic isolation between the PSU’s systems  

and the devices attached.  

 

 

                                                 Fig. 9. Electrical diagram of the EXT IN input. 
 

Summary of Contents for BLACK POWER PSBEN 2024B

Page 1: ...PSBEN 2024B v 1 1 PSBEN 27 6V 2A 2x7Ah EN Buffer switch mode power supply unit Grade 3 EN Edition 8 from 31 01 2019 Supercedes edition 7 from 02 11 2017 LED Version...

Page 2: ...s to cooperation with PowerSecurity 19 5 3 4 Setting the transmission speed trS applies to cooperation with PowerSecurity 20 5 3 5 Setting the parity of the transmission trP applies to cooperation wit...

Page 3: ...www pulsar pl PSBEN2024B BLACK POWER 3 TABLE 13 ELECTRICAL PARAMETERS 32 TABLE 14 MECHANICAL PARAMETERS 33 TABLE 15 SAFETY OF USE 33 9 TECHNICAL INSPECTIONS AND MAINTENANCE 34...

Page 4: ...overcharge protection battery output protection against short circuit and reverse polarity connection jumper selectable battery charging current 0 2 A 0 6 A 1 A 1 5 A remote battery test additional m...

Page 5: ...ES YES No battery charge YES YES Low output voltage YES YES High output voltage YES YES PSU failure YES YES Surge protection YES YES Short circuit protection YES YES YES YES Overload protection YES YE...

Page 6: ...is not mounted in an installation complaint with the EN 50131 standard the acceptable current efficiency amounts to 1 Output current 2 A 0 2 A battery charge 2 Output current 1 6 A 0 6 A battery charg...

Page 7: ...ACK POWER 7 3 2 Block diagram The PSU is manufactured based on a high duty system of DC DC converter The microprocessor system is responsible for full diagnostics of the PSU and battery parameters Fig...

Page 8: ...button disconnection of the PSU during battery assisted operation pin activation of the acoustic indication indication on indication off Caption jumper on jumper off VADJ potentiometer DC voltage adju...

Page 9: ...nt no Description Insolation transformer PSU board see Tab 1 fig 2 TAMPER micro switch contacts of tamper resistance NC FMAINS fuse in the supply circuit 230 V L N power supply connector 230 V protect...

Page 10: ...g surface The grip is located in the central part of the enclosure see fig 3 7 and guarantees indication in case of any attempts of detaching the device from the mounting surface Proper installation i...

Page 11: ...ation at the APS FLT output but it does not affect the protection system against complete battery discharge 11 Check the current consumption of the receivers taking into account the battery charging c...

Page 12: ...g 5 Control panel Table 5 The description of the buttons and LEDs of the LED panel Description Additional information moves the pointer on the screen next screen selection selection approval red LED i...

Page 13: ...e voltage indicator displays the measured output voltage at the AUX output If the voltage drops below 26 V during operation with activated battery test or exceeds 29 4 V the PSU will indicate a failur...

Page 14: ...tically displayed if the memory has more failures pressing the OK button will result in displaying subsequent codes the parameter on the display marks the end of the list of failures 5 2 4 Current fai...

Page 15: ...e code will be automatically displayed if the memory has more failures pressing the OK button will result in displaying subsequent codes the parameter on the display marks the end of the list of failu...

Page 16: ...Low battery voltage APS FLT the battery voltage has dropped below 23 V during battery assisted operation F11 Low battery volt off APS FLT the battery voltage has dropped below 20 V during battery ass...

Page 17: ...bols Symbol Description Additional information Battery test tSt On battery test on OFF battery test off Sections 5 3 1 LED display dimmer On dimmer ON OFF dimmer OFF Sections 5 3 2 Communication addre...

Page 18: ...your choice with the OK button in order to return to the main menu simultaneously press the rightmost and leftmost buttons on the LED panel Deactivating activating the test with the STOP button on the...

Page 19: ...mer on OFF dimmer off confirm by pressing OK in order to return to the main menu simultaneously press the rightmost and leftmost buttons 5 3 3 Setting the communication address Adr applies to cooperat...

Page 20: ...ss parity and speed should have the same settings for both the PSU and the PowerSecurity program The PSU has preset transmission parameters of 115200 baud 8E1 However if it is connected to the network...

Page 21: ...he panel use the or buttons in order to set the required communication mode 8N2 8E1 factory setting 8O1 confirm by pressing OK in order to return to the main menu simultaneously press the rightmost an...

Page 22: ...dicates the PSU failure Under normal status during correct operation the output is close In case of a failure the PSU will switch the output into the open state Any failures can be triggered by the fo...

Page 23: ...ee a correct cooperation between the module and the EXT IN input the VEXT jumper must be on and the connections are to be made accordingly to the diagram below Fig 11 Example of a connection with the...

Page 24: ...ted by the OVP yellow LED on the PCB board and the PSU FLT output 5 9 PSU overload The PSU is fitted with the LED OVL overload on the PCB and indicator on the LED panel informing about output overload...

Page 25: ...s voltage The protection mode is off when the PBAT jumper is removed Caution Deactivating of the UVP function is not recommended since a deep discharge of the battery limits its capability of storing...

Page 26: ...y charging time The PSU has a battery circuit charged with direct current The current selection is done with use of the IBAT jumpers The table below shows how long does it take to charge a fully disch...

Page 27: ...power supply unit power supply current consumption used for the calculation of standby time should be taken into account see section 6 4 7 1 Communication via the USB TTL interface The easiest way of...

Page 28: ...g against adverse environmental conditions Fig 14 Ethernet network communication using the RS485 INTRE interface 7 3 The Wi Fi wireless communication The Wi Fi wireless communication can be implemente...

Page 29: ...inst adverse environmental conditions Fig 16 The Wi Fi communication using the RS485 WIFI INTRW interface 7 4 RS485 network communication Another type of network communication is the RS485 communicati...

Page 30: ...wer supplies in case of failures the backlight changes accordingly in both the manager window and the Windows taskbar In addition the program allows you to download the operation history of the power...

Page 31: ...ynoptic board or the list mode This is especially useful when the PowerSecurity program works with a large number of power supplies The application enables both visualization and analysis of read data...

Page 32: ...the output voltage AUX disconnection automatic return Short circuit protection SCP Electronic current limitation and or FBAT fuse failure in the battery circuit requires fuse replacement Automatic ret...

Page 33: ...Mounting See Fig 3 Net gross weight 5 5 5 9 kg Enclosure Steel plate DC01 1mm color RAL 9005 black Closing Cheese head screw x2 at the front lock assembly possible Terminals Supply 0 63 2 50 AWG 22 10...

Page 34: ...batteries and run the battery test 4 weeks after installation re tighten all screw connections see Fig 2 9 WEEE LABEL According to the European Union WEEE Directive waste electrical and electronic eq...

Reviews: