Pulsar BLACK POWER PSBEN 2012C Manual Download Page 8

www.pulsar.pl   

 

 

 

PSBEN2012C   

 

 

 

 
 

            

3.2 Overview of current failures. 

If any incorrect electrical parameters occur, the PSU will signal the failure  by illuminating an appropriate LED 

on the panel or by activating an acoustic indication (provided it has not been switched off). After pressing the ‘OK’ 
button,  the  panel  display  will  show  a  code  of  the  fault  that  trigger  the  failure.  If  more  than  one  failure  occurs 
simultaneously, another pressing the ‘OK’ button will display the next failure code. 

In  chapter  9  all  possible  failure  codes  that  can  appear  during  the  PSU’s  operation  have  been  shown.  Each 

code  is  accompanied  by  an  appropriate  LED  indication  on  the  panel,  acoustic  indication  and  switching  of  a 
dedicated technical output. 

 
 

3.3 Overview of failure memo. 

The device remembers 30 last failures in non-volatile memory which enables a subsequent overview. 

 
Entering the failure memo overview mode: 
With the “<”, “>” buttons choose the FLt position and approve by pressing “OK”. The number of the failure will  be 
displayed, then its code. Pressing “OK” again will display the next failure in the memory.  
 
 

3.4 Acoustic indication. 

Emergency situations are acoustically indicated. The frequency and the number of signals depend on an event 

type (see chapter 9). The acoustic indication is off after removing an appropriate jumper (fig. 2, [5]). 

 
Table 4. Acoustic indication. 

No. 

Description 

Event 

1 signal per 10s, battery-assisted operation 

No 230V AC supply 

1 signal per 10s, mains operation 

Battery fault, undercharged battery 

2 signals per 10s, battery-assisted operation 

Low level of battery charge 

Fast signals, battery-assisted operation 

The PSU will be disconnected due to the battery 
discharge 

Continuous indication 

PSU failure [see chapter 9] 

1 signal 

Breaking the battery test 

2 signals 

Activation of the battery test 

 

 

3.5 Technical outputs. 

The  PSU  feature  indication  outputs,  with  galvanic  isolation,  which  change  state  if  any  of  the  following  event 

occur: 

 

 

EPS FLT – output indicating AC power loss

The output indicates AC power loss. Under normal status – with the 230V AC supply, the output is 

close.  In  case  of  a  power  failure  the  PSU  will  switch  the  output  into  the  open  state  after a  period  of  time 
determined by the T

AC

 (J1, J2) jumpers. 

 

 

 

 

J1= 

, J2= 

  time lag T= 5s 

 

 

 

 

J1= 

, J2= 

  time lag T= 140s 

 

 

 

 

J1= 

, J2= 

  time lag T= 17m 

 

 

 

 

J1= 

, J2= 

  time lag T= 2h 20m 

Caption: 

 jumper on, 

  jumper off 

 

 

APS FLT - output indicating battery failure.  

The output indicates a failure in the battery circuit. Under  normal status (during correct operation) the 

output is close. In case of a failure the PSU will switch the output into the open state. Any failures can be 
triggered by the following events: 

 

 

- a faulty or undercharged battery 

 

 

- battery voltage below 11,5V during battery-assisted operation 
- battery fuse fault 
- no continuity in the battery circuit 

 

 

PSU FLT - output indicating PSU failure.  

The output indicates the PSU failure. Under normal status (during correct operation) the output is close. 

In case of a failure the PSU will switch the output into the open state. Any failures can be triggered by the 
following events: 

 

- low output voltage Uaux<11,8V 

 

 

- high output voltage Uaux>14,7V 

Summary of Contents for BLACK POWER PSBEN 2012C

Page 1: ...PSBEN 2012C v 1 0 PSBEN 13 8V 2A 17Ah EN Buffer switched mode power supply unit EN Edition 3 from 20 11 2012 Supersedes the 2 from 14 09 2012 edition...

Page 2: ...0 4 4 STANDBY TIME 11 4 5 BATTERY CHARGING TIME 11 4 6 OPERATION WITHOUT A BATTERY 11 5 REMOTE MONITORING OPTION WI FI ETHERNET RS485 USB 12 5 1 COMMUNICATION IN WI FI WIRELESS NETWORK 12 5 2 COMMUNIC...

Page 3: ...OVL acoustic indication of failure adjustable times indicating AC power failure technical inputs outputs with galvanic isolation collective failure input EXT IN EPS technical output indicating AC powe...

Page 4: ...ource are reported to the Alarm Receiving Centre ARC in accordance with 9 2 PN EN 50131 1 Output voltage 0 28A 1 5A battery charge General use if the PSU is not mounted within an installation which is...

Page 5: ...isted operation 5 pin activation of the acoustic indication indication on indication off Caption jumper on jumper off 6 VADJ potentiometer DC voltage adjustment 7 BUZER acoustic indicator 8 FBAT fuse...

Page 6: ...L N 230V AC power connector PE connector 6 Battery connectors positive BAT red negative BAT black 7 Grip of tamper resistance Fig 3 The view of the PSU 3 Operating status indication 3 1 Control panel...

Page 7: ...LED indicates battery failure green LED indicates power at the AUX output of the PSU three yellow LEDs indicate battery charging level Fig 5 Menu of the display FLt PSU fault memo 30 last events Io A...

Page 8: ...tion Battery fault undercharged battery 3 2 signals per 10s battery assisted operation Low level of battery charge 4 Fast signals battery assisted operation The PSU will be disconnected due to the bat...

Page 9: ...l If voltage appears at the EXT IN input it will cause generating a PSU failure storing the information about the event in the internal memo and sending the signal about the failure to the PSU FLT out...

Page 10: ...is removed Caution Deactivating of the UVP function is not recommended since a deep discharge of the battery limits its capability of storing energy lowers its capacity and shortens its durability 4...

Page 11: ...5A battery charge 4 5 Battery charging time The PSU has a battery circuit charged with direct current The current selection is done via IBAT jumpers The table below shows how long it takes to charge a...

Page 12: ...ge of wireless communication is lack of additional cords and fast development or modification of the network s structure Fig 10 WI FI communication with the use of the WI FI INTW interface 5 2 Communi...

Page 13: ...B TTL INTU needs to be used This interface allows direct connection between the computer and the PSU and it is recognisable by the operating system as a virtual COM port Fig 13 KUSB TTL communication...

Page 14: ...eneral use Io 2A 0 2A battery charge Io 1 6A 0 6A battery charge Io 1 2A 1A battery charge Io 0 7A 1 5A battery charge Output voltage setting escalation and keeping time 20ms 30ms 10ms Output voltage...

Page 15: ...an be led Convectional cooling Table 8 Operation safety Protection class PN EN 60950 1 2007 I first Protection grade PN EN 60529 2002 U IP20 Electrical strength of insulation between input network cir...

Page 16: ...s of detaching the device from the mounting surface Proper installation is one of the requirements of the PN EN 50131 6 standard Fig 15 Fixing a tamper grip 2 Connect the power cables 230Vac to L N te...

Page 17: ...ivers from damage The outputs will be battery powered The protection system is indicated by illuminating of the OVP red LED on the pcb board PSU FLT output status change into Hi Z high impedance by so...

Page 18: ...voltage 14 7V F07 ON 2 flashes ON PSU FLT Too high battery voltage Battery voltage 14V F08 ON 3 flashes ON PSU FLT Battery charging circuit failure Too low output voltage of the PSU set 13V Fault in t...

Page 19: ...ibilities to carry out the repairs or if the equipment has been conditionally accepted due to the breaking warranty terms by the claimant 7 All the services rendered by force of the warranty are carri...