QS5.241-60 Installation Manual 

 

 

 

Product Description 

The QS5.241-60 is a DIN-rail mountable DC/DC converter, which provides a floating, stabilized and 
galvanically separated SELV/PELV output voltage. 
The device is equipped with conformal coated pc-boards. 
 

Intended Use 

This device is designed for installation in an enclosure and is intended for use in rolling stock 
equipment for railway applications according to EN 50155 or for use in industrial control, process 
control, monitoring and measurement equipment or the like. Do not use this device in equipment, 
where malfunction may cause severe personal injury or threaten human life. 
 

Installation Instructions 

Install device in an enclosure providing protection against electrical, mechanical and fire hazards. 
Install the device onto a DIN-rail according to EN 60715 with the input terminals on the bottom of the 
device. Other mounting orientations require a reduction in output current. 
Make sure that the wiring is correct by following all local and national codes. Use appropriate copper 
cables that are designed for a minimum operating temperature of 60°C for ambient temperatures up to 
+45°C, 75°C for ambient temperatures up to +60°C and 90°C for ambient temperatures up to +70°C. 
Ensure that all strands of a stranded wire enter the terminal connection. 
The device is designed for pollution degree 2 areas in controlled environments. No condensation or 
frost allowed. 
The enclosure of the device provides a degree of protection of IP20. 
The device is designed as “Class of Protection I” equipment according to IEC 61140. 
Do not use without a proper PE (Protective Earth) connection. 
The device can be powered from a regulated power supply or a similar DC source. The voltage 
between the supply voltage terminals and ground must not exceed 375Vdc continuously.  
A disconnecting means shall be provided for the input of the device. 
The device is designed for convection cooling and does not require an external fan. Do not obstruct 
airflow and do not cover ventilation grid! 
The device is designed for altitudes up to 6000m (19685ft). See additional requirements in the product 
datasheet for use above 2000m (6560ft). 
Keep the following minimum installation clearances: 40mm on top, 20mm on the bottom, 5mm left and 
right side. Increase the 5mm to 15mm in case the adjacent device is a heat source. When the device 
is permanently loaded with less than 50%, the 5mm can be reduced to zero. 
The device is designed, tested and approved for branch circuits up to 30A (UL) and 32A (IEC) without 
additional protection device. If an external fuse is utilized, do not use circuit breakers smaller than 6A 
B- or C-Characteristic to avoid a nuisance tripping of the circuit breaker. 
The maximum surrounding air temperature is +85°C (+185°F). The operational temperature is the 
same as the ambient or surrounding air temperature and is defined 2cm below the device. 
The device is designed to operate in areas between 5% and 95% relative humidity. 
Check for correct supply voltage polarity. The device will not operate when the voltage is reversed. 
 

Functional Description 

The output is electronically protected against no-load, overload and short circuit and can supply any 
kind of loads, including unlimited inductive loads and capacitive loads. 
Do not apply return voltages from the load to the output terminals higher than 35V. 
The output voltage can be adjusted with a small flat-blade screwdriver behind the flap on the front. 
The green DC-OK LED reports an output voltage above 90% of the adjusted voltage of a running 
device. 
The DC-OK relay monitors the output voltage and the contact is closed when the DC-OK LED is on. 
Contact ratings: 60Vdc 0.3A, 30Vdc 1A, 30Vac 0.5A for resistive loads. 
The red overload LED is on, when the output voltage falls below 90% of the adjusted value or in case 
of a short circuit in the output. The LED is flashing, when the device has switched off due to over-
temperature. Input voltage is required. 
The device is equipped with an over-temperature protection. In case of a high temperature, the output 
shuts down and starts automatically again after cooling off. 
The device is designed to deliver 6.3A output current for up to 4s with nominal output voltage. 
Devices can be paralleled to increase the output power. The output voltage shall be adjusted to the 
same value (±100mV) with the same load conditions on all devices, or the devices can be left with the 
factory settings. The ambient temperature is not allowed to 60°C. If more than three devices 
are connected in parallel, a diode, fuse or circuit breaker with a rating of 10A is required on each 
output. 
Same devices can be connected in series for higher output voltages. It is allowed to connect as many 
devices in series as needed, providing the sum of the output voltage does not exceed 150Vdc. 
In case of an internal defect, a redundant circuit limits the maximum output voltage to 36V. The output 
shuts down and automatically attempts to restart. 

 

Technical Data

 

All values are typical figures specified at 110Vdc input voltage, 24V 4.2A 
output, 25°C ambient temperature and after a 5 minutes run-in time unless 
otherwise noted. 

Output voltage 

DC 24V 

Nominal 

Adjustment range 

24 – 28Vdc 

Factory setting 24.1V 

Output current 

Continuous: 

 

4.2 – 3.6A 

Below +70°C ambient  

 

Short-term, up to 4s: 

 

6.3 – 5.4A 

Below +70°C ambient 

 

Short-term, up to10 minutes: 

 

4.2 – 3.6A 

Below +85°C ambient 

Input voltage DC 

DC 110V 

-30% / +40% 

Input voltage range 

77 - 154Vdc 

 

Input current DC 

1.0A  

Input inrush current 

10A pk 

Temp. independent 

Efficiency 

91.1%  

Power losses 

9.8W  

Hold-up time 

42ms  

Temperature range 

-25 to +85°C 

 

Max. wire size (litz wire) 

4mm² Input 

terminals 

Wire size AWG 

AWG 20-10 

Input terminals 

Max. wire diameter 

2.8mm Input 

terminals 

Wire stripping length 

10mm / 0.4inch 

Input terminals 

Max. wire size (litz wire) 

2.5mm² Output/DC-OK 

terminals

Wire size AWG 

AWG 26-12 

Output/DC-OK terminals

Max. wire diameter 

2.3mm Output/DC-OK 

terminals

Wire stripping length 

6mm / 0.25inch 

Output/DC-OK terminals

Size (wxhxd) 

40x124x117mm Without 

DIN-rail 

Weight 

640g / 1.41lb 

 

 
 

Functional Diagram 

+

+

-
-

DC-OK
contact

Output

Over-

Voltage

Protection

Boost

Converter

Output

Voltage

Regulator

Output

Filter

DC-ok
Relay

Output

Voltage
Monitor

Output

Power

Manager

Temper-

ature

Shut-

down

DC-OK

LED

Input Fuse
Input Filter
Active
Inrush
Limiter

Power

Converter

+

-

V

OUT

13

14

Reverse

Polarity

&

Back-

feeding

Protection

Overload

LED

 
 

Output Characteristic 

Output voltage

10A

24V

Output current

12V

0V

2A

4A

6A

8A

0A

Adjustment range

28V

A: continuous
B: up to 4s

A

B

 

 
 

Temperature Range 

Allowed output current at 24V

Ambient temperature

2A

0A

-25°C

A: continuous
B: up to 4s
C: up to 10 minutes

6A

+25°C

0°C

+50°C

+70°C

+85°C

4A

4.2A

6.3A

A

C

B

 

 