POE.8AT-AC1 Installation Manual 

 

 

 

Product Description 

The POE.8AT-AC1 is a DIN-rail mountable single-phase-input power supply, which provides power for 
Power over Ethernet (PoE) applications. It injects power to 8 individual PoE channels (IEEE 802.3at) 
via RJ45 Ethernet ports. 
 

Intended Use 

This device is designed for installation in an enclosure and is intended for commercial use, such as in 
industrial control, process control, monitoring and measurement equipment or the like. Do not use this 
device in equipment where malfunction may cause severe personal injury or threaten human life. 
 

Installation Instructions 

Install device in an enclosure providing protection against electrical, mechanical and fire hazards. 
Install the device onto a DIN-rail according to EN 60715 with the input terminals on the bottom of the 
device. 
Make sure that the wiring is correct by following all local and national codes. Use appropriate copper 
cables that are designed for a minimum operating temperature of 60°C for ambient temperatures up to 
+45°C, 75°C for ambient temperatures up to +60°C and 90°C for ambient temperatures up to +70°C. 
Ensure that all strands of a stranded wire enter the terminal connection. Use ferrules for wires on the 
input terminals. Unused screw terminals should be securely tightened. Use shielded twisted pair 
Ethernet cables specified for usage in IEEE 802.3at. 
The device is designed for pollution degree 2 areas in controlled environments. No condensation or 
frost is allowed. 
The enclosure of the device provides a degree of protection of IP20. The enclosure does not provide 
protection against spilled liquids. 
The isolation of the device is designed to withstand impulse voltages of overvoltage category III 
according to IEC 60664-1. 
The device is designed as “Class of Protection I” equipment according to IEC 61140. Do not use 
without a proper PE (Protective Earth) connection. 
The device is suitable to be supplied from TN, TT or IT mains networks. The continuous voltage 
between the input terminal and the PE potential must not exceed 300Vac. 
The input can also be powered from batteries or similar DC sources. The continuous voltage between 
the supply voltage and the PE/ground potential must not exceed 375Vdc. 
A disconnecting means shall be provided for the input of the device. 
The device is designed for convection cooling and does not require an external fan. Do not obstruct 
airflow and do not cover ventilation grid! 
The device is designed for altitudes up to 2000m (6560ft). 
Keep the following minimum installation clearances: 40mm on top, 20mm on the bottom, 5mm left and 
right side. Increase the 5mm to 15mm in case the adjacent device is a heat source. When the device 
is permanently loaded with less than 50%, the 5mm can be reduced to zero. 
The device is designed, tested and approved for branch circuits up to 20A without additional protection 
device. If an external fuse is utilized, do not use circuit breakers smaller than 6A B- or C-Characteristic 
to avoid a nuisance tripping of the circuit breaker. 
The maximum surrounding air temperature is +70°C (+158°F). The operational temperature is the 
same as the ambient or surrounding air temperature and is defined 2cm below the device. 
The device is designed to operate in areas between 5% and 95% relative humidity. 
Do not plug or unplug the device as long as input voltage is present. 
Do not unplug the connectors more often than 20 times in total. 
 

Functional Description 

The output is electronically protected against no-load, overload and short circuit and can supply any 
kind of loads according to IEEE 802.3at. 
Do not apply return voltages from the load to the output terminals higher than 56V. 
The output voltage can be adjusted with a small flat-blade screwdriver on the front of the unit. 
The green DC-OK LED reports an output voltage above 90% of the adjusted voltage of a running 
device. 
The DC-OK relay monitors the output voltage and the contact is closed when the DC-OK LED is on. 
Contact ratings: 60Vdc 0.3A, 30Vdc 1A, 30Vac 0.5A for resistive loads. 
The device is equipped with an over-current protection for each PoE output channel. If the current 
exceeds the output current limitation value, the affected PoE channel will be switched off. Unplug the 
affected channel for at least 2s. If the over-current is cleared, the device will operate normally again. 
The device is equipped with an over-temperature protection. In case of a high temperature, the output 
shuts down and starts automatically again after cooling off. 
In case of an internal defect, a redundant circuit limits the maximum output voltage to 60V. The output 
shuts down and automatically attempts to restart. 
The device detects connected PoE loads automatically and will not power connected non-PoE devices 
according to IEEE 802.3at. 

 

Technical Data

 

All values are typical figures specified at 230Vac 50Hz input voltage, 56V 
8x 30W output load, 25°C ambient temperature and after a 5 minutes run-
in time unless otherwise noted. 

Output voltage 

DC 48V 

Nominal 

Adjustment range 

48 – 56Vdc 

Factory setting 56V 

RJ45 Output channels 

8x 30W 

Below +60°C ambient  

 

8x 22.5W 

At +70°C ambient 

 

Derate linearly b60°C and +70°C 

Output current limitation 

0.63A 

Below +60°C ambient  

 

0.47A At 

+70°C 

ambient 

Input voltage AC 

AC 100 - 240V 

-15% / +10% 

Mains frequency 

50 – 60Hz 

±6% 

Input current AC 

2.15 / 1.13A 

At 120 / 230Vac 

Power factor 

0.99 / 0.97 

At 120 / 230Vac 

Input voltage DC 

DC 110 - 150V 

±20% 

Input current DC 

2.35A At 

110Vdc 

Input inrush current 

6 / 9A pk 

At 40°C, 120 / 230Vac 

Efficiency 

93.8 / 95.5% 

At 120 / 230Vac 

Power losses 

15.9 / 11.3W 

At 120 / 230Vac 

Hold-up time 

37 / 37ms 

At 120 / 230Vac 

Temperature range 

-25 to +70°C 

 

Max. wire size (litz wire) 

2.5mm² Input 

terminals 

Wire size AWG 

AWG 20-12 

Input terminals 

Maximum wire diameter 

2.4mm Input 

terminals 

Wire stripping length

 

 

7mm / 0.28inch 

Input terminals 

Tightening torque 

0.5Nm / 4.5lb.inch Input terminals 

Max. wire size (litz wire) 

1.5mm²

 

 DC-OK 

terminals 

Wire size AWG 

AWG 24-16 

DC-OK terminals 

Maximal wire diameter 

1.8 mm 

DC-OK terminals 

Wire stripping length 

6mm / 0.25inch 

DC-OK terminals 

Tightening torque 

0.8Nm / 7lb.inch 

DC-OK terminals 

Size (wxhxd) 

77x128x117mm Without 

DIN-rail 

Weight 

900g / 1.98lb 

 

 
 

Functional Diagram 

Output

Over-

Voltage

Protection

PFC

Converter

Voltage

Regulator

Power

Converter

Output

Power

Manager

Temper-

ature

Shut-

down

Input Fuse
Input Filter
Input Rectifier
Inrush Current
Limiter

V

OUT

L

N

DC-OK
Contact

DC-OK

LED

13

14

Ch1

Ch2

Ch3

Ch8

PoE

Power Injector

PoE

Output

Channels

Ch1

Ch2

Ch3

Ch8

PoE
Input
Channels

..

.

..

.

..

.

..

.

Power

Conditioning

DC-ok
Relay

Output

Filter

..

.

 
 

Temperature Range 

Allowed output power

Ambient temperature

0A

-25

8x 30W

0

+60 +70°C

8x 22.5W

 

 