Puls PIM60.121 Manual Download Page 9

PIM60.121

Feb. 2022 / Rev. 2.0 DS-PIM60.121-EN

www.pulspower.com

9 / 17

All parameters are specified at 24V, 5A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.

9.

Lifetime Expectancy

The  Lifetime  expectancy  shown  in  the  table  indicates  the  minimum  operating  hours  (service  life)  and  is  determined  by
the lifetime expectancy of the built-in electrolytic capacitors. Lifetime expectancy is specified in operational hours and is
calculated according to the capacitor’s manufacturer specification.

Please note: The manufacturer of the electrolytic capacitors only guarantees a maximum life of up to 15 years (131 400h).
Any number exceeding this value is a calculated theoretical lifetime which can be used to compare devices.

AC 100V

AC 120V

AC 230V

Lifetime expectancy

89 000h

103 000h

119 000h

At 12V, 5A and 40°C

241 000h

249 000h

256 000h

At 12V, 2.5A and 40°C

252 000h

292 000h

335 000h

At 12V, 5A and 25°C

680 000h

704 000h

724 000h

At 12V, 2.5A and 25°C

10. MTBF

MTBF  stands  for  Mean  Time  Between  Failure,  which  is  calculated  according  to  statistical  device  failures,  and  indicates
reliability of a device. It is the statistical representation of the likelihood of a unit to fail and does not necessarily represent
the life of a product.

The MTBF figure is a statistical representation of the likelihood of a device to fail. A MTBF figure of e.g. 1 000 000h means
that statistically one unit will fail every 100 hours if 10 000 units are installed in the field. However, it cannot be determined
if the failed unit has been running for 50 000h or only for 100h.

For these types of units the MTTF (Mean Time TFailure) value is the same value as the MTBF value.

AC 100V

AC 120V

AC 230V

MTBF SN 29500, IEC 61709

1 542 000h

1 649 000h

1 673 000h

At 12V, 5A and 40°C

2 768 000h

2 911 000h

2 925 000h

At 12V, 5A and 25°C

MTBF MIL HDBK 217F

695 000h

707 000h

685 000h

At 12V, 5A and 40°C; Ground Benign GB40

993 000h

1 008 000h

982 000h

At 12V, 5A and 25°C; Ground Benign GB25

189 000h

192 000h

197 000h

At 12V, 5A and 40°C; Ground Fixed GF40

246 000h

250 000h

258 000h

At 12V, 5A and 25°C; Ground Fixed GF25

Summary of Contents for PIM60.121

Page 1: ...surrounding temperatures up to 70 C The unit is designed as Class of Protection II unit and fulfills the safety and EMC requirements without an input PE connection This saves wiring costs The PIANO fa...

Page 2: ...tly changing the information in this data sheet is subject to revision We therefore kindly ask you to always use the latest issue of this document available under www pulspower com No part of this doc...

Page 3: ...th the input terminals on the bottom of the device Make sure that the wiring is correct by following all local and national codes Use appropriate copper cables that are designed for a minimum operatin...

Page 4: ...ee Fig 3 1 Shut down voltage typ 54Vac Steady state value see Fig 3 1 External input protection See recommendations in chapter 2 AC 100V AC 120V AC 230V Input current typ 1 15A 1A 0 6A At 12V 5A see F...

Page 5: ...pact on the inrush current value The charging current into EMI suppression capacitors is disregarded in the first microseconds after switch on AC 100V AC 120V AC 230V typ 12A 15A 36A At 40 C ambient c...

Page 6: ...ed value which can be achieved Factory settings typ 12V 0 2 at full load cold unit Line regulation max 10mV Between 90 and 300Vac Load regulation max 100mV Between 0 and 5A static value see Fig 6 1 Ri...

Page 7: ...oltage remains within specification following the loss of input power The hold up time is output load dependent At no load the hold up time can be up to several seconds The green DC OK LED is also on...

Page 8: ...W 0 2W 0 3W At no load typ 3 6W 3 4W 3 4W At 12V 2 5A half load typ 7 5W 6 5W 6 2W At 12V 5A full load The average efficiency is an assumption for a typical application where the device is loaded with...

Page 9: ...At 12V 2 5A and 25 C 10 MTBF MTBF stands for Mean Time Between Failure which is calculated according to statistical device failures and indicates reliability of a device It is the statistical represen...

Page 10: ...1 1 Functional diagram 12 Terminals And Wiring The terminals are IP20 Finger safe constructed and suitable for field and factory wiring All Terminals Type Push in terminals Solid wire max 2 5mm2 Stran...

Page 11: ...e noted 13 Front Side And User Elements A Input Terminals N Neutral conductor input L Phase Line input B OutputTerminals Dual terminals for the negative and positive pole Both poles are internally con...

Page 12: ...terion A Conducted disturbance EN 61000 4 6 0 15 80MHz 10V Criterion A Voltage dips EN 61000 4 11 0 of 100Vac 0Vac 20ms Criterion A C 40 of 100Vac 40Vac 200ms Criterion C 70 of 100Vac 70Vac 500ms Crit...

Page 13: ...the derated current limits in order not to overload the unit Humidity 5 to 95 r h According to IEC 60068 2 30 No condensation allowed Atmospheric pressure 110 54kPa See Fig 15 2 for details Altitude U...

Page 14: ...ns IT mains typ 100 A 200 A At 230Vac 50Hz TN TT mains IT mains max 60 A 100 A At 110Vac 50Hz TN TT mains IT mains max 80 A 150 A At 132Vac 60Hz TN TT mains IT mains Touch current leakage current max...

Page 15: ...s for supply voltages up to 1100V Particular requirements and tests for switch mode power supply units and transformers for switch mode power supply units ISA 71 04 1985 Manufacturer s Declaration Onl...

Page 16: ...ight Width 36mm 1 42 Height 90mm 3 54 Depth 91mm 3 58 The DIN rail height must be added to the unit depth to calculate the total required installation depth Weight 225g 0 5lb DIN rail Use 35mm DIN rai...

Page 17: ...DANCY Do not use this device to build redundant systems since there is no monitoring DC OK signal included 21 5 TWO PHASE OPERATION The power supply can also be operated on two phases of a three phase...

Reviews: