PIM36.241
Feb. 2022 / Rev. 2.0 DS-PIM36.241-EN
www.pulspower.com
15 / 17
All parameters are specified at 24V, 1.5A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
18. Approved, Fulfilled or Tested Standards
IEC 61010
CB Scheme Certificate
IEC 61010-2-201 - Electrical Equipment for Measurement, Control and
Laboratory Use - Particular requirements for control equipment
IEC 62368
CB Scheme Certificate
IEC 62368-1 - Audio/video, information and communication
technology equipment - Safety requirements
Output safety level: ES1
UL 61010
UL Certificate
Listed equipment for category NMTR - UL 61010-2-201 - Electrical
equipment for measurement, control and laboratory use - Particular
requirements for control equipment
Applicable for US and Canada
E-File: E198865
NEC Class 2
UL Certificate
Limited Power Source
Listed in the UL 61010-2-201 approval report, investigated according
to UL 1310
ISA-71.04-1985
Manufacturer's Declaration (Online Document)
Airborne Contaminants Corrosion Test
Severity Level: G3 Harsh
H2S: 100ppb
NOx: 1250ppb
Cl2: 20ppb
SO2: 300ppb
Test Duration: 3 weeks, which simulates a service life of at least 10
years
VDMA 24364
Paint Wetting Impairment Substances Test (or LABS-Test)
Tested for Zone 2 and Test Class C1 according to VDMA 24364-C1-L/W
for solvents and water-based paints
19. Regulatory Product Compliance
EU Declaration of
Conformity
The CE mark indicates conformance with the European
– EMC directive
– Low-voltage directive (LVD)
– RoHS directive
REACH Regulation
Manufacturer's Declaration
EU Regulation regarding the Registration, Evaluation, Authorization
and Restriction of Chemicals
EU Regulation 1907/2006
WEEE Regulation
Manufacturer's Declaration
EU Directive on Waste Electrical and Electronic Equipment Registered
in Germany as business to business (B2B) products.
EU Directive 2012/19/EU
RoHS (China RoHS 2)
Manufacturer's Statement
Administrative Measures for the Restriction of the Use of Hazardous
Substances in Electrical and Electronic Products 25 years