PIM36.241
Feb. 2022 / Rev. 2.0 DS-PIM36.241-EN
www.pulspower.com
8 / 17
All parameters are specified at 24V, 1.5A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
8.
Efficiency and Power Losses
AC 100V
AC 120V
AC 230V
Efficiency
typ.
89.4%
90.5%
90.6%
At 24V, 1.5A (full load)
Average efficiency
typ.
89%
89.6%
88.2%
25% at 0.38A, 25% at 0.75A,
25% at 1.13A, 25% at 1.5A
Power losses
typ.
0.25W
0.25W
0.4W
At no load
typ.
2.2W
2.1W
2.4W
At 24V, 0.75A (half load)
typ.
4.3W
3.8W
3.7W
At 24V, 1.5A (full load)
The average efficiency is an assumption for a typical application where the device is loaded with 25% of the nominal
load for 25% of the time, 50% of the nominal load for another 25% of the time, 75% of the nominal load for another
25% of the time and with 100% of the nominal load for the rest of the time.
Fig. 8-1: Efficiency vs. output current at 24V, typ.
Fig. 8-2: Losses vs. output current at 24V, typ.
Fig. 8-3: Efficiency vs. input voltage at 24V, 1.5A, typ.
Fig. 8-4: Losses vs. input voltage at 24V, 1.5A, typ.